RXYMQ6BVM is a Daikin outdoor unit in the VRV IV S series, cooling only / heat pump type. Its rated cooling capacity is 16 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 16 kW
- Power supply
- 1-phase, 220-240 V/220-230 V, 50/60 Hz
- Dimensions (H×W×D)
- 990×940×320 mm
- Weight
- 80 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
RXYMQ6BVM specifications
| System configuration 5 specifications | |
|---|---|
| Capacity index | 150 |
| Total capacity index of connectable indoor units · Combination (%) · 50% | 75 |
| Total capacity index of connectable indoor units · Combination (%) · 100% | 150 |
| Total capacity index of connectable indoor units · Combination (%) · 130% | 195 |
| Maximum number of connectable indoor units | 9 |
| Rated capacity 6 specifications | |
| Cooling capacity · Btu/h | 54,600 |
| Cooling capacity · kW | 16.0 |
| Heating capacity · Btu/h | 54,600 |
| Heating capacity · kW | 16.0 |
| kW | 16.0 |
| HP | 6 |
| Electrical & efficiency 6 specifications | |
| Power supply | 1-phase, 220-240 V/220-230 V, 50/60 Hz |
| Power consumption · Cooling · kW | 4.51 |
| Power consumption · Heating · kW | 3.59 |
| Capacity control · % | 15 to 100 |
| Compressor · Type | Hermetically sealed swing type |
| Compressor · Motor output (Cooling/Heating) · kW | 3.7 |
| Airflow & sound 2 specifications | |
| Airflow rate · m3/min | 80 |
| Sound level (Cooling/Heating) · dB(A) | 55/56 |
| Dimensions & weight 3 specifications | |
| Casing colour | Ivory white (5Y7.5/1) |
| Dimensions (H×W×D) · mm | 990×940×320 |
| Machine weight · kg | 80 |
| Piping & refrigerant 4 specifications | |
| Refrigerant · Type | R-410A |
| Refrigerant · Charge · kg | 4.0 |
| Piping connections · Liquid · mm | 9.5 (Flare) |
| Piping connections · Gas · mm | 19.1 (Brazing) |
| Operating conditions 2 specifications | |
| Operation range · Cooling · °CDB | -5 to 46 |
| Operation range · Heating · °CWB | -20 to 15.5 |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 135 (printed page 134). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp. : 27° CDB, 19° CWB, Outdoor temp. : 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20° CDB, Outdoor temp.: 7° CDB, 6° CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
Outdoor unit combinations
MODEL RXYMQ4AVE RXYMQ5BVM RXYMQ6BVM RXYMQ8AY1 RXYMQ9AY1
kW 11.2 14.0 16.0 22.4 24.0
HP 4 5 6 8 9
Capacity index 100 125 150 200 215
50% 50 62.5 75 100 107.5
Total capacity index
of connectable Combination (%) 100% 100 125 150 200 215
indoor units
130% 130 162.5 195 260 280
Maximum number of connectable indoor units 6 8 9 13 14
Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
134
seireS
S
VI
VRV
VRV IV S
Series
View catalogue page · PDF 135
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 135
Specifications
Heat Pump
MODEL RXYMQ4AVE RXYMQ5BVM RXYMQ6BVM RXYMQ8AY1 RXYMQ9AY1
Power supply 1-phase, 220-230 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380–415 V, 50 Hz
Btu/h 38,200 47,800 54,600 76,400 81,900
Cooling capacity
kW 11.2 14.0 16.0 22.4 24.0
Btu/h 42,700 47,800 54,600 85,300 88,700
Heating capacity
kW 12.5 14.0 16.0 25.0 26.0
Cooling 2.88 3.83 4.51 5.94 6.88
Power consumption kW
Heating 2.60 3.04 3.59 6.25 6.82
Capacity control % 24 to 100 15 to 100 20 to 100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed swing type Hermetically sealed scroll type
Compressor
Motor output
(Cooling/Heating) kW 1.92 3.2/3.5 3.7 3.8 4.8
Airflow rate m3/min 76 81 80 140
Dimensions (H×W×D) mm 990×940×320 1,430×940×320
Machine weight kg 71 78 80 138
Sound level (Cooling/Heating) dB(A) 52/54 53/54 55/56 57/58 58/59
Cooling °CDB -5 to 46
Operation range
Heating °CWB -20 to 15.5
Type R-410A
Refrigerant
Charge kg 2.9 3.4 4.0 5.8
Liquid 9.5 (Flare) 9.5 (Brazing)
Piping connections mm
Gas 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp. : 27° CDB, 19° CWB, Outdoor temp. : 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20° CDB, Outdoor temp.: 7° CDB, 6° CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
Outdoor unit combinations
MODEL RXYMQ4AVE RXYMQ5BVM RXYMQ6BVM RXYMQ8AY1 RXYMQ9AY1
kW 11.2 14.0 16.0 22.4 24.0
HP 4 5 6 8 9
Capacity index 100 125 150 200 215
50% 50 62.5 75 100 107.5
Total capacity index
of connectable Combination (%) 100% 100 125 150 200 215
indoor units
130% 130 162.5 195 260 280
Maximum number of connectable indoor units 6 8 9 13 14
Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
134
seireS
S
VI
VRV
VRV IV S
Series
FACING PAGE — PDF page 134
Outdoor Units
VRV IV S Series
Specifications
Cooling Only
MODEL RXMQ4AVE RXMQ5BVM RXMQ6BVM RXMQ8AY1 RXMQ9AY1
Power supply 1-phase, 220-230 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380–415 V, 50 Hz
Btu/h 38,200 47,800 54,600 76,400 81,900
Cooling capacity
kW 11.2 14.0 16.0 22.4 24.0
Power consumption kW 2.88 3.83 4.51 5.94 6.88
Capacity control % 24 to 100 15 to 100 20 to 100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed swing type Hermetically sealed scroll type
Compressor
Motor output kW 1.92 3.2 3.7 3.8 4.8
Airflow rate m3/min 76 81 80 140
Dimensions (H×W×D) mm 990×940×320 1,430×940×320
Machine weight kg 71 76 78 131
Sound level dB(A) 52 53 55 57 58
Operation range °CDB -5 to 46
Type R-410A
Refrigerant
Charge kg 2.9 3.4 4.0 5.8
Liquid 9.5 (Flare) 9.5 (Brazing)
Piping connections mm
Gas 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27° CDB, 19° CWB, Outdoor temp.: 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
Outdoor unit combinations
MODEL RXMQ4AVE RXMQ5BVM RXMQ6BVM RXMQ8AY1 RXMQ9AY1
kW 11.2 14.0 16.0 22.4 24.0
HP 4 5 6 8 9
Capacity index 100 125 150 200 215
50% 50 62.5 75 100 107.5
Total capacity index
of connectable Combination (%) 100% 100 125 150 200 215
indoor units
130% 130 162.5 195 260 280
Maximum number of connectable indoor units 6 8 9 13 14
Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
133
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗