FXFRQ140AVM is a Daikin indoor unit in the FXFRQ-A series, cassette round flow with streamer type. Its rated cooling capacity is 16 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 16 kW
- Power supply
- 1-phase, 220-240 V/220-230 V, 50/60 Hz
- Dimensions (H×W×D)
- 298×840×840 mm
- Weight
- 26 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FXFRQ140AVM specifications
| Rated capacity 4 specifications | |
|---|---|
| Cooling capacity · Btu/h | 54,600 |
| Cooling capacity · kW | 16.0 |
| Heating capacity · Btu/h | 54,600 |
| Heating capacity · kW | 16.0 |
| Electrical & efficiency 3 specifications | |
| Power supply | 1-phase, 220-240 V/220-230 V, 50/60 Hz |
| Power consumption · Cooling · kW | 0.203 |
| Power consumption · Heating · kW | 0.191 |
| Airflow & sound 3 specifications | |
| Airflow rate (H/HM/M/ML/L) · m3/min | 35.5/32.5/29.5/26.5/23 |
| Airflow rate (H/HM/M/ML/L) · cfm | 1,253/1,147/1,041/935/812 |
| Sound level (H/HM/M/ML/L) · dB(A) | 46/43.5/40.5/38/35 |
| Dimensions & weight 3 specifications | |
| Casing | Galvanised steel plate |
| Dimensions (H×W×D) · mm | 298×840×840 |
| Machine weight · kg | 26 |
| Piping & refrigerant 3 specifications | |
| Piping connections · Liquid (Flare) · mm | 9.5 |
| Piping connections · Gas (Flare) · mm | 15.9 |
| Piping connections · Drain · mm | VP25 (External Dia. 32/Internal Dia. 25) |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 189 (printed page 188). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Panel (Option) Function List
Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Wired remote controller BRC1H63W(K)
Standard
panel Dimensions(H×W×D) mm 50×950×950 Streamer function unit
Weight kg 5.5 Individual airflow direction control
Model BYCQ125EAPF (Fresh White) Switchable 5 step fan speed
Designer
panel Dimensions(H×W×D) mm 97×950×950 Auto airflow rate
Weight kg 6.5 Auto swing
Auto Model BYCQ125EBSF (Fresh White) High ceiling application
grille Dimensions(H×W×D) mm 105×950×950
panel
Weight kg 8
stinU
roodnI
188
View catalogue page · PDF 189
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 189
VRV Indoor Units
Decoration Panel (Option)
Standard panel
Auto grille panel
Grille and air filter cleaning can be performed
without need for a stepladder by lowering the
grille.
Standard panel Standard panel A dedicated remote controller for the auto grille panel is included.
BYCQ125EAF (Fresh White) BYCQ125EAK (Black)
New designer panel
Designer choice has been given a boost with the
increase in number of new types of decoration panels.
FLAT
Flatter styling:
Suction panel grid
texture smoothed.
Designer panel CLEAN
BYCQ125EAPF (Fresh White) Soilin C g l e is a h n a -c r u d t t f o o r s m ee : Wireless
on smart-looking panel. Remote
Controller
Grille panel can be lowered
Close to ideal styling
ROUND to a maximum of 3.9 m.
New designer panel
Subtle distinction: BYCQ125EBSF (Fresh White)
around suction inlets
silvering is a tasteful touch.
Specifications
MODEL FXFRQ25AVM FXFRQ32AVM FXFRQ40AVM FXFRQ50AVM FXFRQ63AVM FXFRQ80AVM FXFRQ100AVM FXFRQ125AVM FXFRQ140AVM
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 42,700 47,800 54,600 Heating capacity
kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 14.0 16.0
Cooling 0.029 0.036 0.040 0.063 0.096 0.158 0.178 0.203
Power consumption kW
Heating 0.027 0.036 0.040 0.063 0.096 0.150 0.166 0.191
Casing Galvanised steel plate
m3/min 13/12.5/11.5/11/10 17/13.5/13/12/11 18/17/13.5/12.5/11 21/20/16/15/13.5 22.5/21.5/21/20/15 32/29/26/23/21 33/30.5/28/25.5/21 35.5/32.5/29.5/26.5/23
Airflow rate (H/HM/M/ML/L)
cfm 459/441/406/388/353 600/477/459/424/388 635/600/477/441/388 741/706/565/530/477 794/759/741/706/530 1,130/1,024/918/812/7411,165/1,077/988/900/7411,253/1,147/1,041/935/812
Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 35/33.5/29.5/28.5/27 36/35.5/31.5/31/28 37/36.5/36/35.5/29.5 43/40.5/37.5/35/33 44/41.5/39/36.5/33 46/43.5/40.5/38/35
Dimensions (H×W×D) mm 256×840×840 298×840×840
Machine weight kg 19 22 25 26
Liquid (Flare) 6.4 9.5
Piping
connections Gas (Flare) mm 12.7 15.9
Drain VP25 (External Dia. 32/Internal Dia. 25)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Panel (Option) Function List
Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Wired remote controller BRC1H63W(K)
Standard
panel Dimensions(H×W×D) mm 50×950×950 Streamer function unit
Weight kg 5.5 Individual airflow direction control
Model BYCQ125EAPF (Fresh White) Switchable 5 step fan speed
Designer
panel Dimensions(H×W×D) mm 97×950×950 Auto airflow rate
Weight kg 6.5 Auto swing
Auto Model BYCQ125EBSF (Fresh White) High ceiling application
grille Dimensions(H×W×D) mm 105×950×950
panel
Weight kg 8
stinU
roodnI
188
FACING PAGE — PDF page 188
Round Flow Cassette with Streamer Type
Individual airflow direction control
Comfortable air conditioning for all room layouts and conditions
Easy setting is possible with a wired remote controller
Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air
distribution.
Individual airflow settings Position 0 No individual setting
No individual setting (Fixed airflow to (Auto airflow)
(Auto airflow) highest position)
Position 0 (Highest point)
Position 1
Position 2
Position 3
Swing Position 4
Position 4 (Lowest point)
(Up/down) (Fixed airflow to the lowest position)
Swing
Individual settings are possible as stated above.
Swing No individual setting (Auto airflow)
Swing is set for
meetings near Position 0
the windows. The airflow is at the Comfort is provided to the entire room
highest setting
Large blow is (Position 0) for people by individual setting corresponding to 4-way
provided to who dislike air blowing
meeting areas directly on them. flow conditions.
near windows.
Blow reduced for areas
No individual setting (Auto airflow)
with few people.
Other functions
Quick and easy installation No individual
setting
Installable in tight ceiling spaces 850 mm (Auto airflow)
175 mm
Min. of 261 mm* ceiling space when using standard panel.
* For FXFRQ25-80A models.
Drain pump is equipped as standard accessory with 850 mm lift.
Easy maintenance
Just open the suction grille!
Drain pan and drain water check
Drain outlet
The condition of the drain pan and drain water can be (with rubber plug)
checked by removing the suction grille and drain plug.
Cleanliness
Silver ion anti-bacterial drain pan
Prevents the growth of slime, bacteria, and mould that cause
odours and clogging.
* Drain pan should be changed once every two to three years.
Filter has anti-mould and antibacterial treatment
BAF552A160
High Performance Prefilter (MERV 8) (Option) See page 296
This filter can catch more harmful substances in the air such as PM2.5.
187
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗