FXDSQ32AVM is a Daikin indoor unit in the FXDSQ-A series, concealed ceiling ducted 3d airflow type. Its rated cooling capacity is 3.6 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 3.6 kW
- Power supply
- 1-phase, 220-240/220-230 V, 50/60 Hz
- Dimensions (H×W×D)
- 200×700×450 mm
- Weight
- 17 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FXDSQ32AVM specifications
| Rated capacity 4 specifications | |
|---|---|
| Cooling capacity · Btu/h | 12,300 |
| Cooling capacity · kW | 3.6 |
| Heating capacity · Btu/h | 13,600 |
| Heating capacity · kW | 4.0 |
| Electrical & efficiency 3 specifications | |
| Power supply | 1-phase, 220-240/220-230 V, 50/60 Hz |
| Power consumption *1 · Cooling · kW | 0.032 |
| Power consumption *1 · Heating · kW | 0.028 |
| Airflow & sound 4 specifications | |
| Airflow rate (H/HM/M/ML/L) · m3/min | 10.0/9.3/8.6/7.9/7.2 |
| Airflow rate (H/HM/M/ML/L) · cfm | 353/328/304/279/254 |
| External static pressure · Pa | 10-0 *2 |
| Sound level (H/HM/M/ML/L)*1 *3 · dB(A) | 34/32/30/29/27 |
| Dimensions & weight 3 specifications | |
| Casing | Galvanized steel plate |
| Dimensions (H×W×D) · mm | 200×700×450 |
| Machine weight · kg | 17 |
| Piping & refrigerant 3 specifications | |
| Piping connections · Liquid (Flare) · mm | 6.4 |
| Piping connections · Gas (Flare) · mm | 12.7 |
| Piping connections · Drain · mm | PVC26 (External Dia. 26 / Internal Dia. 20) |
| Controls & accessories 3 specifications | |
| 3D Auto swing panel · Dimensions (H×W×D) · mm | 180×722×70 |
| 3D Auto swing panel · Colour | Fresh white |
| 3D Auto swing panel · Weight · kg | 1.0 |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 201 (printed page 200). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Height difference: 0 m.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 5 m, Height difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Values are based on external static pressure of 10 Pa.
*2: External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory setting is 10 Pa )
*3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
200
)C°(
tniopteS
VRV Indoor Units
Cooling Heating
30°C near ceiling
Room temperature is
calculated as 27°C in the area which
is in the vicinity of the person.
24°C near floor 20°C near floor 20°C near floor
Absence Presence
Example
• When there are no 2288°°CC
people in a room, the 2277°°CC
set temperature is 2266°°CC 2266°°CC
shifted automatically.
After After Time
30 min another 30 min
stinU
roodnI
View catalogue page · PDF 201
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 201
Comfort and energy saving preventing over cooling / heating
Sensing sensor mode • Cooling setpoint: 26°C
• Shift temperature: 1.0°C
• Shift time: 30 min.
Sensing sensor low mode (default: OFF) • Limit cooling temperature: 30°C
28
27
26
Automatically
Occupied Unoccupied reverts when
people return.
Sensing sensor stop mode (default: OFF)
• Based on preset user conditions, the system automatically stops operation if the room is unoccupied.
*Adjustment is possible for shift time and set temperature by local setting.
Specifications
MODEL FXDSQ20AVM FXDSQ25AVM FXDSQ32AVM FXDSQ40AVM FXDSQ50AVM FXDSQ63AVM
Power supply 1-phase, 220-240/220-230 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating capacity
kW 2.5 3.2 4.0 5.0 6.3 8.0
Cooling 0.028 0.029 0.032 0.049 0.054
Power consumption *1 kW
Heating 0.024 0.025 0.028 0.045 0.050
Casing Galvanized steel plate
m3/min 8.7/8.1/7.6/7.0/6.5 9.0/8.5/8.0/7.5/7.0 10.0/9.3/8.6/7.9/7.2 12.0/11.2/10.5/9.7/9.0 15.0/14.0/13.0/11.5/10.5 19.0/17.0/15.0/13.0/11.5
Airflow rate (H/HM/M/ML/L)
cfm 307/286/268/247/229 318/300/282/265/247 353/328/304/279/254 424/395/371/342/318 530/494/459/406/371 671/600/530/459/406
External static pressure Pa 10-0 *2
Sound level (H/HM/M/ML/L)*1 *3 dB(A) 31/29/27/26/24 31/29/27/26/24 34/32/30/29/27 39/37/35/33/31 39/37/35/33/30
Dimensions (H×W×D) mm 200×700×450 200×900×450 200×1,100×450
Machine weight kg 17 20 23
Liquid (Flare) 6.4 9.5
Piping
Gas (Flare) mm 12.7 15.9
connections
Drain PVC26 (External Dia. 26 / Internal Dia. 20)
3D Auto Dimensions (H×W×D) mm 180×722×70 180×922×70 180×1,122×70
swing Colour Fresh white
panel Weight kg 1.0 1.5 2.0
Notes: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Height difference: 0 m.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 5 m, Height difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Values are based on external static pressure of 10 Pa.
*2: External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory setting is 10 Pa )
*3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
200
)C°(
tniopteS
VRV Indoor Units
Cooling Heating
30°C near ceiling
Room temperature is
calculated as 27°C in the area which
is in the vicinity of the person.
24°C near floor 20°C near floor 20°C near floor
Absence Presence
Example
• When there are no 2288°°CC
people in a room, the 2277°°CC
set temperature is 2266°°CC 2266°°CC
shifted automatically.
After After Time
30 min another 30 min
stinU
roodnI
FACING PAGE — PDF page 200
3D Airflow Duct with Sensing Type
FXDSQ-A
3D airflow with sensing function for comfort and energy savings
Comfort
3D airflow
The wide coverage of the airflow angle
creates a comfortable 3D airflow.
• Horizontal & Vertical direction can be adjusted freely by
the remote controller settings as to provide 3D airflow to
every corner of the room.
• Can freely select 5 positions and swing mode for each
up/down and left/right direction with remote controller.
5
Horizontal Cooling range 6 0 ° 0 ° Heating range
flaps of swing of swing
Vertical flaps 45° 45°
5-step & auto airflow control
• Control of airflow rate can be selected from 5-step and Auto to provide comfortable airflow.
Installation flexibility
Only 450 mm
Slim design
200 mm
• Slim and compact design with a height of only 200 mm and the depth
of only 450 mm which is suitable to install in limited spaces.
* Panel dimensions are not included.
Daikin advanced sensing technology
Dual sensors
Infrared presence sensor
The presence sensor detects where people are and adjusts the airflow direction
accordingly.
Infrared floor sensor
The sensor detects the floor temperature and automatically adjusts operation of the
indoor unit to reduce the temperature difference between the ceiling and the floor.
199