Back to resultsSpecification results
Daikin FXMQ-AFVM — representative product image
Representative image · Vietnamese catalogue, PDF 234 ↗
Indoor unitFXMQ-AFVM →

FXMQ80AFVM

Daikin · Outdoor air processing unit

FXMQ80AFVM is a Daikin indoor unit in the FXMQ-AFVM series, outdoor air processing unit type. Its rated cooling capacity is 9 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
9 kW
Power supply
1 phase, 220-240/220-230 V, 50/60 Hz
Dimensions (H×W×D)
300×700×700 mm
Weight
29 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FXMQ80AFVM specifications

FXMQ80AFVM specifications · PCVVN2507Aaprv
Rated capacity 4 specifications
Cooling capacity *1 · Btu/h30,700
Cooling capacity *1 · kW9.0
Heating capacity *1 · Btu/h27,600
Heating capacity *1 · kW8.1
Electrical & efficiency 3 specifications
Power supply1 phase, 220-240/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.080
Power consumption · Heating · kW0.095
Airflow & sound 5 specifications
Fan · Motor output · kW0.140
Fan · Airflow rate (H/M/L) · m³/min11.5/8.6/5.8
Fan · Airflow rate (H/M/L) · cfm406/304/205
Fan · External static pressure · PaRated 100 (200-50)
Sound level (H/M/L) *3 · dB(A)37.5/30/23
Dimensions & weight 3 specifications
CasingGalvanised steel plate
Dimensions (H×W×D) · mm300×700×700
Machine weight · kg29
Piping & refrigerant 3 specifications
Refrigerant piping · Liquid · mm9.5 (Flare)
Refrigerant piping · Gas · mm15.9 (Flare)
Refrigerant piping · Drain · mmVP25 (External dia. 32, Internal dia. 25)
Operating conditions 2 specifications
Operation range *4 · Cooling · °CDB15 to 43
Operation range *4 · Heating · °CDB-5 to 19
Filters 6 specifications
Air filter*2
Filters · MERV8 filterBAF376B56
Filters · MERV14 filterBAF377B56
Filters · Filter chamber for MERV8/14 filterKDDF37AB56
Filters · Long-life replacement filterKAF371B56
Filters · Streamer duct chamberBDEZ500A140VE
Controls & accessories 17 specifications
lortnoc/noitarepO · Wired remote controllerBRC1H63W(K) / BRC1E63 / BRC2E61
lortnoc/noitarepO · Wireless remote controller *4Cooling only: BRC4C66 / Heat pump: BRC4C65
lortnoc/noitarepO · Remote sensor (for indoor temperature)BRCS01A-6
lortnoc/noitarepO · Simple touch controllerDTP401A61
lortnoc/noitarepO · AC adaptor for simple touch controllerDTP401A62
lortnoc/noitarepO · Central remote controllerDCS302CA61
lortnoc/noitarepO · Unified ON/OFF controllerDCS301BA61
lortnoc/noitarepO · Schedule timerDST301BA61
Service panelKTBJ25K56F
Air discharge adaptorKDAJ25K56A
Adaptor for wiring (operation status output) BRP11B62
Wiring adaptor for electrical appendices (1) KRP2A61
Wiring adaptor for electrical appendices (2) KRP4AA51
Installation box for adaptor PCB  *1 KRP4A96 *2, 3
External control adaptor for outdoor unit DTA104A61
Adaptor for multi tenant (24V type) DTA114A61
Digital input adaptor for hotel application BRP7A53

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 237 (printed page 236). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: *1. The capacity is the maximum value under the following conditions: • Cooling: Indoor temp. of 33°CDB, 28°CWB, Outdoor temp. of 33°CDB. • Heating: Indoor temp. 0°CDB, -2.9°CWB, Outdoor temp. 0°CDB, -2.9°CWB. • Equivalent reference piping length: 7.5 m (0 m horizontal) • The rated external static pressure and air volume are set in (). *2. An intake filter is not supplied, so be sure to install the optional filter. *3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. These values are normally somewhat higher during actual operation as a result of ambient conditions. *4. The operation range can be extended to 15°C in cooling operation and 19°C in heating operation by field setting. When fresh air intake mode is enabled during cooling operation, operation range cannot be extended. (limit at 19 to 43°C) Options Model FXMQ80AFVM FXMQ140AFVM FXMQ200AFVM FXMQ250AFVM Wired remote controller BRC1H63W(K) / BRC1E63 / BRC2E61 Wireless remote controller *4 Cooling only: BRC4C66 / Heat pump: BRC4C65 Remote sensor (for indoor temperature) BRCS01A-6 Simple touch controller DTP401A61 AC adaptor for simple touch controller DTP401A62 Central remote controller DCS302CA61 Unified ON/OFF controller DCS301BA61 Schedule timer DST301BA61 236 lortnoc/noitarepO sretliF m³/min 11.5/8.6/5.8 20.5/15.4/10.3 29.0/21.8/14.5 36.0/27.0/18.0 MERV8 filter BAF376B56 BAF376B80 BAF376B160 MERV14 filter BAF377B56 BAF377B80 BAF377B160 Filter chamber for MERV8/14 filter KDDF37AB56 KDDF37AB80 KDDF37AB160 Long-life replacement filter KAF371B56 KAF371B80 KAF371B160 BDEZ500A140VE Streamer duct chamber BDEZ500A140VE BDEZ500A510VE BDEZ500A510VE Service panel KTBJ25K56F KTBJ25K80F KTBJ25K160F Air discharge adaptor KDAJ25K56A KDAJ25K71A KDAJ25K140A Adaptor for wiring (operation status output)  BRP11B62 Wiring adaptor for electrical appendices (1)  KRP2A61 Wiring adaptor for electrical appendices (2)  KRP4AA51 Installation box for adaptor PCB  *1  KRP4A96 *2, 3 External control adaptor for outdoor unit  DTA104A61 Adaptor for multi tenant (24V type)  DTA114A61 Digital input adaptor for hotel application  BRP7A53 Notes: *1. Installation Box ☆ is necessary for each adaptor marked ★. *2. Up to 2 adaptors can be fixed for each installation box. *3. Only one installation box can be installed for each indoor unit. *4. Remote sensor is necessary when using wireless remote controller. tnempiuqE tnemtaerT riA Air Treatment Equipment
View catalogue page · PDF 237

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 237
Read all text from this page and its facing page
PDF page 237 Specifications Model FXMQ80AFVM FXMQ140AFVM FXMQ200AFVM FXMQ250AFVM Power supply 1 phase, 220-240/220-230 V, 50/60 Hz Btu/h 30,700 54,600 76,400 95,500 Cooling capacity *1 kW 9.0 16.0 22.4 28.0 Btu/h 27,600 47,800 68,200 85,300 Heating capacity *1 kW 8.1 14.0 20.0 25.0 Cooling 0.080 0.100 0.115 0.180 Power consumption kW Heating 0.095 0.125 0.155 0.225 Casing Galvanised steel plate Dimensions (H×W×D) mm 300×700×700 300×1,000×700 300×1,400×700 Motor output kW 0.140 0.350 Fan Airflow rate (H/M/L) cfm 406/304/205 724/544/364 1,024/770/512 1,271/953/635 External static pressure Pa Rated 100 (200-50) Air filter *2 Liquid 9.5 (Flare) Refrigerant piping Gas mm 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing) Drain VP25 (External dia. 32, Internal dia. 25) Machine weight kg 29 37 47 48 Sound level (H/M/L) *3 dB(A) 37.5/30/23 41/34/25 42/35/26 44/36/27 Cooling 15 to 43 Operation range *4 °CDB Heating -5 to 19 Notes: *1. The capacity is the maximum value under the following conditions: • Cooling: Indoor temp. of 33°CDB, 28°CWB, Outdoor temp. of 33°CDB. • Heating: Indoor temp. 0°CDB, -2.9°CWB, Outdoor temp. 0°CDB, -2.9°CWB. • Equivalent reference piping length: 7.5 m (0 m horizontal) • The rated external static pressure and air volume are set in (). *2. An intake filter is not supplied, so be sure to install the optional filter. *3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. These values are normally somewhat higher during actual operation as a result of ambient conditions. *4. The operation range can be extended to 15°C in cooling operation and 19°C in heating operation by field setting. When fresh air intake mode is enabled during cooling operation, operation range cannot be extended. (limit at 19 to 43°C) Options Model FXMQ80AFVM FXMQ140AFVM FXMQ200AFVM FXMQ250AFVM Wired remote controller BRC1H63W(K) / BRC1E63 / BRC2E61 Wireless remote controller *4 Cooling only: BRC4C66 / Heat pump: BRC4C65 Remote sensor (for indoor temperature) BRCS01A-6 Simple touch controller DTP401A61 AC adaptor for simple touch controller DTP401A62 Central remote controller DCS302CA61 Unified ON/OFF controller DCS301BA61 Schedule timer DST301BA61 236 lortnoc/noitarepO sretliF m³/min 11.5/8.6/5.8 20.5/15.4/10.3 29.0/21.8/14.5 36.0/27.0/18.0 MERV8 filter BAF376B56 BAF376B80 BAF376B160 MERV14 filter BAF377B56 BAF377B80 BAF377B160 Filter chamber for MERV8/14 filter KDDF37AB56 KDDF37AB80 KDDF37AB160 Long-life replacement filter KAF371B56 KAF371B80 KAF371B160 BDEZ500A140VE Streamer duct chamber BDEZ500A140VE BDEZ500A510VE BDEZ500A510VE Service panel KTBJ25K56F KTBJ25K80F KTBJ25K160F Air discharge adaptor KDAJ25K56A KDAJ25K71A KDAJ25K140A Adaptor for wiring (operation status output)  BRP11B62 Wiring adaptor for electrical appendices (1)  KRP2A61 Wiring adaptor for electrical appendices (2)  KRP4AA51 Installation box for adaptor PCB  *1  KRP4A96 *2, 3 External control adaptor for outdoor unit  DTA104A61 Adaptor for multi tenant (24V type)  DTA114A61 Digital input adaptor for hotel application  BRP7A53 Notes: *1. Installation Box ☆ is necessary for each adaptor marked ★. *2. Up to 2 adaptors can be fixed for each installation box. *3. Only one installation box can be installed for each indoor unit. *4. Remote sensor is necessary when using wireless remote controller. tnempiuqE tnemtaerT riA Air Treatment Equipment FACING PAGE — PDF page 236 Air Treatment Equipment Outdoor-Air Processing Unit (Room Temperature Control Type) Extended operation range The outdoor operation temperature range extended from 19 to 15°CDB during cooling operation and from 15 to 19°CDB during heating operation*. This enables reliable operation even under wider temperature conditions. Outdoor air temperature (°CDB) 32 100 % H R u e % m la t i R d iv e i e t l y ative Hu midity 90 Outdoor Air (° T C e W m B p ) erature S O up p p e o ra r t t i e o d n C R o a o n l g in e g E C H x o e t o a e l t n i i n n d g g e : : d 1 - 5 o 5 ° p ° C C e D D ra B B t i t t o o o n 1 4 r 9 3 a ° ° n C C g D D e B B : Su O p p p e o ra rt t e io d n H R e a a n ti g n e g Op F e a ra n tion 30% Relative Humidity 20% H u R m el i a d t i i t v y e –5 15 19 (33.5) 43 * Thermo-off (fan) operation starts automatically when cooling 19°CDB or less / heating15°CDB or more. In case of cooling mode, operation range can be extended to 15°CDB by field setting. In case of heating mode, operation range can be extended to 19°CDB by field setting High efficiency filter (MERV8/MERV14) (Option) The filter options of MERV8 and MERV14 are available. The high efficiency filter can help remove infectious aerosol in the air. MERV8 filter MERV14 filter 235

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗