FXMQ125MFV1 is a Daikin indoor unit in the FXMQ-MFV1 series, outdoor air processing unit type. Its rated cooling capacity is 14 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 14 kW
- Power supply
- 1-phase 220-240 V, 50 Hz
- Dimensions (H×W×D)
- 470 × 744 × 1,100 mm
- Weight
- 86 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FXMQ125MFV1 specifications
| System configuration 1 specifications | |
|---|---|
| Connectable outdoor units *4 | 5 HP and above |
| Rated capacity 4 specifications | |
| Cooling capacity *1 · Btu/h | 47,800 |
| Cooling capacity *1 · kW | 14.0 |
| Heating capacity *1 · Btu/h | 30,400 |
| Heating capacity *1 · kW | 8.9 |
| Electrical & efficiency 2 specifications | |
| Power supply | 1-phase 220-240 V, 50 Hz |
| Power consumption · kW | 0.359 |
| Airflow & sound 7 specifications | |
| Fan · Motor output · kW | 0.380 |
| Fan · Airflow rate · m3/min | 18 |
| Fan · Airflow rate · cfm | 635 |
| Fan · External static pressure · 220 V/240 V · Pa | 185/225 |
| Sound level *3 · 220 V/240 V · dB(A) | 42/43 |
| Operation range (Fan mode operation between 15 and 19°C) · Cooling | 19 to 43°C |
| Operation range (Fan mode operation between 15 and 19°C) · Heating | -5 to 15°C |
| Dimensions & weight 3 specifications | |
| Casing | Galvanised steel plate |
| Dimensions (H × W × D) · mm | 470 × 744 × 1,100 |
| Machine weight · kg | 86 |
| Piping & refrigerant 3 specifications | |
| Refrigerant piping · Liquid · mm | 9.5 (Flare) |
| Refrigerant piping · Gas · mm | 15.9 (Flare) |
| Refrigerant piping · Drain · mm | PS1B female thread |
| Operating conditions 2 specifications | |
| Range of the discharge temperature *5 · Cooling | 13 to 25°C |
| Range of the discharge temperature *5 · Heating | 18 to 30°C |
| Filters 6 specifications | |
| Air filter | *2 |
| Filters · Long-life replacement filter | KAF371N140 |
| Filters · High-efficiency filter · Colourimetric method 65% | KAF372M140 |
| Filters · High-efficiency filter · Colourimetric method 90% | KAF373M140 |
| Filters · Filter chamber * | KDJ3705L140 |
| Filters · Streamer duct chamber | BDEZ500A140VE |
| Controls & accessories 9 specifications | |
| lortnoc/noitarepO · Operation remote controller | BRC1H63W(K) / BRC1E63 / BRC2E61 |
| lortnoc/noitarepO · Simple touch controller | DTP401A61 |
| lortnoc/noitarepO · AC adaptor for simple touch controller | DTP401A62 |
| lortnoc/noitarepO · Central remote controller | DCS302CA61 |
| lortnoc/noitarepO · Unified ON/OFF controller | DCS301BA61 |
| lortnoc/noitarepO · Schedule timer | DST301BA61 |
| lortnoc/noitarepO · Wiring adaptor for electrical appendices (2) | KRP4AA51 |
| Drain pump kit | KDU30L250VE |
| Adaptor for wiring | KRP1B61 |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 233 (printed page 232). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: *1. Specifications are based on the following conditions:
• Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB.
• Heating: Outdoor temp. 0°CDB, -2.9°CWB (50% RH), and discharge temp. of 25°CDB.
• Equivalent reference piping length: 7.5 m (0 m horizontal)
*2. An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
*3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
These values are normally somewhat higher during actual operation as a result of ambient conditions.
*4. It is possible to connect to the outdoor unit if the total capacity of the indoor units is 50% to 100% of the capacity index of the outdoor unit.
*5. Local setting mode is not displayed on the remote controller.
• This equipment cannot be incorporated into the remote group control of the VRV system.
Options
232
sretliF
MODEL FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Operation remote controller BRC1H63W(K) / BRC1E63 / BRC2E61
DTP401A61
DTP401A62
DCS302CA61
DCS301BA61
DST301BA61
KRP4AA51
lortnoc/noitarepO
This unit is intended for the treatment of outdoor air only. Not to be used for maintaining indoor air temperature. Be sure that the discharge airflow will not
blow on people directly.
Group control of the product and standard indoor units is not supported. A separate remote controller should be connected to individual unit.
If the unit is utilised to operate 24 hours a day, maintenance (part replacement, etc.) must be performed periodically.
Temperature setting and Power Proportional Distribution (PPD) are not possible even if the intelligent Touch Controller or the intelligent Touch Manager is installed.
The remote controller wired to the outdoor-air processing unit must not be set as the master remote controller. Otherwise, when set to “Auto,” the operation mode
will switch according to the outdoor air conditions, regardless of the indoor temperature.
Central remote controller
Unified ON/OFF controller
Schedule timer
Wiring adaptor for electrical appendices (2)
Long-life replacement filter KAF371N140 KAF371N280
Colourimetric method 65% KAF372M140 KAF372M280
High-efficiency filter
Colourimetric method 90% KAF373M140 KAF373M280
Filter chamber * KDJ3705L140 KDJ3705L280
Streamer duct chamber BDEZ500A140VE BDEZ500A510VE
Drain pump kit KDU30L250VE
Adaptor for wiring KRP1B61
Notes: * Filter chamber has a suction-type flange. (Main unit does not.)
• Dimensions and weight of the equipment may vary depending on the options used.
• Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
• Some options may not be used in combination.
• Operating sound may increase somewhat depending on the options used.
tnempiuqE
tnemtaerT
riA
Air Treatment Equipment
Simple touch controller
AC adaptor for simple touch controller
View catalogue page · PDF 233
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 233
Precautions for use of FXMQ-MF series
1.
2.
3.
4.
5.
Specifications
Type Ceiling Mounted Duct Type
MODEL FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Power supply 1-phase 220-240 V, 50 Hz
Btu/h 47,800 76,400 95,500
Cooling capacity *1
kW 14.0 22.4 28.0
Btu/h 30,400 47,400 59,400
Heating capacity *1
kW 8.9 13.9 17.4
Power consumption kW 0.359 0.548 0.638
Casing Galvanised steel plate
Dimensions (H × W × D) mm 470 × 744 × 1,100 470 × 1,380 × 1,100
Motor output kW 0.380
m3/min 18 28 35
Fan Airflow rate
cfm 635 988 1,236
External static pressure 220 V/240 V Pa 185/225 225/275 205/255
Air filter *2
Liquid 9.5 (Flare)
Refrigerant
Gas mm 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)
piping
Drain PS1B female thread
Machine weight kg 86 123
Sound level *3 220 V/240 V dB(A) 42/43 47/48
Connectable outdoor units *4 5 HP and above 8 HP and above 10 HP and above
Operation range Cooling 19 to 43°C
(Fan mode operation between 15 and 19°C) Heating -5 to 15°C
Cooling 13 to 25°C
Range of the discharge temperature *5
Heating 18 to 30°C
Notes: *1. Specifications are based on the following conditions:
• Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB.
• Heating: Outdoor temp. 0°CDB, -2.9°CWB (50% RH), and discharge temp. of 25°CDB.
• Equivalent reference piping length: 7.5 m (0 m horizontal)
*2. An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
*3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
These values are normally somewhat higher during actual operation as a result of ambient conditions.
*4. It is possible to connect to the outdoor unit if the total capacity of the indoor units is 50% to 100% of the capacity index of the outdoor unit.
*5. Local setting mode is not displayed on the remote controller.
• This equipment cannot be incorporated into the remote group control of the VRV system.
Options
232
sretliF
MODEL FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Operation remote controller BRC1H63W(K) / BRC1E63 / BRC2E61
DTP401A61
DTP401A62
DCS302CA61
DCS301BA61
DST301BA61
KRP4AA51
lortnoc/noitarepO
This unit is intended for the treatment of outdoor air only. Not to be used for maintaining indoor air temperature. Be sure that the discharge airflow will not
blow on people directly.
Group control of the product and standard indoor units is not supported. A separate remote controller should be connected to individual unit.
If the unit is utilised to operate 24 hours a day, maintenance (part replacement, etc.) must be performed periodically.
Temperature setting and Power Proportional Distribution (PPD) are not possible even if the intelligent Touch Controller or the intelligent Touch Manager is installed.
The remote controller wired to the outdoor-air processing unit must not be set as the master remote controller. Otherwise, when set to “Auto,” the operation mode
will switch according to the outdoor air conditions, regardless of the indoor temperature.
Central remote controller
Unified ON/OFF controller
Schedule timer
Wiring adaptor for electrical appendices (2)
Long-life replacement filter KAF371N140 KAF371N280
Colourimetric method 65% KAF372M140 KAF372M280
High-efficiency filter
Colourimetric method 90% KAF373M140 KAF373M280
Filter chamber * KDJ3705L140 KDJ3705L280
Streamer duct chamber BDEZ500A140VE BDEZ500A510VE
Drain pump kit KDU30L250VE
Adaptor for wiring KRP1B61
Notes: * Filter chamber has a suction-type flange. (Main unit does not.)
• Dimensions and weight of the equipment may vary depending on the options used.
• Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
• Some options may not be used in combination.
• Operating sound may increase somewhat depending on the options used.
tnempiuqE
tnemtaerT
riA
Air Treatment Equipment
Simple touch controller
AC adaptor for simple touch controller
FACING PAGE — PDF page 232
Air Treatment Equipment
Outdoor-Air Processing Unit (Discharge Air Temperature Control Type)
FXMQ-MF Series
Combine fresh air treatment and air conditioning,
supplied from a single system.
Fresh air treatment and air conditioning can be Lineup
achieved with a single system. VRV indoor units
Model Name FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
for air conditioning and an outdoor-air
Capacity index 125 200 250
processing unit can be connected to the same
refrigerant line. Airflow rate 1,080 m3/h 1,680 m3/h 2,100 m3/h
VRV Outdoor Units
Connection Conditions
Outdoor-Air Processing Unit
• Outdoor-air processing units can be used without indoor
units. The total connection capacity index must be 50% to
Indoor Unit Indoor Unit 100% of the capacity index of the outdoor units.
• When outdoor-air processing units and standard indoor units
are combined, the total connection capacity index of the
outdoor-air processing units must not exceed 30% of the
capacity index of the outdoor units.
Because connection is possible depending on conditions even
Air Outdoor
when the capacity index of outdoor-air processing units
Conditioning Air Supply exceeds 30% of the capacity index of the outdoor units,
contact your local distributor.
Outdoor-air processing / Discharge air temperature control
The unit supplies outdoor fresh air controlling discharge air temperature from the unit.
Outdoor-Air Processing Unit
Outdoor Air Supply Air (Discharge Air)
* The default setting of the discharge air temperature is 18°C for
cooling operation, and 25°C for heating operation.
* While in unit protection mode and depending on outdoor air
Discharge conditions, discharge air temperature may not be at the set
temperature.
Air Temperature
* The fan stops in defrosting, oil returning and hot start operations
Heat Exchanger due to mechanical protection control.
Operation range
Applicable to outdoor air temperature range from –5 to 43°C.
Outdoor air temperature (°CDB) 32 In cooling operation, 19 to 43°C is adoptable.
100% 9 H R 0 u e % m lat id R iv i e e t l y ative Humidity
Outdoor Air (° T C e W m B p )
erature
S O up p p e o ra r t t i e o d n C R o a o n l g in e g
Su O p p p e o ra rt t e io d n H R e a a n ti g n e g
Op F e a ra n tion
30%
Relative Humidity 20% H u R m el i a d t i i t v y e Notes:
2
1
.
.
T
T
p h
h
ip e
e
i n s
o
y g
p
s
e
t le e
r
n
a
m g
t i
t w
o
h
n
i : l l 7
r a
n .5
n
o
g
t m
e
o , p
s
H
h
e e
o
r i a
w
g t h e
n
t i
i
n d
n
i f f
t
a f
h
e n
e
r e m
g
n
r
o
a
c d e
p
: e
h
0 w
i s
m h
u
. e
n
n
d
t
e
h
r
e
t h
o
e
u t
f
d
o
o
ll
o
o
r
w
a
in
ir
g
t e
co
m
n
p
d
e
i
r
t
a
io
t
n
u
s
r
.
e
E
i
q
s
u
5
i
°
v
C
a l
o
e
r
n t
below.
–5 15 19 (33.5) 43
231
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗