Back to resultsSpecification results
Daikin VRV X/A MAX — representative product image
Representative image · Vietnamese catalogue, PDF 115 ↗
Outdoor unitVRV X/A MAX →

RXQ52AMYMW

Daikin · Corrosion resistant

RXQ52AMYMW is a Daikin outdoor unit in the VRV X/A MAX series, corrosion resistant type. Its rated cooling capacity is 145 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
145 kW
Power supply
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Dimensions (H×W×D)
(1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) mm
Weight
(280+280+280) kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

RXQ52AMYMW specifications

RXQ52AMYMW specifications · PCVVN2507Aaprv
System configuration 1 specifications
Combination unitsRXQ16AYMW / RXQ18AYMW / RXQ18AYMW
Rated capacity 2 specifications
Cooling capacity · Btu/h495,000
Cooling capacity · kW145
Electrical & efficiency 5 specifications
Power supply3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Power consumption · kW43.5
Capacity control · %3-100
Compressor · TypeHermetically sealed scroll type
Compressor · Motor output · kW(3.5×1)+(3.5×1)+(4.0×1) +(4.0×1)+(4.0×1)+(4.0×1)
Airflow & sound 2 specifications
Airflow rate · m3/min257+257+257
Sound level · dB(A)65
Dimensions & weight 3 specifications
Casing colourMetallic brown
Dimensions (H×W×D) · mm(1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Machine weight · kg(280+280+280)
Piping & refrigerant 4 specifications
Refrigerant · TypeR-410A
Refrigerant · Charge · kg8.2+8.4+8.4
Piping connections · Liquid · mm19.1 (Brazing)
Piping connections · Gas · mm41.3 (Brazing)
Operating conditions 1 specifications
Operation range · °CDB10 to 49

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 115 (printed page 114). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. •Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. 113 When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
View catalogue page · PDF 115

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 115
Read all text from this page and its facing page
PDF page 115 VRV X/A MAX Series Cooling Only RXQ20AYMW RXQ18AMYMW RXQ20AMYMW RXQ22AMYMW RXQ24AMYMW RXQ26AMYMW RXQ28AMYMW RXQ30AMYMW — RXQ8AYMW RXQ8AYMW RXQ10AYMW RXQ12AYMW RXQ12AYMW RXQ12AYMW RXQ12AYMW — RXQ10AYMW RXQ12AYMW RXQ12AYMW RXQ12AYMW RXQ14AYMW RXQ16AYMW RXQ18AYMW 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 191,000 172,000 191,000 210,000 229,000 251,000 268,000 285,000 56.0 50.4 55.9 61.5 67.0 73.5 78.5 83.5 17.7 12.0 13.9 15.5 17.4 19.4 21.6 24.0 7-100 7-100 7-100 6-100 6-100 6-100 5-100 5-100 Metallic brown Hermetically sealed scroll type (5.6×1)+(3.5×1) (5.6×1)+(4.0×1) (3.8×1)+(6.3×1) (3.4×1)+(4.5×1) (3.4×1)+(5.6×1) (4.5×1)+(5.6×1) (5.6×1)+(5.6×1) (5.6×1)+(6.4×1) +(3.5×1) +(4.0×1) 297 178+178 178+191 191+191 191+257 1,657×1,240×765 (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×1,240×765) (310) (180+195) (195+195) (195+235) (195+280) 65 60 61 62 63 10 to 49 R-410A 11.8 5.9+6.7 5.9+6.8 6.7+6.8 6.8+6.8 6.8+7.4 6.8+8.2 6.8+8.4 15.9 (Brazing) 19.1 (Brazing) 28.6 (Brazing) 34.9 (Brazing) RXQ46AMYMW RXQ48AMYMW RXQ50AMYMW RXQ52AMYMW RXQ54AMYMW RXQ56AMYMW RXQ58AMYMW RXQ60AMYMW RXQ14AYMW RXQ14AYMW RXQ14AYMW RXQ16AYMW RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ20AYMW RXQ14AYMW RXQ16AYMW RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ20AYMW RXQ20AYMW RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ20AYMW RXQ20AYMW RXQ20AYMW 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 444,000 461,000 478,000 495,000 512,000 532,000 553,000 573,000 130 135 140 145 150 156 162 168 36.7 38.9 41.3 43.5 45.9 48.3 50.7 53.1 3-100 3-100 3-100 3-100 3-100 3-100 2-100 2-100 Metallic brown Hermetically sealed scroll type (6.4×1)+(6.4×1) (6.4×1)+(3.5×1)+(3.5×1) (6.4×1)+(4.0×1)+(4.0×1) (3.5×1)+(3.5×1)+(4.0×1) ((44..00××11))++((44..00××11))++((44..00××11)) (4.0×1)+(4.0×1)+(4.0×1) (4.0×1)+(4.0×1)+(3.8×1) (3.8×1)+(6.3×1)+(3.8×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1)+(4.0×1) ++((44..00××11))++((44..00××11))++((44..00××11)) +(4.0×1)+(3.8×1)+(6.3×1) +(6.3×1)+(3.8×1)+(6.3×1) +(6.3×1)+(3.8×1)+(6.3×1) 257+257+257 257+257+297 257+297+297 297+297+297 (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (235+235+280) (235+280+280) (280+280+280) (280+280+310) (280+310+310) (310+310+310) 65 66 68 69 70 10 to 49 R-410A 7.4+7.4+8.4 7.4+8.2+8.4 7.4+8.4+8.4 8.2+8.4+8.4 8.4+8.4+8.4 8.4+8.4+11.8 8.4+11.8+11.8 11.8+11.8+11.8 19.1 (Brazing) 41.3 (Brazing) 114 seireS XAM A/X VRV FACING PAGE — PDF page 114 Outdoor Units VRV A MAX Series Specifications MODEL RXQ6AYMW RXQ8AYMW RXQ10AYMW RXQ12AYMW RXQ14AYMW RXQ16AYMW RXQ18AYMW — — — — — — — Combination units — — — — — — — Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 171,000 Cooling capacity kW 16.0 22.4 28.0 33.5 40.0 45.0 50.0 Power consumption kW 3.38 5.17 6.84 8.70 10.7 12.9 15.3 Capacity control % 25-100 20-100 13-100 12-100 11-100 10-100 10-100 Casing colour Metallic brown Type Hermetically sealed scroll type Compressor Motor output kW 2.3×1 3.4×1 4.5×1 5.6×1 6.4×1 (3.5×1)+(3.5×1) (4.0×1)+(4.0×1) Airflow rate m3/min 119 178 191 257 Dimensions (H×W×D) mm 1,657×930×765 1,657×1,240×765 Machine weight kg (180) (195) (235) (280) Sound level dB(A) 56 57 59 60 61 Operation range °CDB 10 to 49 Type R-410A Refrigerant Charge kg 5.9 6.7 6.8 7.4 8.2 8.4 Piping Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) connections Gas mm 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) MODEL RXQ32AMYMW RXQ34AMYMW RXQ36AMYMW RXQ38AMYMW RXQ40AMYMW RXQ42AMYMW RXQ44AMYMW RXQ14AYMW RXQ16AYMW RXQ18AYMW RXQ18AYMW RXQ20AYMW RXQ12AYMW RXQ12AYMW Combination units RXQ18AYMW RXQ18AYMW RXQ18AYMW RXQ20AYMW RXQ20AYMW RXQ12AYMW RXQ12AYMW — — — — — RXQ18AYMW RXQ20AYMW Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 307,000 324,000 341,000 362,000 382,000 399,000 420,000 Cooling capacity kW 90.0 95.0 100 106 112 117 123 Power consumption kW 26.0 28.2 30.6 33.0 35.4 32.7 35.1 Capacity control % 5-100 5-100 5-100 4-100 3-100 4-100 3-100 Casing colour Metallic brown Type Hermetically sealed scroll type Compressor (6.4×1)+(4.0×1) (3.5×1)+(3.5×1) (4.0×1)+(4.0×1) (4.0×1)+(4.0×1) (3.8×1)+(6.3×1) (5.6×1)+(5.6×1) (5.6×1)+(5.6×1) Motor output kW +(4.0×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1) +(3.8×1)+(6.3×1) +(3.8×1)+(6.3×1) +(4.0×1)+(4.0×1) +(3.8×1)+(6.3×1) Airflow rate m3/min 257+257 257+297 297+297 191+191+257 191+191+297 (1,657×930×765)+(1,657×930×765)+ Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765) Machine weight kg (235+280) (280+280) (280+310) (310+310) (195+195+280) (195+195+310) Sound level dB(A) 64 66 68 65 67 Operation range °CDB 10 to 49 Type R-410A Refrigerant Charge kg 7.4+8.4 8.2+8.4 8.4+8.4 8.4+11.8 11.8+11.8 6.8+6.8+8.4 6.8+6.8+11.8 Piping Liquid mm 19.1 (Brazing) connections Gas mm 34.9 (Brazing) 41.3 (Brazing) Notes: Specifications are based on the following conditions; •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. •Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. 113 When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗