RXQ78BYM is a Daikin outdoor unit in the VRV 6 A series, cooling only type. Its rated cooling capacity is 219 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 219 kW
- Power supply
- 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
- Dimensions (H×W×D)
- (1,660 × 1,750 × 765) + (1,660 × 1,750 × 765) + (1,660 × 1,750 × 765) mm
- Weight
- 354 + 354 + 354 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
RXQ78BYM specifications
| System configuration 1 specifications | |
|---|---|
| Combination units | RXQ26BYM / RXQ26BYM / RXQ26BYM |
| Rated capacity 2 specifications | |
| Cooling capacity · Btu/h | 747,000 |
| Cooling capacity · kW | 219 |
| Electrical & efficiency 6 specifications | |
| Power supply | 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz |
| Power consumption · kW | 70.5 |
| Capacity control | 3-100 |
| EER (TCVN13256: 2021) | — |
| Compressor · Type | Hermetically sealed scroll type |
| Compressor · Motor output · kW | 11.1 + 11.1 + 11.1 |
| Airflow & sound 2 specifications | |
| Airflow rate · m3/min | 411 + 411 + 411 |
| Sound level · dB(A) | 73 |
| Dimensions & weight 3 specifications | |
| Casing colour | Ivory white (5Y7.5/1) |
| Dimensions (H x W x D) · mm | (1,660 × 1,750 × 765) + (1,660 × 1,750 × 765) + (1,660 × 1,750 × 765) |
| Machine weight · kg | 354 + 354 + 354 |
| Piping & refrigerant 4 specifications | |
| Refrigerant · Type | R-410A |
| Refrigerant · Charge · kg | 11.7 + 11.7 + 11.7 |
| Piping connections · Liquid · mm | φ 22.2 (Brazing) |
| Piping connections · Gas · mm | φ 41.3 (Brazing) |
| Operating conditions 1 specifications | |
| Operation range · ºCDB | 10 to 52 |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 97 (printed page 96). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Indoor temp.: 27° CDB , 19° CWB / Outdoor temp.: 35° CDB / Equivalent piping length: 7.5m , Height difference: 0 m.
• Sound level : Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
95
View catalogue page · PDF 97
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 97
*EER (TCVN13256: 2021)
According to TCVN13256: 2021 issued by the Ministry of Science and Technology of Vietnam,
EER (Energy Efficiency Ratio) is the index to describe the energy saving levels of VRV system.
EER (TCVN13256: 2021) is calculated according to the following formula:
φ100% φ75% φ50% φ25%
EER (TCVN13256: 2021) = 0.01 × + 0.42 × + 0.45 × + 0.12 ×
P P P P
100% 75% 50% 25%
φn%: Cooling capacity at n% heat load (kW)
Pn%: Input power at n% heat load (kW)
RXQ70BYM RXQ72BYM RXQ74BYM RXQ76BYM RXQ78BYM
RXQ20BYM RXQ20BYM RXQ22BYM RXQ24BYM RXQ26BYM
RXQ24BYM RXQ26BYM RXQ26BYM RXQ26BYM RXQ26BYM
RXQ26BYM RXQ26BYM RXQ26BYM RXQ26BYM RXQ26BYM
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
669,000 689,000 706,000 727,000 747,000
196 202 207 213 219
59.6 62.9 64.9 67.2 70.5
3-100
— — — — —
Ivory white (5Y7.5/1)
Hermetically sealed scroll type
8.3 + 9.8 + 11.1 8.3 + 11.1 + 11.1 8.9 + 11.1 + 11.1 9.8 + 11.1 + 11.1 11.1 + 11.1 + 11.1
306 + 390 + 411 306 + 411 + 411 375 + 411 + 411 390 + 411 + 411 411 + 411 + 411
(1,660 × 1,240 × 765) + (1,660 × 1,750 × 765) +
(1,660 × 1,750 × 765) + (1,660 × 1,750 × 765) + (1,660 × 1,750 × 765)
(1,660 × 1,750 × 765)
293 + 354 + 354 354 + 354 + 354
72 73
10 to 52
R-410A
11.7 + 11.7 + 11.7
φ 19.1 (Brazing) φ 22.2 (Brazing)
φ 41.3 (Brazing)
96
seireS
A
6
VRV
VRV 6 A
Series
Cooling Only
FACING PAGE — PDF page 96
Outdoor Units
VRV 6 A Series
Specifications
Model RXQ62BYM RXQ64BYM RXQ66BYM RXQ68BYM
RXQ20BYM RXQ20BYM RXQ20BYM RXQ20BYM
Combination units RXQ20BYM RXQ20BYM RXQ20BYM RXQ22BYM
RXQ22BYM RXQ24BYM RXQ26BYM RXQ26BYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 590,000 611,000 631,000 648,000
Cooling capacity
kW 173 179 185 190
Power consumption kW 49.7 52.0 55.3 57.3
Capacity control 3-100
EER (TCVN13256: 2021) — — — —
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed scroll type
Compressor
Motor output kW 8.3 + 8.3 + 8.9 8.3 + 8.3 + 9.8 8.3 + 8.3 + 11.1 8.3 + 8.9 + 11.1
Airflow rate m3/min 306 + 306 + 375 306 + 306 + 390 306 + 306 + 411 306 + 375 + 411
(1,660 × 1,240 × 765) +
Dimensions (H x W x D) mm (1,660 × 1,240 × 765) + (1,660 × 1,240 × 765) + (1,660 × 1,750 × 765) (1,660 × 1,750 × 765) +
(1,660 × 1,750 × 765)
Machine weight kg 293 + 293 + 354 293 + 354 + 354
Sound level dB(A) 71 72
Operation range ºCDB 10 to 52
Type R-410A
Refrigerant
Charge kg 11.7 + 11.7 + 11.7
Piping Liquid mm φ 19.1 (Brazing)
connections Gas mm φ 41.3 (Brazing)
Notes: Specifications are based on the following conditions;
• Indoor temp.: 27° CDB , 19° CWB / Outdoor temp.: 35° CDB / Equivalent piping length: 7.5m , Height difference: 0 m.
• Sound level : Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
95
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗