VAM800HVE specifications
System configuration
Heat exchange systemCounterflow total heat exchange (latent and sensible)
Heat exchange mediumNon-flammable paper
Electrical & efficiency
Power supply1 phase, 220–240 V / 220 V, 50/60 Hz
Temperature exchange efficiency · Cooling, extra high (50/60 Hz) · %61.5/61.5
Temperature exchange efficiency · Cooling, high (50/60 Hz) · %61.5/61.5
Temperature exchange efficiency · Cooling, low (50/60 Hz) · %64.0/65.0
Temperature exchange efficiency · Heating, extra high (50/60 Hz) · %77.5/77.5
Temperature exchange efficiency · Heating, high (50/60 Hz) · %77.5/77.5
Temperature exchange efficiency · Heating, low (50/60 Hz) · %78.5/79.5
Enthalpy exchange efficiency · Cooling, extra high (50/60 Hz) · %63.0/63.0
Enthalpy exchange efficiency · Cooling, high (50/60 Hz) · %63.0/63.0
Enthalpy exchange efficiency · Cooling, low (50/60 Hz) · %64.5/65.5
Enthalpy exchange efficiency · Heating, extra high (50/60 Hz) · %72.0/72.0
Enthalpy exchange efficiency · Heating, high (50/60 Hz) · %72.0/72.0
Enthalpy exchange efficiency · Heating, low (50/60 Hz) · %74.0/75.0
Power consumption · Heat exchange, extra high (50/60 Hz) · W644–684/829
Power consumption · Heat exchange, high (50/60 Hz) · W603–612/712
Power consumption · Heat exchange, low (50/60 Hz) · W504–544/562
Power consumption · Bypass, extra high (50/60 Hz) · W644–684/829
Power consumption · Bypass, high (50/60 Hz) · W603–612/712
Power consumption · Bypass, low (50/60 Hz) · W504–544/562
Fan motor output · kW0.190 × 2
Airflow & sound
Sound level · Heat exchange, extra high (50/60 Hz) · dB(A)41.5–42.5/41.0
Sound level · Heat exchange, high (50/60 Hz) · dB(A)39.5–41.0/37.0
Sound level · Heat exchange, low (50/60 Hz) · dB(A)36.0–38.5/33.0
Sound level · Bypass, extra high (50/60 Hz) · dB(A)41.5–42.5/41.0
Sound level · Bypass, high (50/60 Hz) · dB(A)39.5–41.0/37.0
Sound level · Bypass, low (50/60 Hz) · dB(A)36.0–38.5/33.0
Fan typeSirocco fan
Airflow at extra high speed (50/60 Hz) · m³/h800/800
External static pressure at extra high speed (50/60 Hz) · Pa210–235/250
Airflow at high speed (50/60 Hz) · m³/h800/800
External static pressure at high speed (50/60 Hz) · Pa170–215/140
Airflow at low speed (50/60 Hz) · m³/h720/610
External static pressure at low speed (50/60 Hz) · Pa138–174/81
Effective supply airflow ratio, extra high · %90
Dimensions & weight
CasingGalvanized steel
InsulationNon-flammable polyurethane foam
Dimensions (H×W×D) · mm387×1,012×1,110
Weight · kg63
Piping & refrigerant
Inner duct connection · mmØ250
Outer duct connection · mmØ250
Operating conditions
Ambient operating conditions−15 to 50 °CDB, up to 80% RH
Filters
Air filterMulti-directional fibre mat

Source reference

VN-PCXDHMT2111A · PDF page 11 · Printed page 10
Vietnamese source PDF · English specifications translated from the source

Open catalogue PDF · page 11
Model page: https://vrv.vn/spec/vam800hve/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Catalogue notes (summary)

Notes: Pairs are in 50/60 Hz order. The catalogue cites JIS B8628:2017 for heat exchange and sound testing. The reference table on PDF page 13 uses VAM-G test conditions. Use the main VAM-HVE tables on PDF pages 10–11.