Back to resultsSpecification results
Daikin FXZQ-B — representative product image
Representative image · Vietnamese catalogue, PDF 194 ↗
Indoor unitFXZQ-B →

FXZQ50BVM

Daikin · Compact 4-way cassette

FXZQ50BVM is a Daikin indoor unit in the FXZQ-B series, compact 4-way cassette type. Its rated cooling capacity is 5.6 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
5.6 kW
Power supply
1-phase, 220-240 V/220-230 V, 50/60 Hz
Dimensions (H×W×D)
260×575×575 (For depth add 63 mm for electrical box) mm
Weight
18.5 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FXZQ50BVM specifications

FXZQ50BVM specifications · PCVVN2507Aaprv
Rated capacity 4 specifications
Cooling capacity · Btu/h19,100
Cooling capacity · kW5.6
Heating capacity · Btu/h21,500
Heating capacity · kW6.3
Electrical & efficiency 3 specifications
Power supply1-phase, 220-240 V/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.092
Power consumption · Heating · kW0.086
Airflow & sound 4 specifications
Airflow rate (H/M/L) · m³/min14.5/12.5/10.0
Airflow rate (H/M/L) · cfm512/441/353
Sound level (H/M/L) · dB(A)43.0/40.0/33.0
Sound power (H) · dB(A)60
Dimensions & weight 3 specifications
CasingGalvanised steel plate
Dimensions (H×W×D) · mm260×575×575 (For depth add 63 mm for electrical box)
Machine weight · kg18.5
Piping & refrigerant 3 specifications
Piping connections · Liquid (Flare) · mm6.4
Piping connections · Gas (Flare) · mm12.7
Piping connections · Drain · mmVP20 (External Dia. 26/Internal Dia. 20)

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 195 (printed page 194). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Panel (Option) Panel type Grid ceiling panel Appearance Model BYFQ60CAW Colour White (N9.5) Dimensions (H×W×D) mm 46×620×620 Weight kg 2.8 194 stinU roodnI
View catalogue page · PDF 195

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 195
Read all text from this page and its facing page
PDF page 195 VRV Indoor Units Specifications MODEL FXZQ20BVM FXZQ25BVM FXZQ32BVM FXZQ40BVM FXZQ50BVM Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Btu/h 7,500 9,600 12,300 15,400 19,100 Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 Btu/h 8,500 10,900 13,600 17,100 21,500 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 Power Cooling 0.043 0.045 0.059 0.092 kW consumption Heating 0.036 0.038 0.053 0.086 Casing Galvanised steel plate m³/min 8.7/7.5/6.5 9.0/8.0/6.5 10.0/8.5/7.0 11.5/9.5/8.0 14.5/12.5/10.0 Airflow rate (H/M/L) cfm 307/265/229 318/282/229 353/300/247 406/335/282 512/441/353 Sound level (H/M/L) dB(A) 32.0/29.5/25.5 33.0/30.0/25.5 33.5/30.0/26.0 37.0/32.0/28.0 43.0/40.0/33.0 Sound power (H) dB(A) 49 50 51 54 60 Dimensions (H×W×D) mm 260×575×575 (For depth add 63 mm for electrical box) Machine weight kg 15.5 16.5 18.5 Liquid (Flare) 6.4 Piping connections Gas (Flare) mm 12.7 Drain VP20 (External Dia. 26/Internal Dia. 20) Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Panel (Option) Panel type Grid ceiling panel Appearance Model BYFQ60CAW Colour White (N9.5) Dimensions (H×W×D) mm 46×620×620 Weight kg 2.8 194 stinU roodnI FACING PAGE — PDF page 194 Compact Multi Flow Cassette Type FXZQ-B Quiet, compact, and designed for user comfort Compact & elegant design • Fully-flat integration in standard architectural ceiling tiles, leaving only 8 mm 8 mm • Remarkable blend of iconic design and engineering excellence with an elegant finish in white • The newly designed panel integrates fully within one ceiling tile enabling lights, speakers and sprinklers to be installed in the adjoining ceiling tiles. Efficiency & comfort Dual sensors (Option) • Two optional intelligent sensors improve energy efficiency and comfort. • An optional presence and floor sensor kit can be fitted to the cassette for draught prevention, energy-saving operation and to provide optimal control of airflow. Individual airflow direction control* • Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air distribution. *Applicable when wired remote controller BRC1E63 or BRC1H63W(K) is used. Auto swing (up/down) • Possibility to select automatic vertical moving of the air discharge flaps for efficient air and temperature distribution throughout the room. Cleanliness Streamer filter clean unit (Option) See page 7 - 8 • Irradiates Streamer when the fan and air conditioning operation are stopped. Streamer fumigates the cabin and sterilizes the filter. Remarks: 1) Only the stylish remote controller BRC1H63W(K) can be connected for ON/OFF operation of the streamer. 2) The Streamer function operates only when the fan and air conditioning operation are stopped. BAPWS55A61 The maximum operation of Streamer is 180 minutes per day. Ceiling soiling prevention • Prevents air from blowing against the ceiling to prevent ceiling stains. 193