VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

FXMQ80AFVM

Indoor unit · FXMQ-AFVM · Outdoor air processing unit

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FXMQ80AFVM specifications
Rated capacity
Cooling capacity *1 · Btu/h30,700
Cooling capacity *1 · kW9.0
Heating capacity *1 · Btu/h27,600
Heating capacity *1 · kW8.1
Electrical & efficiency
Power supply1-phasese, 220-240/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.080
Power consumption · Heating · kW0.095
Airflow & sound
Fan · Motor output · kW0.140
Fan · Airflow rate (H/M/L) · m³/min11.5/8.6/5.8
Fan · Airflow rate (H/M/L) · cfm406/304/205
Fan · External static pressure · PaRated 100 (200-50)
Sound level (H/M/L) *3 · dB(A)37.5/30/23
Dimensions & weight
CasingGalvanised steel plate
Dimensions (H×W×D) · mm300×700×700
Machine weight · kg29
Piping & refrigerant
Refrigerant piping · Liquid · mm9.5 (Flare)
Refrigerant piping · Gas · mm15.9 (Flare)
Refrigerant piping · Drain · mmVP25 (External dia. 32, Internal dia. 25)
Operating conditions
Operation range *4 · Cooling · °CDB15 to 43
Operation range *4 · Heating · °CDB-5 to 19
Filters
Air filter*2
Filters · MERV8 filterBAF376B56
Filters · MERV14 filterBAF377B56
Filters · Filter chamber for MERV8/14 filterKDDF37AB56
Filters · Long-life replacement filterKAF371B56
Filters · Streamer duct chamberBDEZ500A140VE
Controls & accessories
lortnoc/noitarepO · Wired remote controllerBRC1H63W(K) / BRC1E63 / BRC2E61
lortnoc/noitarepO · Wireless remote controller *4Cooling only: BRC4C66 / Heat pump: BRC4C65
lortnoc/noitarepO · Remote sensor (for indoor temperature)BRCS01A-6
lortnoc/noitarepO · Simple touch controllerDTP401A61
lortnoc/noitarepO · AC adaptor for simple touch controllerDTP401A62
lortnoc/noitarepO · Central remote controllerDCS302CA61
lortnoc/noitarepO · Unified ON/OFF controllerDCS301BA61
lortnoc/noitarepO · Schedule timerDST301BA61
Service panelKTBJ25K56F
Air discharge adaptorKDAJ25K56A
Adaptor for wiring (operation status output) BRP11B62
Wiring adaptor for electrical appendices (1) KRP2A61
Wiring adaptor for electrical appendices (2) KRP4AA51
Installation box for adaptor PCB  *1 KRP4A96 *2, 3
External control adaptor for outdoor unit DTA104A61
Adaptor for multi tenant (24V type) DTA114A61
Digital input adaptor for hotel application BRP7A53

Source reference

PCVVN2507Aaprv · PDF page 237 · Printed page 236
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 237
Model page: https://vrv.vn/spec/fxmq80afvm/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes:
*1. The capacity is the maximum value under the following conditions:
• Cooling: Indoor temp. of 33°CDB, 28°CWB, Outdoor temp. of 33°CDB.
• Heating: Indoor temp. 0°CDB, -2.9°CWB, Outdoor temp. 0°CDB, -2.9°CWB.
• Equivalent reference piping length: 7.5 m (0 m horizontal)
• The rated external static pressure and air volume are set in ().
*2. An intake filter is not supplied, so be sure to install the optional filter.
*3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
These values are normally somewhat higher during actual operation as a result of ambient conditions.
*4. The operation range can be extended to 15°C in cooling operation and 19°C in heating operation by field setting.
When fresh air intake mode is enabled during cooling operation, operation range cannot be extended. (limit at 19 to 43°C)
Options
Model FXMQ80AFVM FXMQ140AFVM FXMQ200AFVM FXMQ250AFVM
Wired remote controller BRC1H63W(K) / BRC1E63 / BRC2E61
Wireless remote controller *4 Cooling only: BRC4C66 / Heat pump: BRC4C65
Remote sensor (for indoor temperature) BRCS01A-6
Simple touch controller DTP401A61
AC adaptor for simple touch controller DTP401A62
Central remote controller DCS302CA61
Unified ON/OFF controller DCS301BA61
Schedule timer DST301BA61
236
lortnoc/noitarepO
sretliF
m³/min 11.5/8.6/5.8 20.5/15.4/10.3 29.0/21.8/14.5 36.0/27.0/18.0
MERV8 filter BAF376B56 BAF376B80 BAF376B160
MERV14 filter BAF377B56 BAF377B80 BAF377B160
Filter chamber for MERV8/14 filter KDDF37AB56 KDDF37AB80 KDDF37AB160
Long-life replacement filter KAF371B56 KAF371B80 KAF371B160
BDEZ500A140VE
Streamer duct chamber BDEZ500A140VE BDEZ500A510VE
BDEZ500A510VE
Service panel KTBJ25K56F KTBJ25K80F KTBJ25K160F
Air discharge adaptor KDAJ25K56A KDAJ25K71A KDAJ25K140A
Adaptor for wiring (operation status output)  BRP11B62
Wiring adaptor for electrical appendices (1)  KRP2A61
Wiring adaptor for electrical appendices (2)  KRP4AA51
Installation box for adaptor PCB  *1  KRP4A96 *2, 3
External control adaptor for outdoor unit  DTA104A61
Adaptor for multi tenant (24V type)  DTA114A61
Digital input adaptor for hotel application  BRP7A53
Notes:
*1. Installation Box ☆ is necessary for each adaptor marked ★.
*2. Up to 2 adaptors can be fixed for each installation box.
*3. Only one installation box can be installed for each indoor unit.
*4. Remote sensor is necessary when using wireless remote controller.
tnempiuqE
tnemtaerT
riA
Air Treatment Equipment