FVGR250PV1

Daikin · Floor standing · Direct air blow · Packaged Inverter · R-410A

FVGR250PV1 is a Daikin indoor unit in the FVGR-P · Packaged series, floor standing · direct air blow · packaged inverter · r-410a type. Its reference system cooling capacity (*1) is 27 kW according to catalogue PCTPMT2309.

Reference system cooling capacity
27 kW
Power supply
1 Phase, 220–240 V, 50 Hz
Dimensions (H×W×D)
1,870×1,170×510 mm
Weight
149 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FVGR250PV1 specifications

FVGR250PV1 specifications · PCTPMT2309
System configuration 1 specifications
Unit combinationFVGR250PV1 + RZUR250PY1
Rated capacity 5 specifications
Cooling capacity (19.5°CWB) *1 · kW27.00
Cooling capacity (19.5°CWB) *1 (Max.) · kW27.00 (28.40)
Cooling capacity (19.5°CWB) *1 (Max.) · Btu/h92,000 (97,000)
Cooling capacity (19°CWB) *2 (Max.) · kW26.70 (28.10)
Cooling capacity (19°CWB) *2 (Max.) · Btu/h91,000 (96,000)
Electrical & efficiency 4 specifications
System power consumption (19.5°CWB) *1 · kW9.58
System power consumption (19°CWB) *2 · kW9.46
CSPF (19°CWB) *24.20
Power supply1 Phase, 220–240 V, 50 Hz
Airflow & sound 5 specifications
Air flow rate (H) · m³/min80
Air flow rate (H) · cfm2,830
Fan · Motor output · kW0.245×2
Fan · DriveDirect Drive
Sound level · dB(A)61
Dimensions & weight 3 specifications
Casing colourIvory White
Dimensions (H×W×D) · mm1,870×1,170×510
Machine weight · kg149
Piping & refrigerant 2 specifications
Drain · mmPS 1B Internal thread
Refrigerant · TypeR-410A

Catalogue source & rating conditions

Values are taken from PCTPMT2309, PDF page 4 (printed page 5). Daikin Inverter Air Cooled Packaged · PCTPMT2309.

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Note: *1. Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. *2. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. *3. Capacity is net, including a deduction for cooling for indoor fan motor heat. *4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. Consider location and soundproofing measures near residences. *5. The value is the external static pressure with standard pulley. *6. Max. 40 m if the outdoor unit is lower than the indoor unit. Packaged system: cooling capacity, system power consumption and CSPF refer to the stated indoor/outdoor pairing. Outdoor model pages use the FDR pairing as the reference, except the RZUR-P models, which use their respective FVGR-P pairings. Parenthetical capacities are the source maximum values. Optional equipment is shown separately in the PDF.
View catalogue page · PDF 4

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 4
Read all text from this page and its facing page
Note: *1. Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. *2. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. *3. Capacity is net, including a deduction for cooling for indoor fan motor heat. *4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. Consider location and soundproofing measures near residences. *5. The value is the external static pressure with standard pulley. *6. Max. 40 m if the outdoor unit is lower than the indoor unit. Packaged system: cooling capacity, system power consumption and CSPF refer to the stated indoor/outdoor pairing. Outdoor model pages use the FDR pairing as the reference, except the RZUR-P models, which use their respective FVGR-P pairings. Parenthetical capacities are the source maximum values. Optional equipment is shown separately in the PDF.

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗