Back to resultsSpecification results

RWHQ16THYM is a Daikin outdoor unit in the VRV IV Hot water heat recovery series, hot water heat recovery type. Its rated cooling capacity is 44.8 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
44.8 kW
Power supply
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Dimensions (H×W×D)
(1,657x930x765)+(1,657x930x765) mm
Weight
185+185 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

RWHQ16THYM specifications

RWHQ16THYM specifications · PCVVN2507Aaprv
System configuration 1 specifications
Combination unitsRWHQ8TYM / RWHQ8TYM / —
Rated capacity 2 specifications
Cooling capacity · Btu/h153,000
Cooling capacity · kW44.8
Electrical & efficiency 5 specifications
Power supply3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Power consumption · kW10.3
Capacity control · %10-100
Compressor · TypeHermetically Sealed Scroll Type
Compressor · Motor output · kW(3.4x1)+ (3.4x1)
Airflow & sound 2 specifications
Airflow rate · m3/min157+157
Sound level · dB(A)59
Dimensions & weight 3 specifications
Casing colourIvory white (5Y7.5/1)
Dimensions (HxWxD) · mm(1,657x930x765)+(1,657x930x765)
Machine weight · kg185+185
Piping & refrigerant 6 specifications
Refrigerant · TypeR-410A
Refrigerant · Charge · kg6.4+6.4
Piping connections (Indoor unit) · Liquid · mm12.7(Brazing)
Piping connections (Indoor unit) · Gas · mm28.6(Brazing)
Piping connections (Heat exchanger unit) · Inlet pipe · mm19.1(Brazing x 2)
Piping connections (Heat exchanger unit) · Outlet pipe · mm—
Operating conditions 1 specifications
Operation range · °CDB15 to 49

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 170 (printed page 169). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
View catalogue page · PDF 170

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 170
Read all text from this page and its facing page
PDF page 170 Outdoor Units VRV IV Heat Recovery Hot Water System Specifications High-COP Type MODEL RWHQ12THYM RWHQ14THYM RWHQ16THYM RWHQ18THYM RWHQ20THYM RWHQ22THYM RWHQ24THYM RWHQ6TYM RWHQ6TYM RWHQ8TYM RWHQ6TYM RWHQ6TYM RWHQ6TYM RWHQ8TYM Combination units RWHQ6TYM RWHQ8TYM RWHQ8TYM RWHQ6TYM RWHQ6TYM RWHQ8TYM RWHQ8TYM — — — RWHQ6TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 109,000 131,000 153,000 164,000 186,000 207,000 229,000 Cooling capacity kW 32.0 38.4 44.8 48.0 54.4 60.8 67.2 Power consumption kW 7.10 8.68 10.3 10.7 12.2 13.8 15.4 Capacity control % 10-100 7-100 Casing colour Ivory white (5Y7.5/1) Type Hermetically Sealed Scroll Type Compressor (2.4x1)+ (2.4x1)+ (3.4x1)+ (2.4x1)+(2.4x1)+ (2.4x1)+(2.4x1)+ (2.4x1)+(3.4x1)+ (3.4x1)+(3.4x1)+ Motor output kW (2.4x1) (3.4x1) (3.4x1) (2.4x1) (3.4x1) (3.4x1) (3.4x1) Airflow rate m3/min 119+119 119+157 157+157 119+119+119 119+119+157 119+157+157 157+157+157 Dimensions (HxWxD) mm (1,657x930x765)+(1,657x930x765) (1,657x930x765)+(1,657x930x765)+(1,657x930x765) Machine weight kg 185+185 185+185+185 Sound level dB(A) 58 59 60 61 Operation range °CDB 15 to 49 Type R-410A Refrigerant Charge kg 6.4+6.4 6.4+6.4+6.4 Piping Liquid mm 12.7(Brazing) 15.9(Brazing) connections (Indoor unit) Gas mm 28.6(Brazing) 34.9(Brazing) Piping Inlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 3) connections (Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 3) MODEL RWHQ42THYM RWHQ44THYM RWHQ46THYM RWHQ48THYM RWHQ50THYM RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ16TYM RWHQ16TYM Combination units RWHQ14TYM RWHQ14TYM RWHQ16TYM RWHQ16TYM RWHQ16TYM RWHQ14TYM RWHQ16TYM RWHQ16TYM RWHQ16TYM RWHQ18TYM Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 409,000 427,000 444,000 461,000 478,000 Cooling capacity kW 120 125 130 135 140 Power consumption kW 32.4 34.5 36.6 38.7 41.1 Capacity control % 4-100 3-100 Casing colour Ivory white (5Y7.5/1) Type Hermetically Sealed Scroll Type Compressor (2.9x1)+(3.3x1)+(2.9x1)+ (2.9x1)+(3.3x1)+(2.9x1)+ (2.9x1)+(3.3x1)+(3.6x1)+ (3.6x1)+(3.7x1)+(3.6x1)+ (3.6x1)+(3.7x1)+(3.6x1)+ Motor output kW (3.3x1)+(2.9x1)+(3.3x1) (3.3x1)+(3.6x1)+(3.7x1) (3.7x1)+(3.6x1)+(3.7x1) (3.7x1)+(3.6x1)+(3.7x1) (3.7x1)+(4.4x1)+(4.0x1) Airflow rate m3/min 233+233+233 Dimensions (H×W×D) mm (1,657x1,240x765)+(1,657x1,240x765)+(1,657x1,240x765) Machine weight kg 285+285+285 Sound level dB(A) 65 66 Operation range ºCDB 15 to 49 Type R-410A Refrigerant Charge kg 10.3+10.3+10.3 10.3+10.3+10.4 10.3+10.4+10.4 10.4+10.4+10.4 10.4+10.4+10.5 Piping Liquid mm 19.1(Brazing) c (I o n n d n o e o c r t u io n n it s ) Gas mm 41.3( B razing) Piping Inlet pipe mm 19.1(Brazing x 3) connections (Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 3) 169 Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. FACING PAGE — PDF page 171 RWHQ26THYM RWHQ28THYM RWHQ30THYM RWHQ32THYM RWHQ34THYM RWHQ36THYM RWHQ38THYM RWHQ40THYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ12TYM RWHQ12TYM RWHQ8TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ12TYM RWHQ14TYM RWHQ12TYM RWHQ14TYM RWHQ10TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 248,000 267,000 286,000 305,000 327,000 348,000 365,000 389,000 72.8 78.3 83.9 89.4 95.9 102 107 114 17.5 19.2 21.3 23.0 24.9 26.7 28.7 30.5 6-100 5-100 4-100 Ivory white (5Y7.5/1) Hermetically Sealed Scroll Type (3.4x1)+(3.4x1)+ (3.4x1)+(3.4x1)+ (3.4x1)+(4.1x1)+ (3.4x1)+(5.2x1)+ (3.4x1)+(5.2x1)+ (3.4x1)+(2.9x1)+(3.3x1)+ (5.2x1)+(5.2x1)+ (5.2x1)+(2.9x1)+(3.3x1)+ (4.1x1) (5.2x1) (5.2x1) (5.2x1) (2.9x1)+(3.3x1) (2.9x1)+(3.3x1) (2.9x1)+(3.3x1) (2.9x1)+(3.3x1) 157+157+165 157+157+178 157+165+178 157+178+178 157+178+233 157+233+233 178+178+233 178+233+233 (1,657x930x765)+ (1,657x930x765)+ (1,657x930x765)+ (1,657x930x765)+ (1,657x930x765)+(1,657x930x765)+(1,657x930x765) (1,657x930x765)+ (1,657x1,240x765)+ (1,657x930x765)+ (1,657x1,240x765)+ (1,657x1,240x765) (1,657x1,240x765) (1,657x1,240x765) (1,657x1,240x765) 185+185+200 185+200+200 185+200+285 185+285+285 200+200+285 200+285+285 61 62 63 64 15 to 49 R-410A 6.4+6.4+6.5 6.4+6.4+6.8 6.4+6.5+6.8 6.4+6.8+6.8 6.4+6.8+10.3 6.4+10.3+10.3 6.8+6.8+10.3 6.8+10.3+10.3 19.1(Brazing) 34.9(Brazing) 41.3(Brazing) 19.1(Brazing x 3) 19.1(Brazing x 3) Standard Type MODEL RWHQ6TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ14TYM RWHQ16TYM Combination units — — — — — — Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 Cooling capacity kW 16.0 22.4 28.0 33.5 40.0 45.0 Power consumption kW 3.55 5.13 7.22 8.93 10.8 12.9 Capacity control % 20-100 16-100 15-100 11-100 10-100 Casing colour Ivory white (5Y7.5/1) Type Hermetically Sealed Scroll Type Compressor Motor output kW 2.4x1 3.4x1 4.1x1 5.2x1 (2.9x1)+(3.3x1) (3.6x1)+(3.7x1) Airflow rate m3/min 119 157 165 178 233 Dimensions (H×W×D) mm 1,657x930x765 1,657x1,240x765 Machine weight kg 185 200 285 Sound level dB(A) 55 56 57 59 60 61 Operation range ºCDB 15 to 49 Type R-410A Refrigerant Charge kg 6.4 6.5 6.8 10.3 10.4 Piping Liquid mm 9.5(Brazing) 12.7(Brazing) c (I o n n d n o e o c r t u io n n it s ) Gas mm 19.1(Brazing) 22.2(Brazing) 28.6( B razing) Piping Inlet pipe mm 19.1(Brazing) connections (Heat exchanger unit) Outlet pipe mm 19.1(Brazing) 170 •Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures. metsyS retaW toH yrevoceR taeH VI VRV VRV IV Heat Recovery Hot Water System

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗