VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

VAM1000HVE

Other equipment · VAM-HVE · Heat recovery ventilation unit

Data based on the source catalogue; not all specifications have been manually verified. Check the original source before use.

VAM1000HVE specifications
System configuration
Heat exchange systemCounterflow total heat exchange (latent and sensible)
Heat exchange mediumNon-flammable paper
Electrical & efficiency
Power supply1 phase, 220–240 V / 220 V, 50/60 Hz
Temperature exchange efficiency · Cooling, extra high (50/60 Hz) · %58.0/58.0
Temperature exchange efficiency · Cooling, high (50/60 Hz) · %58.0/58.0
Temperature exchange efficiency · Cooling, low (50/60 Hz) · %61.5/62.0
Temperature exchange efficiency · Heating, extra high (50/60 Hz) · %74.0/74.0
Temperature exchange efficiency · Heating, high (50/60 Hz) · %74.0/74.0
Temperature exchange efficiency · Heating, low (50/60 Hz) · %76.0/76.5
Enthalpy exchange efficiency · Cooling, extra high (50/60 Hz) · %60.0/60.0
Enthalpy exchange efficiency · Cooling, high (50/60 Hz) · %60.0/60.0
Enthalpy exchange efficiency · Cooling, low (50/60 Hz) · %62.0/62.5
Enthalpy exchange efficiency · Heating, extra high (50/60 Hz) · %68.5/68.5
Enthalpy exchange efficiency · Heating, high (50/60 Hz) · %68.5/68.5
Enthalpy exchange efficiency · Heating, low (50/60 Hz) · %72.0/72.5
Power consumption · Heat exchange, extra high (50/60 Hz) · W683–736/883
Power consumption · Heat exchange, high (50/60 Hz) · W621–656/763
Power consumption · Heat exchange, low (50/60 Hz) · W539–569/594
Power consumption · Bypass, extra high (50/60 Hz) · W683–736/883
Power consumption · Bypass, high (50/60 Hz) · W621–656/763
Power consumption · Bypass, low (50/60 Hz) · W539–569/594
Fan motor output · kW0.190 × 2
Airflow & sound
Sound level · Heat exchange, extra high (50/60 Hz) · dB(A)42.0–43.0/42.5
Sound level · Heat exchange, high (50/60 Hz) · dB(A)40.0–41.0/38.0
Sound level · Heat exchange, low (50/60 Hz) · dB(A)38.0–39.5/34.5
Sound level · Bypass, extra high (50/60 Hz) · dB(A)42.0–43.0/42.5
Sound level · Bypass, high (50/60 Hz) · dB(A)40.0–41.0/38.0
Sound level · Bypass, low (50/60 Hz) · dB(A)38.0–39.5/34.5
Fan typeSirocco fan
Airflow at extra high speed (50/60 Hz) · m³/h1,000/1,000
External static pressure at extra high speed (50/60 Hz) · Pa205–225/220
Airflow at high speed (50/60 Hz) · m³/h1,000/1,000
External static pressure at high speed (50/60 Hz) · Pa155–195/100
Airflow at low speed (50/60 Hz) · m³/h880/835
External static pressure at low speed (50/60 Hz) · Pa115–150/70
Effective supply airflow ratio, extra high · %90
Dimensions & weight
CasingGalvanized steel
InsulationNon-flammable polyurethane foam
Dimensions (H×W×D) · mm387×1,012×1,110
Weight · kg63
Piping & refrigerant
Inner duct connection · mmØ250
Outer duct connection · mmØ250
Operating conditions
Ambient operating conditions−15 to 50 °CDB, up to 80% RH
Filters
Air filterMulti-directional fibre mat

Source reference

VN-PCXDHMT2111A · PDF page 11 · Printed page 10
Vietnamese source PDF · English specifications translated from the source

Open catalogue PDF · page 11
Model page: https://vrv.vn/spec/vam1000hve/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Catalogue notes (summary)

Notes: Pairs are in 50/60 Hz order. The catalogue cites JIS B8628:2017 for heat exchange and sound testing. The reference table on PDF page 13 uses VAM-G test conditions. Use the main VAM-HVE tables on PDF pages 10–11.