VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

FXZQ50BVM

Indoor unit · FXZQ-B · Compact 4-way cassette

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FXZQ50BVM specifications
Rated capacity
Cooling capacity · Btu/h19,100
Cooling capacity · kW5.6
Heating capacity · Btu/h21,500
Heating capacity · kW6.3
Electrical & efficiency
Power supply1-phase, 220-240 V/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.092
Power consumption · Heating · kW0.086
Airflow & sound
Airflow rate (H/M/L) · m³/min14.5/12.5/10.0
Airflow rate (H/M/L) · cfm512/441/353
Sound level (H/M/L) · dB(A)43.0/40.0/33.0
Sound power (H) · dB(A)60
Dimensions & weight
CasingGalvanised steel plate
Dimensions (H×W×D) · mm260×575×575 (For depth add 63 mm for electrical box)
Machine weight · kg18.5
Piping & refrigerant
Piping connections · Liquid (Flare) · mm6.4
Piping connections · Gas (Flare) · mm12.7
Piping connections · Drain · mmVP20 (External Dia. 26/Internal Dia. 20)

Source reference

PCVVN2507Aaprv · PDF page 195 · Printed page 194
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 195
Model page: https://vrv.vn/spec/fxzq50bvm/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Panel (Option)
Panel type Grid ceiling panel
Appearance
Model BYFQ60CAW
Colour White (N9.5)
Dimensions (H×W×D) mm 46×620×620
Weight kg 2.8
194
stinU
roodnI