FXMQ20PAVE is a Daikin indoor unit in the FXMQ-PA series, concealed ceiling ducted medium–high static pressure type. Its rated cooling capacity is 2.2 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 2.2 kW
- Power supply
- 1-phase, 220-240 V/220 V, 50/60 Hz
- Dimensions (H×W×D)
- 300x550x700 mm
- Weight
- 25 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FXMQ20PAVE specifications
| Rated capacity 4 specifications | |
|---|---|
| Cooling capacity · Btu/h | 7,500 |
| Cooling capacity · kW | 2.2 |
| Heating capacity · Btu/h | 8,500 |
| Heating capacity · kW | 2.5 |
| Electrical & efficiency 3 specifications | |
| Power supply | 1-phase, 220-240 V/220 V, 50/60 Hz |
| Power consumption · Cooling · kW | 0.056 *1 |
| Power consumption · Heating · kW | 0.044 *1 |
| Airflow & sound 4 specifications | |
| Airflow rate (HH/H/L) · m3/min | 9/7.5/6.5 |
| Airflow rate (HH/H/L) · cfm | 318/265/229 |
| External static pressure · Pa | 30-100 (50) *2 |
| Sound level (HH/H/L) · dB(A) | 33/31/29 |
| Dimensions & weight 3 specifications | |
| Casing | Galvanised steel plate |
| Dimensions (H×W×D) · mm | 300x550x700 |
| Machine weight · kg | 25 |
| Piping & refrigerant 3 specifications | |
| Piping connections · Liquid (Flare) · mm | 6.4 |
| Piping connections · Gas (Flare) · mm | 12.7 |
| Piping connections · Drain · mm | VP25 (External Dia. 32/Internal Dia. 25) |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 209 (printed page 208). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Power consumption values are based on conditions of rated external static pressure.
*2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or
ten (FXMQ140PA) levels of control.
These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA.
208
stinU
roodnI
View catalogue page · PDF 209
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 209
VRV Indoor Units
Cleanliness
Silver ion anti-bacterial drain pan
Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
*Drain pan should be changed once every two to three years.
Filter has anti-mould and antibacterial treatment
Specifications
MODEL FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Btu/h 8,500 10,900 13,600 17,100 21,500
Heating capacity
kW 2.5 3.2 4.0 5.0 6.3
Cooling 0.056 *1 0.060 *1 0.151 *1 0.128 *1
Power consumption kW
Heating 0.044 *1 0.048 *1 0.139 *1 0.116 *1
Casing Galvanised steel plate
m3/min 9/7.5/6.5 9.5/8/7 16/13/11 18/16.5/15
Airflow rate (HH/H/L)
cfm 318/265/229 335/282/247 565/459/388 635/582/530
External static pressure Pa 30-100 (50) *2 30-160 (100) *2 50-200 (100) *2
Sound level (HH/H/L) dB(A) 33/31/29 34/32/30 39/37/35 41/39/37
Dimensions (H×W×D) mm 300x550x700 300x700x700 300x1,000x700
Machine weight kg 25 27 35
Liquid (Flare) 6.4
Piping
Gas (Flare) mm 12.7
connections
Drain VP25 (External Dia. 32/Internal Dia. 25)
MODEL FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 7.1 9.0 11.2 14.0 16.0
Btu/h 27,300 34,100 42,700 54,600 61,400
Heating capacity
kW 8.0 10.0 12.5 16.0 18.0
Cooling 0.138 *1 0.185 *1 0.215 *1 0.284 *1 0.405 *1
Power consumption kW
Heating 0.127 *1 0.173 *1 0.203 *1 0.272 *1 0.380 *1
Casing Galvanised steel plate
m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32
Airflow rate (HH/H/L)
cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
External static pressure Pa 50-200 (100) *2 50-140 (100) *2
Sound level (HH/H/L) dB(A) 42/40/38 43/41/39 44/42/40 46/45/43
Dimensions (H×W×D) mm 300×1,000×700 300×1,400×700
Machine weight kg 35 45 46
Liquid (Flare) 9.5
Piping
Gas (Flare) mm 15.9
connections
Drain VP25 (External Dia. 32/Internal Dia. 25)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Power consumption values are based on conditions of rated external static pressure.
*2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or
ten (FXMQ140PA) levels of control.
These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA.
208
stinU
roodnI
FACING PAGE — PDF page 208
Middle-High Static Pressure Duct Type
FXMQ-PA
Middle and high static pressure allows for flexible duct design
Design flexibility
Using a DC fan motor, the external static pressure can
be controlled within a range of 30 Pa* to 200 Pa*.
Adjustable external static pressure
30Pa* 200Pa
*30 Pa – 100 Pa for FXMQ20PA-32PA
*30 Pa – 160 Pa for FXMQ40PA
*50 Pa – 200 Pa for FXMQ50PA-125PA
*50 Pa – 140 Pa for FXMQ140PA
Easy installation
“Airflow rate auto adjustment function” at field setting
(local setting by remote controller)
Rated airflow
• All models are only 300 mm in height and the weight of the FXMQ40-140PA has been reduced.
• Drain pump is equipped as standard accessory with 700 mm lift.
Comfort
• Control of the airflow rate can be selected from 3-step control and Auto. Auto airflow rate control can
be selected with wired remote controller.
• Low operation sound level: down to 29 dB(A)
Energy saving
• DC fan motor is used to realise energy-saving operation.
Easy maintenance
Inspection and cleaning is facilitated by separating the drain pipe
and inspection opening and by the drain pan maintenance check hole.
207
)PSE(
erusserp
citats
lanretxE
Duct resistance at
designing system
rpm 1
*This function is not available with FXMQ140PAVE. Actual duct
*This function can only be set via wired remote controller. rpm 2 resistance
Field setting Various adjustments are required
without “airflow rate (Due to excess or deficiency of
Design Installation airflow) e.g. Duct re-construction,
auto adjustment function”
Motor replacement, Damper
replacement, etc.
rpm 7 System
operation
Field setting Innovating
rpm 8
with “airflow rate Function!
Design Installation
auto adjustment function”
by remote controller
<Mechanism> Airflow
1. During field setting, power input of DC fan is detected.
2. External static pressure is estimated from power input of DC fan because PCB of Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated
FXMQ-PA has table of external static pressure vs. power input of DC fan. airflow. (Refer to Engineering Data Book for details)
3. Actual duct resistance is calculated according to 1 and 2. ”Airflow rate auto adjustment function” should be used at field setting only.
4. Fan speed is automatically adjusted to produce rated airflow.
Separate drain pipe and inspection opening
Drain pan maintenance
check hole