RXYQ40BYM is a Daikin outdoor unit in the VRV H series, heat pump type. Its rated cooling capacity is 112 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 112 kW
- Power supply
- 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
- Dimensions (H×W×D)
- (1,660×1,240×765)+(1,660×1,240×765) mm
- Weight
- 340+340 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
RXYQ40BYM specifications
| System configuration 1 specifications | |
|---|---|
| Combination units | RXYQ20BYM / RXYQ20BYM / — |
| Rated capacity 4 specifications | |
| Cooling capacity · Btu/h | 382,000 |
| Cooling capacity · kW | 112 |
| Heating capacity · Btu/h | 430,000 |
| Heating capacity · kW | 126 |
| Electrical & efficiency 7 specifications | |
| Power supply | 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz |
| Power consumption · Cooling · kW | 33.8 |
| Power consumption · Heating · kW | 34.0 |
| Capacity control · % | 4-100 |
| EER (TCVN13256: 2021) | 4.71 |
| Compressor · Type | Hermetically sealed scroll type |
| Compressor · Motor output · kW | (4.5+7.4)+ (4.5+7.4) |
| Airflow & sound 3 specifications | |
| Airflow rate · m³/min | 306+306 |
| Sound level (Cooling/Heating) · dB (A) | 68/69 |
| Sound power · dB | 93 |
| Dimensions & weight 3 specifications | |
| Casing colour | Ivory white (5Y7.5/1) |
| Dimensions (H×W×D) · mm | (1,660×1,240×765)+(1,660×1,240×765) |
| Machine weight · kg | 340+340 |
| Piping & refrigerant 4 specifications | |
| Refrigerant · Type | R-410A |
| Refrigerant · Charge · kg | 11.7+11.7 |
| Piping connections · Liquid · mm | 19.1 (Brazing) |
| Piping connections · Gas · mm | 41.3 (Brazing) |
| Operating conditions 2 specifications | |
| Operation range · Cooling · °CDB | –5 to 52 |
| Operation range · Heating · °CWB | –25 to 15.5 |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 56 (printed page 55). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
55
View catalogue page · PDF 56
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 56
Outdoor Units
VRV H Series
Specifications
Model RXYQ8BYM RXYQ10BYM RXYQ12BYM RXYQ14BYM RXYQ16BYM RXYQ18BYM RXYQ20BYM
— — — — — — —
Combination units
— — — — — — —
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 76,400 95,500 114,000 136,000 154,000 171,000 191,000
Cooling capacity
kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0
Btu/h 85,300 107,000 128,000 154,000 171,000 191,000 215,000
Heating capacity
kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0
Power Cooling kW 5.17 6.81 8.70 10.7 13.3 14.3 16.9
consumption Heating kW 5.33 6.99 9.67 11.0 13.5 14.9 17.0
Capacity control % 11-100 13-100 12-100 7-100 5-100 4-100
EER (TCVN13256: 2021) 5.45 5.11 4.75 4.85 4.74 4.88 4.71
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed scroll type
Compressor
Motor output kW 4.3 6.2 7.7 3.9+4.4 4.4+5.0 4.0+6.6 4.5+7.4
Airflow rate m³/min 155 169 181 260 266 258 306
Dimensions (H×W×D) mm 1,660×930×765 1,660×1,240×765
Machine weight kg 215 225 310 340
Sound level (Cooling/Heating) dB (A) 56/56 57/58 60/62 61/61 65/66
Sound power dB 78 79 83 85 90
Cooling °CDB –5 to 52
Operation range
Heating °CWB –25 to 15.5
Type R-410A
Refrigerant
Charge kg 6.9 7.1 7.2 9.7 9.9 11.7
Piping Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing)
connections Gas mm 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing)
Model RXYQ36BYM RXYQ38BYM RXYQ40BYM RXYQ42BYM RXYQ44BYM RXYQ46BYM RXYQ48BYM
RXYQ16BYM RXYQ18BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM
Combination units RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM RXYQ24BYM RXYQ24BYM
— — — — — — —
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 345,000 362,000 382,000 401,000 420,000 439,000 458,000
Cooling capacity
kW 101 106 112 117 123 128 134
Btu/h 386,000 406,000 430,000 450,000 471,000 491,000 512,000
Heating capacity
kW 113 119 126 132 138 144 150
Power Cooling kW 30.2 31.2 33.8 35.5 38.5 40.2 43.2
consumption Heating kW 30.5 31.9 34.0 37.1 39.2 41.8 44.4
Capacity control % 5-100 4-100 5-100
EER (TCVN13256: 2021) 4.72 4.79 4.71 4.61 4.56 4.48 4.45
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed scroll type
Compressor (4.4+5.0)+ (4.0+6.6)+ (4.5+7.4)+ (4.5+7.4)+ (4.5+7.4)+ (7.0+7.3)+ (7.7+8.0)+
Motor output kW
(4.5+7.4) (4.5+7.4) (4.5+7.4) (7.0+7.3) (7.7+8.0) (7.7+8.0) (7.7+8.0)
Airflow rate m³/min 266+306 258+306 306+306 306+430 430+430
(1,660×1,240×765)+ (1,660×1,750×765)+
Dimensions (H×W×D) mm (1,660×1,240×765)+(1,660×1,240×765) (1,660×1,750×765) (1,660×1,750×765)
Machine weight kg 310+340 340+340 340+385 385+385
Sound level (Cooling/Heating) dB (A) 66/67 68/69 69/70 70/70 71/71
Sound power dB 91 93
Cooling °CDB –5 to 52
Operation range
Heating °CWB –25 to 15.5
Type R-410A
Refrigerant
Charge kg 9.9+11.7 11.7+11.7
Piping Liquid mm 19.1 (Brazing)
connections Gas mm 41.3 (Brazing)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
55
FACING PAGE — PDF page 57
VRV H
Series
Heat Pump
56
seireS
H
VRV
*EER (TCVN13256: 2021)
According to TCVN13256: 2021 issued by the Ministry of Science and Technology of Vietnam,
EER (Energy Efficiency Ratio) is the index to describe the energy saving levels of VRV system.
EER (TCVN13256: 2021) is calculated according to the following formula:
φ100% φ75% φ50% φ25%
EER (TCVN13256: 2021) = 0.01 × + 0.42 × + 0.45 × + 0.12 ×
P P P P
100% 75% 50% 25%
φn%: Cooling capacity at n% heat load (kW)
Pn%: Input power at n% heat load (kW)
RXYQ22BYM RXYQ24BYM RXYQ26BYM RXYQ28BYM RXYQ30BYM RXYQ32BYM RXYQ34BYM
— — RXYQ12BYM RXYQ12BYM RXYQ12BYM RXYQ12BYM RXYQ14BYM
— — RXYQ14BYM RXYQ16BYM RXYQ18BYM RXYQ20BYM RXYQ20BYM
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
210,000 229,000 250,000 268,000 285,000 305,000 327,000
61.5 67.0 73.5 78.5 83.5 89.5 96.0
235,000 256,000 282,000 299,000 319,000 343,000 369,000
69.0 75.0 82.5 87.5 93.5 100 108
18.6 21.6 19.4 22.0 23.0 25.6 27.6
19.6 22.2 20.7 23.2 24.6 26.7 28.0
5-100 7-100 6-100
4.53 4.46 4.80 4.74 4.82 4.72 4.77
Ivory white (5Y7.5/1)
Hermetically sealed scroll type
(3.9+4.4)+
7.0+7.3 7.7+8.0 7.7+(3.9+4.4) 7.7+(4.4+5.0) 7.7+(4.0+6.6) 7.7+(4.5+7.4)
(4.5+7.4)
430 181+260 181+266 181+258 181+306 260+306
(1,660×1,240×765)+
1,660×1,750×765 (1,660×930×765)+(1,660×1,240×765)
(1,660×1,240×765)
385 225+310 225+340 310+340
67/67 68/68 64/65 66/67
90 86 87 91
–5 to 52
–25 to 15.5
R-410A
11.7 7.2+9.7 7.2+9.9 7.2+11.7 9.7+11.7
15.9 (Brazing) 19.1 (Brazing)
28.6 (Brazing) 34.9 (Brazing)
RXYQ50BYM RXYQ52BYM RXYQ54BYM RXYQ56BYM RXYQ58BYM RXYQ60BYM
RXYQ12BYM RXYQ12BYM RXYQ14BYM RXYQ16BYM RXYQ18BYM RXYQ20BYM
RXYQ18BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM
RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM RXYQ20BYM
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
476,000 496,000 518,000 536,000 553,000 573,000
139 145 152 157 162 168
534,000 558,000 584,000 601,000 621,000 645,000
156 163 171 176 182 189
39.9 42.5 44.5 47.1 48.1 50.7
41.6 43.7 45.0 47.5 48.9 51.0
6-100 5-100 4-100
4.78 4.72 4.74 4.72 4.76 4.71
Ivory white (5Y7.5/1)
Hermetically sealed scroll type
7.7+(4.0+6.6)+ 7.7+(4.5+7.4)+ (3.9+4.4)+(4.5+7.4)+ (4.4+5.0)+(4.5+7.4)+ (4.0+6.6)+(4.5+7.4)+ (4.5+7.4)+(4.5+7.4)+
(4.5+7.4) (4.5+7.4) (4.5+7.4) (4.5+7.4) (4.5+7.4) (4.5+7.4)
181+258+306 181+306+306 260+306+306 266+306+306 258+306+306 306+306+306
(1,660×930×765)+(1,660×1,240×765)+
(1,660×1,240×765) (1,660×1,240×765)+(1,660×1,240×765)+(1,660×1,240×765)
225+340+340 310+340+340 340+340+340
67/68 69/70 70/71
92 93 94 95
–5 to 52
–25 to 15.5
R-410A
7.2+11.7+11.7 9.7+11.7+11.7 9.9+11.7+11.7 11.7+11.7+11.7
19.1 (Brazing)
41.3 (Brazing)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗