VAM800HVE is a Daikin heat recovery ventilation unit. Airflow at high speed (50/60 Hz): 800/800 m³/h according to catalogue VN-PCXDHMT2111A.
- Airflow at high speed (50/60 Hz)
- 800/800 m³/h
- Power supply
- 1 phase, 220–240 V / 220 V, 50/60 Hz
- Dimensions (H×W×D)
- 387×1,012×1,110 mm
- Weight
- 63 kg
Product overview VAM800HVE
VAM800HVE is a Daikin other equipment in the VAM-HVE series (Heat recovery ventilation unit).
Application and design
The unit supplies outdoor air and exhausts indoor air through a total heat exchanger. Check airflow, static pressure and sound by fan speed and supply frequency.
Catalogue performance
- Airflow at high speed (50/60 Hz)
- 800/800 m³/h
- External static pressure at extra high speed (50/60 Hz) · Pa
- 210–235/250
- Sound level · Heat exchange, extra high (50/60 Hz) · dB(A)
- 41.5–42.5/41.0
Configuration and installation
- Power supply
- 1 phase, 220–240 V / 220 V, 50/60 Hz
- Dimensions (H×W×D) · mm
- 387×1,012×1,110
- Weight · kg
- 63
Checking a specification or quotation
Select the fan speed for the duct system operating point. Check the duct connection sizes and access for servicing the heat exchanger.
Check catalogue rating conditions and connection arrangements when selecting equipment.
VAM800HVE specifications
| System configuration 2 specifications | |
|---|---|
| Heat exchange system | Counterflow total heat exchange (latent and sensible) |
| Heat exchange medium | Non-flammable paper |
| Electrical & efficiency 20 specifications | |
| Power supply | 1 phase, 220–240 V / 220 V, 50/60 Hz |
| Temperature exchange efficiency · Cooling, extra high (50/60 Hz) · % | 61.5/61.5 |
| Temperature exchange efficiency · Cooling, high (50/60 Hz) · % | 61.5/61.5 |
| Temperature exchange efficiency · Cooling, low (50/60 Hz) · % | 64.0/65.0 |
| Temperature exchange efficiency · Heating, extra high (50/60 Hz) · % | 77.5/77.5 |
| Temperature exchange efficiency · Heating, high (50/60 Hz) · % | 77.5/77.5 |
| Temperature exchange efficiency · Heating, low (50/60 Hz) · % | 78.5/79.5 |
| Enthalpy exchange efficiency · Cooling, extra high (50/60 Hz) · % | 63.0/63.0 |
| Enthalpy exchange efficiency · Cooling, high (50/60 Hz) · % | 63.0/63.0 |
| Enthalpy exchange efficiency · Cooling, low (50/60 Hz) · % | 64.5/65.5 |
| Enthalpy exchange efficiency · Heating, extra high (50/60 Hz) · % | 72.0/72.0 |
| Enthalpy exchange efficiency · Heating, high (50/60 Hz) · % | 72.0/72.0 |
| Enthalpy exchange efficiency · Heating, low (50/60 Hz) · % | 74.0/75.0 |
| Power consumption · Heat exchange, extra high (50/60 Hz) · W | 644–684/829 |
| Power consumption · Heat exchange, high (50/60 Hz) · W | 603–612/712 |
| Power consumption · Heat exchange, low (50/60 Hz) · W | 504–544/562 |
| Power consumption · Bypass, extra high (50/60 Hz) · W | 644–684/829 |
| Power consumption · Bypass, high (50/60 Hz) · W | 603–612/712 |
| Power consumption · Bypass, low (50/60 Hz) · W | 504–544/562 |
| Fan motor output · kW | 0.190 × 2 |
| Airflow & sound 14 specifications | |
| Sound level · Heat exchange, extra high (50/60 Hz) · dB(A) | 41.5–42.5/41.0 |
| Sound level · Heat exchange, high (50/60 Hz) · dB(A) | 39.5–41.0/37.0 |
| Sound level · Heat exchange, low (50/60 Hz) · dB(A) | 36.0–38.5/33.0 |
| Sound level · Bypass, extra high (50/60 Hz) · dB(A) | 41.5–42.5/41.0 |
| Sound level · Bypass, high (50/60 Hz) · dB(A) | 39.5–41.0/37.0 |
| Sound level · Bypass, low (50/60 Hz) · dB(A) | 36.0–38.5/33.0 |
| Fan type | Sirocco fan |
| Airflow at extra high speed (50/60 Hz) · m³/h | 800/800 |
| External static pressure at extra high speed (50/60 Hz) · Pa | 210–235/250 |
| Airflow at high speed (50/60 Hz) · m³/h | 800/800 |
| External static pressure at high speed (50/60 Hz) · Pa | 170–215/140 |
| Airflow at low speed (50/60 Hz) · m³/h | 720/610 |
| External static pressure at low speed (50/60 Hz) · Pa | 138–174/81 |
| Effective supply airflow ratio, extra high · % | 90 |
| Dimensions & weight 4 specifications | |
| Casing | Galvanized steel |
| Insulation | Non-flammable polyurethane foam |
| Dimensions (H×W×D) · mm | 387×1,012×1,110 |
| Weight · kg | 63 |
| Piping & refrigerant 2 specifications | |
| Inner duct connection · mm | Ø250 |
| Outer duct connection · mm | Ø250 |
| Operating conditions 1 specifications | |
| Ambient operating conditions | −15 to 50 °CDB, up to 80% RH |
| Filters 1 specifications | |
| Air filter | Multi-directional fibre mat |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from VN-PCXDHMT2111A, PDF page 11 (printed page 10). Vietnamese source PDF · English specifications translated from the source.
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.