VAM1000HVE is a Daikin heat recovery ventilation unit. Airflow at high speed (50/60 Hz): 1,000/1,000 m³/h according to catalogue VN-PCXDHMT2111A.

Airflow at high speed (50/60 Hz)
1,000/1,000 m³/h
Power supply
1 phase, 220–240 V / 220 V, 50/60 Hz
Dimensions (H×W×D)
387×1,012×1,110 mm
Weight
63 kg
Data based on the source catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

Product overview VAM1000HVE

VAM1000HVE is a Daikin other equipment in the VAM-HVE series (Heat recovery ventilation unit).

Application and design

The unit supplies outdoor air and exhausts indoor air through a total heat exchanger. Check airflow, static pressure and sound by fan speed and supply frequency.

Catalogue performance

Airflow at high speed (50/60 Hz)
1,000/1,000 m³/h
External static pressure at extra high speed (50/60 Hz) · Pa
205–225/220
Sound level · Heat exchange, extra high (50/60 Hz) · dB(A)
42.0–43.0/42.5

Configuration and installation

Power supply
1 phase, 220–240 V / 220 V, 50/60 Hz
Dimensions (H×W×D) · mm
387×1,012×1,110
Weight · kg
63

Checking a specification or quotation

Select the fan speed for the duct system operating point. Check the duct connection sizes and access for servicing the heat exchanger.

Check catalogue rating conditions and connection arrangements when selecting equipment.

VAM1000HVE specifications

VAM1000HVE specifications · VN-PCXDHMT2111A
System configuration 2 specifications
Heat exchange systemCounterflow total heat exchange (latent and sensible)
Heat exchange mediumNon-flammable paper
Electrical & efficiency 20 specifications
Power supply1 phase, 220–240 V / 220 V, 50/60 Hz
Temperature exchange efficiency · Cooling, extra high (50/60 Hz) · %58.0/58.0
Temperature exchange efficiency · Cooling, high (50/60 Hz) · %58.0/58.0
Temperature exchange efficiency · Cooling, low (50/60 Hz) · %61.5/62.0
Temperature exchange efficiency · Heating, extra high (50/60 Hz) · %74.0/74.0
Temperature exchange efficiency · Heating, high (50/60 Hz) · %74.0/74.0
Temperature exchange efficiency · Heating, low (50/60 Hz) · %76.0/76.5
Enthalpy exchange efficiency · Cooling, extra high (50/60 Hz) · %60.0/60.0
Enthalpy exchange efficiency · Cooling, high (50/60 Hz) · %60.0/60.0
Enthalpy exchange efficiency · Cooling, low (50/60 Hz) · %62.0/62.5
Enthalpy exchange efficiency · Heating, extra high (50/60 Hz) · %68.5/68.5
Enthalpy exchange efficiency · Heating, high (50/60 Hz) · %68.5/68.5
Enthalpy exchange efficiency · Heating, low (50/60 Hz) · %72.0/72.5
Power consumption · Heat exchange, extra high (50/60 Hz) · W683–736/883
Power consumption · Heat exchange, high (50/60 Hz) · W621–656/763
Power consumption · Heat exchange, low (50/60 Hz) · W539–569/594
Power consumption · Bypass, extra high (50/60 Hz) · W683–736/883
Power consumption · Bypass, high (50/60 Hz) · W621–656/763
Power consumption · Bypass, low (50/60 Hz) · W539–569/594
Fan motor output · kW0.190 × 2
Airflow & sound 14 specifications
Sound level · Heat exchange, extra high (50/60 Hz) · dB(A)42.0–43.0/42.5
Sound level · Heat exchange, high (50/60 Hz) · dB(A)40.0–41.0/38.0
Sound level · Heat exchange, low (50/60 Hz) · dB(A)38.0–39.5/34.5
Sound level · Bypass, extra high (50/60 Hz) · dB(A)42.0–43.0/42.5
Sound level · Bypass, high (50/60 Hz) · dB(A)40.0–41.0/38.0
Sound level · Bypass, low (50/60 Hz) · dB(A)38.0–39.5/34.5
Fan typeSirocco fan
Airflow at extra high speed (50/60 Hz) · m³/h1,000/1,000
External static pressure at extra high speed (50/60 Hz) · Pa205–225/220
Airflow at high speed (50/60 Hz) · m³/h1,000/1,000
External static pressure at high speed (50/60 Hz) · Pa155–195/100
Airflow at low speed (50/60 Hz) · m³/h880/835
External static pressure at low speed (50/60 Hz) · Pa115–150/70
Effective supply airflow ratio, extra high · %90
Dimensions & weight 4 specifications
CasingGalvanized steel
InsulationNon-flammable polyurethane foam
Dimensions (H×W×D) · mm387×1,012×1,110
Weight · kg63
Piping & refrigerant 2 specifications
Inner duct connection · mmØ250
Outer duct connection · mmØ250
Operating conditions 1 specifications
Ambient operating conditions−15 to 50 °CDB, up to 80% RH
Filters 1 specifications
Air filterMulti-directional fibre mat

Catalogue source & rating conditions

Values are taken from VN-PCXDHMT2111A, PDF page 11 (printed page 10). Vietnamese source PDF · English specifications translated from the source.

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read catalogue notes (summary)
Notes: Pairs are in 50/60 Hz order. The catalogue cites JIS B8628:2017 for heat exchange and sound testing. The reference table on PDF page 13 uses VAM-G test conditions. Use the main VAM-HVE tables on PDF pages 10–11.
View catalogue page · PDF 11

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original catalogue, PDF page 11