Back to resultsSpecification results

RSUYQ7AYM is a Daikin outdoor unit in the VRV S High efficiency series, vrv s type. Its rated cooling capacity is 20 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
20 kW
Power supply
3-phase, 380-415 V/380 V, 50/60 Hz
Dimensions (H×W×D)
870×1,100×460 mm
Weight
120 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

RSUYQ7AYM specifications

RSUYQ7AYM specifications · PCVVN2507Aaprv
System configuration 5 specifications
Capacity index175
Total capacity index of connectable indoor units · Combination (%) · 50%87.5
Total capacity index of connectable indoor units · Combination (%) · 100%175
Total capacity index of connectable indoor units · Combination (%) · 130%227.5
Maximum number of connectable indoor units11
Rated capacity 6 specifications
Cooling capacity · Btu/h68,200
Cooling capacity · kW20.0
Heating capacity · Btu/h76,400
Heating capacity · kW22.4
kW20.0
HP7
Electrical & efficiency 6 specifications
Power supply3-phase, 380-415 V/380 V, 50/60 Hz
Power consumption · Cooling · kW5.46
Power consumption · Heating · kW5.10
Capacity control · %9 to 100
Compressor · TypeHermetically sealed swing type
Compressor · Motor output (Cooling / Heating) · kW1.9/2.3
Airflow & sound 3 specifications
Airflow rate · Cooling · m³/min123
Airflow rate · Heating · m³/min137
Sound level (Cooling/Heating) · dB(A)58/61
Dimensions & weight 3 specifications
Casing colourIvory white (5Y7.5/1)
Dimensions (H×W×D) · mm870×1,100×460
Machine weight · kg120
Piping & refrigerant 4 specifications
Refrigerant · TypeR-410A
Refrigerant · Charge · kg5.4
Piping connections · Liquid · mm9.5 (Flare)
Piping connections · Gas · mm19.1 (Brazing)
Operating conditions 2 specifications
Operation range · Cooling · °CDB-5 to 52
Operation range · Heating · °CWB-20 to 15.5

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 127 (printed page 126). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Note: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures. • Refrigerant charge is required. Outdoor unit combinations MODEL RSUYQ4AVM RSUYQ5AVM RSUYQ6AVM RSUYQ7AYM RSUYQ8AYM kW 11.2 14.0 16.0 20.0 22.4 HP 4 5 6 7 8 Capacity index 100 125 150 175 200 50% 50 62.5 75 87.5 100 Total capacity index of Combination (%) 100% 100 125 150 175 200 connectable indoor units 130% 130 162.5 195 227.5 260 Maximum number of connectable indoor units 6 8 9 11 13 Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit. 126 seireS ycneicfifE hgiH S VRV VRV S High Efficiency Series
View catalogue page · PDF 127

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 127
Read all text from this page and its facing page
PDF page 127 Specifications Heat Pump MODEL RSUYQ4AVM RSUYQ5AVM RSUYQ6AVM RSUYQ7AYM RSUYQ8AYM Power supply 1-phase, 220-240/220-230 V, 50/60 Hz 3-phase, 380-415 V/380 V, 50/60 Hz Btu/h 38,200 47,800 54,600 68,200 76,400 Cooling capacity kW 11.2 14.0 16.0 20.0 22.4 Btu/h 42,700 54,600 61,400 76,400 85,300 Heating capacity kW 12.5 16.0 18.0 22.4 25.0 Power Cooling kW 2.49 3.44 4.10 5.46 6.61 consumption Heating kW 2.54 3.37 3.98 5.10 5.92 Capacity control % 23 to 100 15 to 100 9 to 100 Casing colour Ivory white (5Y7.5/1) Type Hermetically sealed swing type Compressor Motor output (Cooling / kW 2.0/2.4 3.1/3.6 3.5/4.0 1.9/2.3 3.2/3.2 Heating) Cooling m³/min 87 84 87 123 Airflow rate Heating m³/min 90 84 94 137 145 Dimensions (H×W×D) mm 870×1,100×460 Machine weight kg 95 98 120 Sound level (Cooling/Heating) dB(A) 51/52 52/54 58/61 59/63 Operation Cooling °CDB -5 to 52 range Heating °CWB -20 to 15.5 Type R-410A Refrigerant Charge kg 4.0 4.2 5.4 Piping Liquid mm 9.5 (Flare) connections Gas mm 15.9 (Flare) 19.1 (Brazing) Note: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures. • Refrigerant charge is required. Outdoor unit combinations MODEL RSUYQ4AVM RSUYQ5AVM RSUYQ6AVM RSUYQ7AYM RSUYQ8AYM kW 11.2 14.0 16.0 20.0 22.4 HP 4 5 6 7 8 Capacity index 100 125 150 175 200 50% 50 62.5 75 87.5 100 Total capacity index of Combination (%) 100% 100 125 150 175 200 connectable indoor units 130% 130 162.5 195 227.5 260 Maximum number of connectable indoor units 6 8 9 11 13 Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit. 126 seireS ycneicfifE hgiH S VRV VRV S High Efficiency Series FACING PAGE — PDF page 126 Outdoor Units VRV S High Efficiency Series Specifications Cooling Only MODEL RSUQ4AVM RSUQ5AVM RSUQ6AVM RSUQ7AYM RSUQ8AYM RSUQ9AYM Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380-415 V/380 V, 50/60 Hz Btu/h 38,200 47,800 54,600 68,200 76,400 81,900 Cooling capacity kW 11.2 14.0 16.0 20.0 22.4 24.0 Power consumption kW 2.49 3.44 4.10 5.46 6.61 7.21 Capacity control % 23 to 100 16 to 100 9 to 100 Casing colour Ivory white (5Y7.5/1) Type Hermetically sealed swing type Compressor Motor output kW 2.0 3.1 3.5 1.9 3.2 3.8 Airflow rate m3/min 87 84 87 123 137 Dimensions (H×W×D) mm 870×1,100×460 Machine weight kg 95 98 115 Sound level dB(A) 51 52 58 59 60 Operation range °CDB -5 to 52 Type R-410A Refrigerant Charge kg 4.0 4.2 5.4 Liquid mm 9.5 (Flare) Piping connections Gas mm 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing) Note: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures. • Refrigerant charge is required. Outdoor unit combinations MODEL RSUQ4AVM RSUQ5AVM RSUQ6AVM RSUQ7AYM RSUQ8AYM RSUQ9AYM kW 11.2 14.0 16.0 20.0 22.4 24.0 HP 4 5 6 7 8 9 Capacity index 100 125 150 175 200 215 50% 50 62.5 75 87.5 100 107.5 Total capacity index of Combination (%) 100% 100 125 150 175 200 215 connectable indoor units 130% 130 162.5 195 227.5 260 280 Maximum number of connectable indoor units 6 8 9 11 13 14 Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit. 125

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗