FXMQ50PAVE

Daikin · Concealed ceiling ducted medium–high static pressure

FXMQ50PAVE is a Daikin indoor unit in the FXMQ-PA series, concealed ceiling ducted medium–high static pressure type. Its rated cooling capacity is 5.6 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
5.6 kW
Power supply
1-phase, 220-240 V/220 V, 50/60 Hz
Dimensions (H×W×D)
300x1,000x700 mm
Weight
35 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FXMQ50PAVE specifications

FXMQ50PAVE specifications · PCVVN2507Aaprv
Rated capacity 4 specifications
Cooling capacity · Btu/h19,100
Cooling capacity · kW5.6
Heating capacity · Btu/h21,500
Heating capacity · kW6.3
Electrical & efficiency 3 specifications
Power supply1-phase, 220-240 V/220 V, 50/60 Hz
Power consumption · Cooling · kW0.128 *1
Power consumption · Heating · kW0.116 *1
Airflow & sound 4 specifications
Airflow rate (HH/H/L) · m3/min18/16.5/15
Airflow rate (HH/H/L) · cfm635/582/530
External static pressure · Pa50-200 (100) *2
Sound level (HH/H/L) · dB(A)41/39/37
Dimensions & weight 3 specifications
CasingGalvanised steel plate
Dimensions (H×W×D) · mm300x1,000x700
Machine weight · kg35
Piping & refrigerant 3 specifications
Piping connections · Liquid (Flare) · mm6.4
Piping connections · Gas (Flare) · mm12.7
Piping connections · Drain · mmVP25 (External Dia. 32/Internal Dia. 25)

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 209 (printed page 208). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. *1: Power consumption values are based on conditions of rated external static pressure. *2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or ten (FXMQ140PA) levels of control. These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA. 208 stinU roodnI
View catalogue page · PDF 209

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 209
Read all text from this page and its facing page
PDF page 209 VRV Indoor Units Cleanliness Silver ion anti-bacterial drain pan Prevents the growth of slime, bacteria, and mould that cause odours and clogging. *Drain pan should be changed once every two to three years. Filter has anti-mould and antibacterial treatment Specifications MODEL FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE Power supply 1-phase, 220-240 V/220 V, 50/60 Hz Btu/h 7,500 9,600 12,300 15,400 19,100 Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 Btu/h 8,500 10,900 13,600 17,100 21,500 Heating capacity kW 2.5 3.2 4.0 5.0 6.3 Cooling 0.056 *1 0.060 *1 0.151 *1 0.128 *1 Power consumption kW Heating 0.044 *1 0.048 *1 0.139 *1 0.116 *1 Casing Galvanised steel plate m3/min 9/7.5/6.5 9.5/8/7 16/13/11 18/16.5/15 Airflow rate (HH/H/L) cfm 318/265/229 335/282/247 565/459/388 635/582/530 External static pressure Pa 30-100 (50) *2 30-160 (100) *2 50-200 (100) *2 Sound level (HH/H/L) dB(A) 33/31/29 34/32/30 39/37/35 41/39/37 Dimensions (H×W×D) mm 300x550x700 300x700x700 300x1,000x700 Machine weight kg 25 27 35 Liquid (Flare) 6.4 Piping Gas (Flare) mm 12.7 connections Drain VP25 (External Dia. 32/Internal Dia. 25) MODEL FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE Power supply 1-phase, 220-240 V/220 V, 50/60 Hz Btu/h 24,200 30,700 38,200 47,800 54,600 Cooling capacity kW 7.1 9.0 11.2 14.0 16.0 Btu/h 27,300 34,100 42,700 54,600 61,400 Heating capacity kW 8.0 10.0 12.5 16.0 18.0 Cooling 0.138 *1 0.185 *1 0.215 *1 0.284 *1 0.405 *1 Power consumption kW Heating 0.127 *1 0.173 *1 0.203 *1 0.272 *1 0.380 *1 Casing Galvanised steel plate m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32 Airflow rate (HH/H/L) cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130 External static pressure Pa 50-200 (100) *2 50-140 (100) *2 Sound level (HH/H/L) dB(A) 42/40/38 43/41/39 44/42/40 46/45/43 Dimensions (H×W×D) mm 300×1,000×700 300×1,400×700 Machine weight kg 35 45 46 Liquid (Flare) 9.5 Piping Gas (Flare) mm 15.9 connections Drain VP25 (External Dia. 32/Internal Dia. 25) Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. *1: Power consumption values are based on conditions of rated external static pressure. *2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or ten (FXMQ140PA) levels of control. These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA. 208 stinU roodnI FACING PAGE — PDF page 208 Middle-High Static Pressure Duct Type FXMQ-PA Middle and high static pressure allows for flexible duct design Design flexibility Using a DC fan motor, the external static pressure can be controlled within a range of 30 Pa* to 200 Pa*. Adjustable external static pressure 30Pa* 200Pa *30 Pa – 100 Pa for FXMQ20PA-32PA *30 Pa – 160 Pa for FXMQ40PA *50 Pa – 200 Pa for FXMQ50PA-125PA *50 Pa – 140 Pa for FXMQ140PA Easy installation “Airflow rate auto adjustment function” at field setting (local setting by remote controller) Rated airflow • All models are only 300 mm in height and the weight of the FXMQ40-140PA has been reduced. • Drain pump is equipped as standard accessory with 700 mm lift. Comfort • Control of the airflow rate can be selected from 3-step control and Auto. Auto airflow rate control can be selected with wired remote controller. • Low operation sound level: down to 29 dB(A) Energy saving • DC fan motor is used to realise energy-saving operation. Easy maintenance Inspection and cleaning is facilitated by separating the drain pipe and inspection opening and by the drain pan maintenance check hole. 207 )PSE( erusserp citats lanretxE Duct resistance at designing system rpm 1 *This function is not available with FXMQ140PAVE. Actual duct *This function can only be set via wired remote controller. rpm 2 resistance Field setting Various adjustments are required without “airflow rate (Due to excess or deficiency of Design Installation airflow) e.g. Duct re-construction, auto adjustment function” Motor replacement, Damper replacement, etc. rpm 7 System operation Field setting Innovating rpm 8 with “airflow rate Function! Design Installation auto adjustment function” by remote controller <Mechanism> Airflow 1. During field setting, power input of DC fan is detected. 2. External static pressure is estimated from power input of DC fan because PCB of Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated FXMQ-PA has table of external static pressure vs. power input of DC fan. airflow. (Refer to Engineering Data Book for details) 3. Actual duct resistance is calculated according to 1 and 2. ”Airflow rate auto adjustment function” should be used at field setting only. 4. Fan speed is automatically adjusted to produce rated airflow. Separate drain pipe and inspection opening Drain pan maintenance check hole

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗