TECHNICAL SPECIFICATION SHEET · DAIKIN

FVGR250PV1

Indoor unit · FVGR-P · Packaged · Floor standing · Direct air blow · Packaged Inverter · R-410A

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FVGR250PV1 specifications
System configuration
Unit combinationFVGR250PV1 + RZUR250PY1
Rated capacity
Cooling capacity (19.5°CWB) *1 · kW27.00
Cooling capacity (19.5°CWB) *1 (Max.) · kW27.00 (28.40)
Cooling capacity (19.5°CWB) *1 (Max.) · Btu/h92,000 (97,000)
Cooling capacity (19°CWB) *2 (Max.) · kW26.70 (28.10)
Cooling capacity (19°CWB) *2 (Max.) · Btu/h91,000 (96,000)
Electrical & efficiency
System power consumption (19.5°CWB) *1 · kW9.58
System power consumption (19°CWB) *2 · kW9.46
CSPF (19°CWB) *24.20
Power supply1 Phase, 220–240 V, 50 Hz
Airflow & sound
Air flow rate (H) · m³/min80
Air flow rate (H) · cfm2,830
Fan · Motor output · kW0.245×2
Fan · DriveDirect Drive
Sound level · dB(A)61
Dimensions & weight
Casing colourIvory White
Dimensions (H×W×D) · mm1,870×1,170×510
Machine weight · kg149
Piping & refrigerant
Drain · mmPS 1B Internal thread
Refrigerant · TypeR-410A

Source reference

PCTPMT2309 · PDF page 4 · Printed page 5
Daikin Inverter Air Cooled Packaged · PCTPMT2309

Open catalogue PDF · page 4
Model page: https://vrv.vn/spec/fvgr250pv1/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Note:
*1. Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*2. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*3. Capacity is net, including a deduction for cooling for indoor fan motor heat.
*4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. Consider location and soundproofing measures near residences.
*5. The value is the external static pressure with standard pulley.
*6. Max. 40 m if the outdoor unit is lower than the indoor unit.
Packaged system: cooling capacity, system power consumption and CSPF refer to the stated indoor/outdoor pairing. Outdoor model pages use the FDR pairing as the reference, except the RZUR-P models, which use their respective FVGR-P pairings. Parenthetical capacities are the source maximum values. Optional equipment is shown separately in the PDF.