TECHNICAL SPECIFICATION SHEET · DAIKIN
FXFRQ140AVM
Indoor unit · FXFRQ-A · Cassette Round Flow with Streamer
Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.
| Rated capacity | |
|---|---|
| Cooling capacity · Btu/h | 54,600 |
| Cooling capacity · kW | 16.0 |
| Heating capacity · Btu/h | 54,600 |
| Heating capacity · kW | 16.0 |
| Electrical & efficiency | |
| Power supply | 1-phase, 220-240 V/220-230 V, 50/60 Hz |
| Power consumption · Cooling · kW | 0.203 |
| Power consumption · Heating · kW | 0.191 |
| Airflow & sound | |
| Airflow rate (H/HM/M/ML/L) · m3/min | 35.5/32.5/29.5/26.5/23 |
| Airflow rate (H/HM/M/ML/L) · cfm | 1,253/1,147/1,041/935/812 |
| Sound level (H/HM/M/ML/L) · dB(A) | 46/43.5/40.5/38/35 |
| Dimensions & weight | |
| Casing | Galvanised steel plate |
| Dimensions (H×W×D) · mm | 298×840×840 |
| Machine weight · kg | 26 |
| Piping & refrigerant | |
| Piping connections · Liquid (Flare) · mm | 9.5 |
| Piping connections · Gas (Flare) · mm | 15.9 |
| Piping connections · Drain · mm | VP25 (External Dia. 32/Internal Dia. 25) |
Source reference
PCVVN2507Aaprv · PDF page 189 · Printed page 188
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)
Open catalogue PDF · page 189
Model page: https://vrv.vn/spec/fxfrq140avm/
Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.
Original source notes
Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Panel (Option) Function List Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Wired remote controller BRC1H63W(K) Standard panel Dimensions(H×W×D) mm 50×950×950 Streamer function unit Weight kg 5.5 Individual airflow direction control Model BYCQ125EAPF (Fresh White) Switchable 5 step fan speed Designer panel Dimensions(H×W×D) mm 97×950×950 Auto airflow rate Weight kg 6.5 Auto swing Auto Model BYCQ125EBSF (Fresh White) High ceiling application grille Dimensions(H×W×D) mm 105×950×950 panel Weight kg 8 stinU roodnI 188