Back to resultsSpecification results
Daikin FXB(P)Q-P — representative product image
Representative image · Vietnamese catalogue, PDF 222 ↗
Indoor unitFXB(P)Q-P →

FXBQ40PVE

Daikin · Cleanroom air conditioner

FXBQ40PVE is a Daikin indoor unit in the FXB(P)Q-P series, cleanroom air conditioner type. Its rated cooling capacity is 4.5 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
4.5 kW
Power supply
1-phase, 220-240 V/220 V, 50/60 Hz
Dimensions (H×W×D)
492×1,788×1,000 mm
Weight
See specifications
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FXBQ40PVE specifications

FXBQ40PVE specifications · PCVVN2507Aaprv
Rated capacity 4 specifications
Cooling capacity · Btu/h15,400
Cooling capacity · kW4.5
Heating capacity · Btu/h17,100
Heating capacity · kW5.0
Electrical & efficiency 3 specifications
Power supply1-phase, 220-240 V/220 V, 50/60 Hz
Power consumption · Cooling · kW0.31
Power consumption · Heating · kW0.31
Airflow & sound 3 specifications
Airflow rate (H/L) · m3/min19.5/17.5
Airflow rate (H/L) · cfm688/618
Sound level (H/L) *4 · dB(A)44/42
Dimensions & weight 3 specifications
Indoor unit weight · kg140 *3
CasingGalvanised steel plate
Dimensions (H×W×D) · mm492×1,788×1,000
Piping & refrigerant 3 specifications
Piping connections · Liquid (Flare) · mm6.4
Piping connections · Gas (Flare) · mm12.7
Piping connections · Drain · mmPT1B
Filters 3 specifications
Intake filter efficiency *170% by gravimetric method
Outlet HEPA filter efficiency *299.97% by DOP method *5
Filter(Option) · HEPA filter · ModelBAFH82A50
Controls & accessories 4 specifications
MODEL · Outlet unitIntegrated with the indoor unit
Outlet unit weight · kg–
Panel (Option) · Ceiling intake type · ModelBYB82A50C
Panel (Option) · Floor-level intake type · ModelBYB82A50W

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 223 (printed page 222). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) *1: An intake air filter is only attached to the ceiling intake type. *2: HEPA filter sold separately. The dust collection efficiency of HEPA filter is 99.97%. However, air may slightly leak around the filter when installing. *3: Weight including HEPA filter and panel. *4: Anechoic chamber conversion value under JIS B 8616 test conditions. Value usually increases slightly in practice due to surrounding conditions. *5: The clean room air conditioner does not support DOP testing (leak test) based on GMP standards (Standards for Manufacturing Control and Quality Control for Medical Devices ) due to slight leakage at time of product installation. *6: Weight including panel. *In the case of an installation in an operating theatre etc. where an air conditioner malfunction may have serious consequences, please build in redundancy with two or more outdoor units. Because the ceiling intake type provides concentrated air conditioning that blows directly under the outlet. Use the floor-level intake type in Accordingly, please be aware of the following. the following kind of locations. Warning • Sufficient heating may not be achieved near the floor or at locations far from the outlet. • Locations in which heating of • In the case of utilization in a hospital, some patients may be susceptible to cool drafts, so please ensure that they do not come directly under the outlet. the lower part or the entire • Install multiple units using two or more outdoor unit systems for installations to rooms such as operating rooms where the failure of the air room is important. conditioner may have serious consequences. • Locations necessitating a • In order to maintain static pressure in a room, the indoor fan continues to operate even when an abnormality occurs due to the thermostat shutting particularly high cleanliness off, defrost operation, protection device operation, or similar issue. factor and in which there are • When incorporating outdoor air from the fresh air intake, install a damper or similar device to the duct routing and have it interlocked with the indoor many people. fan so that the outdoor air is shut out when the fan stops. The air that incorporates the suction filter may flow backward and allow dust trapped in the filter to return to the room. • When using gas to disinfect hospital operating rooms where this unit is installed, stop operation and cover the air inlet and outlet with plastic sheets to prevent the gas from reaching and damaging the air conditioner. 222 stinU roodnI
View catalogue page · PDF 223

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 223
Read all text from this page and its facing page
PDF page 223 VRV Indoor Units Antibacterial Suppresses the propagation of bacteria in the duct with a proprietary antibacterial coating The filter implements an antibacterial treatment with a new coating combining a silver-based inorganic antibacterial material (an organic antibacterial material that is effective against germs) that prevents mould. This enhances the antibacterial properties of the duct. An antibacterial treatment using a silver-based organic substance reduces mould. Antibacterial fiber used in the intake filter Fan Intake filter With a long-life filter employing anti-mould antibacterial fiber near the intake, cleaning performance is further enhanced. * Please be aware that antibacterial products suppress the propagation of bacteria but do not have a sterilizing effect. Also, mould may grow in places where dust or soot accumulates. * A material for which the registered safety was verified by Japanese chemicals and dangerous substances regulation law (Act on the Evaluation of Chemical Substances and Regulation of Their Outlet panel HEPA filter Sheet steel Intake panel Manufacture, etc) is used for the antibacterial material. (punching metal) drain pan (punching metal) * Periodic maintenance is required (such as cleaning the air filter and washing the inside to the unit). (antibacterial treated) Specifications Type Integrated outlet unit model Separate outlet unit model Indoor unit FXBQ40PVE FXBQ50PVE FXBQ63PVE FXBPQ63PVE MODEL Outlet unit Integrated with the indoor unit BAF82A63 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz Btu/h 15,400 19,100 24,200 Cooling capacity kW 4.5 5.6 7.1 Btu/h 17,100 21,500 27,300 Heating capacity kW 5.0 6.3 8.0 Cooling 0.31 0.45 Power consumption kW Heating 0.31 0.45 Intake filter efficiency *1 70% by gravimetric method Outlet HEPA filter efficiency *2 99.97% by DOP method *5 Indoor unit weight kg 140 *3 185 *3 120 *6 Casing Galvanised steel plate m3/min 19.5/17.5 26/22.5 Airflow rate (H/L) cfm 688/618 918/794 Sound level (H/L) *4 dB(A) 44/42 Dimensions (H×W×D) mm 492×1,788×1,000 492×1,788×1,300 492×1,078×1,300 Outlet unit weight kg – 65 *3 Liquid (Flare) 6.4 9.5 Piping Gas (Flare) mm 12.7 15.9 connections Drain PT1B Filter(Option) HEPA filter BAFH82A50 BAFH82A63 Panel Ceiling intake type Model BYB82A50C BYB82A63C BYB82A63CP (Option) Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) *1: An intake air filter is only attached to the ceiling intake type. *2: HEPA filter sold separately. The dust collection efficiency of HEPA filter is 99.97%. However, air may slightly leak around the filter when installing. *3: Weight including HEPA filter and panel. *4: Anechoic chamber conversion value under JIS B 8616 test conditions. Value usually increases slightly in practice due to surrounding conditions. *5: The clean room air conditioner does not support DOP testing (leak test) based on GMP standards (Standards for Manufacturing Control and Quality Control for Medical Devices ) due to slight leakage at time of product installation. *6: Weight including panel. *In the case of an installation in an operating theatre etc. where an air conditioner malfunction may have serious consequences, please build in redundancy with two or more outdoor units. Because the ceiling intake type provides concentrated air conditioning that blows directly under the outlet. Use the floor-level intake type in Accordingly, please be aware of the following. the following kind of locations. Warning • Sufficient heating may not be achieved near the floor or at locations far from the outlet. • Locations in which heating of • In the case of utilization in a hospital, some patients may be susceptible to cool drafts, so please ensure that they do not come directly under the outlet. the lower part or the entire • Install multiple units using two or more outdoor unit systems for installations to rooms such as operating rooms where the failure of the air room is important. conditioner may have serious consequences. • Locations necessitating a • In order to maintain static pressure in a room, the indoor fan continues to operate even when an abnormality occurs due to the thermostat shutting particularly high cleanliness off, defrost operation, protection device operation, or similar issue. factor and in which there are • When incorporating outdoor air from the fresh air intake, install a damper or similar device to the duct routing and have it interlocked with the indoor many people. fan so that the outdoor air is shut out when the fan stops. The air that incorporates the suction filter may flow backward and allow dust trapped in the filter to return to the room. • When using gas to disinfect hospital operating rooms where this unit is installed, stop operation and cover the air inlet and outlet with plastic sheets to prevent the gas from reaching and damaging the air conditioner. 222 stinU roodnI FACING PAGE — PDF page 222 Clean Room Air Conditioner FXB(P)Q-P Suitable for hospitals and other clean spaces Easily provides the high Select the air flow system and cleanliness environment installation method to match the required by various industries layout and purpose of the room Daikin’s clean room air conditioners are specially Two types of clean room air conditioners are designed to achieve an environment cleanliness available – an integrated unit model and a class 10,000. These air conditioners easily realize a separate outlet unit model. cleanliness-class environment and help create a It is also possible to configure the air flow system proper environment of hospitals, food and to ceiling intake or floor-level intake according to beverage factories, electronics factories, and other the panel selected. spaces that require clean air. This flexible design enables the air conditioner to easily adopt to any room layout or use. Instances of installation by type (for a hospital) Ceiling intake type Floor-level intake type Type (high speed contracted flow/high ceiling model) (gentle wind distribution/high cleanness class model) Easy to increase the cleanness and air-conditioning effect. Construction work is simple and a ceiling installation is possible. Features A low flow speed prevents drying of the affected part Dust filtering and air-conditioning can be started immediately. and the experience of drafts. Cleanness class*1 100,000 to 10,000 10,000 Wind speed 1.0 m/s or higher Approximately 0.5 m/s • Concentrated air conditioning centered directly under the unit • Total air conditioning with an emphasis on cleanliness • Easy installation Integrated outlet unit Intake (sourced locally) model Blow Applications: Surgery prep rooms, recovery rooms, nurse stations, etc. Applications: Operating theatres, delivery rooms, etc. method • Somewhat concentrated air conditioning centered • Total air conditioning with an emphasis on cleanliness directly under the outlet • Maintenance possible from a different room • Can provide air conditioning Separate in rooms with irregular shapes Outlet Air outlet unit unit conditioner Intake model (sourced locally) Applications: CCU*2, sterile rooms, etc. Applications: Premature nurseries, newborn nurseries, ICU*3, etc. * 1. Cleanliness class. A scale expressing the cleanliness of air established by NASA (National Aeronautics and Space Administration). Class 10,000 represents a state of less than 10,000 minute particles of diameter under 0.5 μm per cubic foot. For comparison, the cleanliness of a typical office is around class 1,000,000. * 2. CCU (Cardiac Care Unit). A ward dedicated to the admission of patients with myocardial infarctions and other heart diseases. * 3. ICU (Intensive Care Unit). A ward for the careful treatment and nursing of patients with serious illnesses, injuries, or recovering from operations. Prevents uncomfortable drafts with a low flow speed of approximately 0.5 m/s The floor-level intake system has a low flow speed of approximately 0.5 m/s. Filtration Class 10,000 clean room condition achieved with a HEPA filter (sold separately) The low pressure-loss HEPA filter (sold separately) demonstrates superior dust filtering performance and easily accomplishes an air cleanliness of class 10,000. * It may not be possible to maintain cleanliness in rooms with low air tightness. 221