FDR300QY1 is a Daikin indoor unit in the FDR-Q · Packaged series, duct type · packaged inverter · r-410a type. Its reference system cooling capacity (*1) is 35.2 kW according to catalogue PCTPMT2309.
- Reference system cooling capacity
- 35.2 kW
- Power supply
- 3 Phase, 380–415 V, 50 Hz
- Dimensions (H×W×D)
- 625×1,980×850 mm
- Weight
- 177 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FDR300QY1 specifications
| System configuration 1 specifications | |
|---|---|
| Unit combination | FDR300QY1 + RZUR300QY1 |
| Rated capacity 5 specifications | |
| Cooling capacity (19.5°CWB) *1 *3 · kW | 35.20 |
| Cooling capacity (19.5°CWB) *1 *3 (Max.) · kW | 35.20 (35.76) |
| Cooling capacity (19.5°CWB) *1 *3 (Max.) · Btu/h | 120,000 (122,000) |
| Cooling capacity (19°CWB) *2 *3 (Max.) · kW | 34.70 (35.20) |
| Cooling capacity (19°CWB) *2 *3 (Max.) · Btu/h | 118,000 (120,000) |
| Electrical & efficiency 4 specifications | |
| System power consumption (19.5°CWB) *1 *3 · kW | 11.28 |
| System power consumption (19°CWB) *2 *3 · kW | 11.19 |
| CSPF (19°CWB) *2 | 4.14 |
| Power supply | 3 Phase, 380–415 V, 50 Hz |
| Airflow & sound 6 specifications | |
| Air flow rate (H) · m³/min | 120 |
| Air flow rate (H) · cfm | 4,240 |
| External static pressure *5 · Pa | 150 |
| Fan · Motor output · kW | 1.5 |
| Fan · Drive | Belt Drive |
| Sound level · dB(A) | 59 |
| Dimensions & weight 3 specifications | |
| Casing colour | Galvanized Steel |
| Dimensions (H×W×D) · mm | 625×1,980×850 |
| Machine weight · kg | 177 |
| Piping & refrigerant 2 specifications | |
| Drain · mm | PS 1B Internal thread |
| Refrigerant · Type | R-410A |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCTPMT2309, PDF page 4 (printed page 6). Daikin Inverter Air Cooled Packaged · PCTPMT2309.
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Note:
*1. Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*2. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*3. Capacity is net, including a deduction for cooling for indoor fan motor heat.
*4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. Consider location and soundproofing measures near residences.
*5. The value is the external static pressure with standard pulley.
*6. Max. 40 m if the outdoor unit is lower than the indoor unit.
Packaged system: cooling capacity, system power consumption and CSPF refer to the stated indoor/outdoor pairing. Outdoor model pages use the FDR pairing as the reference, except the RZUR-P models, which use their respective FVGR-P pairings. Parenthetical capacities are the source maximum values. Optional equipment is shown separately in the PDF.
View catalogue page · PDF 4
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
Note:
*1. Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*2. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*3. Capacity is net, including a deduction for cooling for indoor fan motor heat.
*4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. Consider location and soundproofing measures near residences.
*5. The value is the external static pressure with standard pulley.
*6. Max. 40 m if the outdoor unit is lower than the indoor unit.
Packaged system: cooling capacity, system power consumption and CSPF refer to the stated indoor/outdoor pairing. Outdoor model pages use the FDR pairing as the reference, except the RZUR-P models, which use their respective FVGR-P pairings. Parenthetical capacities are the source maximum values. Optional equipment is shown separately in the PDF.
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗