Back to resultsSpecification results
Daikin VRV R — representative product image
Representative image · Vietnamese catalogue, PDF 38 ↗
Outdoor unitVRV R →

REYQ38BYM9

Daikin · Heat recovery

REYQ38BYM9 is a Daikin outdoor unit in the VRV R series, heat recovery type. Its rated cooling capacity is 106 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
106 kW
Power supply
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Dimensions (H×W×D)
(1,660×1,240×765) + (1,660×1,240×765) mm
Weight
357+357 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

REYQ38BYM9 specifications

REYQ38BYM9 specifications · PCVVN2507Aaprv
System configuration 1 specifications
Combination unitsREYQ18BYM9 / REYQ20BYM9 / —
Rated capacity 4 specifications
Cooling capacity · Btu/h362,000
Cooling capacity · kW106
Heating capacity · Btu/h406,000
Heating capacity · kW119
Electrical & efficiency 7 specifications
Power supply3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Power consumption · Cooling · kW31.9
Power consumption · Heating · kW31.7
Capacity control · %2-100
EER (TCVN13256: 2021)4.66
Compressor · TypeHermetically sealed scroll type
Compressor · Motor output · kW(4.04+6.56)+ (4.51+7.37)
Airflow & sound 3 specifications
Airflow rate · m3/min258+306
Sound level · dB(A)66
Sound power · dB90
Dimensions & weight 3 specifications
Casing colourIvory white (5Y7.5/1)
Dimensions (H×W×D) · mm(1,660×1,240×765) + (1,660×1,240×765)
Machine weight · kg357+357
Piping & refrigerant 5 specifications
Refrigerant · TypeR-410A
Refrigerant · Charge · kg11.7+11.7
Piping connections · Liquid · mm19.1 (Brazing)
Piping connections · Gas · mm41.3 (Brazing)
Piping connections · High and low pressure gas · mm34.9 (Brazing)
Operating conditions 2 specifications
Operation range · Cooling · ºCDB-5 to 49
Operation range · Heating · ºCWB-25 to 15.5

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 38 (printed page 37). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. 37
View catalogue page · PDF 38

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 38
Read all text from this page and its facing page
PDF page 38 Outdoor Units VRV R Series Specifications Model REYQ8BYM9 REYQ10BYM9 REYQ12BYM9 REYQ14BYM9 REYQ16BYM9 REYQ18BYM9 REYQ20BYM9 — — — — — — — Combination units — — — — — — — Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 76,400 95,500 114,000 136,000 154,000 171,000 191,000 Cooling capacity kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 Btu/h 85,300 107,000 128,000 154,000 171,000 191,000 215,000 Heating capacity kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0 Power Cooling kW 5.17 6.80 8.71 11.2 12.9 14.4 17.5 consumption Heating kW 5.68 7.29 9.81 12.8 13.6 14.5 17.2 Capacity control % 11-100 7-100 6-100 5-100 4-100 EER (TCVN13256: 2021) 5.17 4.74 4.51 4.64 4.66 4.75 4.57 Casing colour Ivory white (5Y7.5/1) Type Hermetically sealed scroll type Compressor Motor output kW 4.13 5.87 7.67 8.45 4.44+5.03 4.04+6.56 4.51+7.37 Airflow rate m3/min 155 169 181 260 266 258 306 Dimensions (H×W×D) mm 1,660×930×765 1,660×1,240×765 Machine weight kg 227 231 232 281 323 357 Sound level dB(A) 56 57 59 63 62 61 65 Sound power dB 80 83 85 89 Operation Cooling ºCDB -5 to 49 range Heating ºCWB -25 to 15.5 Type R-410A Refrigerant Charge kg 10.6 10.9 11.7 Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) Piping Gas mm 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) connections High and low pressure gas mm 15.9 (Brazing) 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) Model REYQ34BYM9 REYQ36BYM9 REYQ38BYM9 REYQ40BYM9 REYQ42BYM9 REYQ44BYM9 REYQ14BYM9 REYQ16BYM9 REYQ18BYM9 REYQ20BYM9 REYQ18BYM9 REYQ20BYM9 Combination units REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ24BYM9 REYQ24BYM9 — — — — — — Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Btu/h 328,000 345,000 362,000 382,000 399,000 420,000 Cooling capacity kW 96.0 101 106 112 117 123 Btu/h 369,000 386,000 406,000 430,000 447,000 471,000 Heating capacity kW 108 113 119 126 131 138 Power Cooling kW 28.7 30.4 31.9 35.0 35.7 38.8 consumption Heating kW 30.0 30.8 31.7 34.4 36.7 39.4 Capacity control % 2-100 EER (TCVN13256: 2021) 4.59 4.61 4.66 4.57 4.47 4.40 Casing colour Ivory white (5Y7.5/1) Type Hermetically sealed scroll type Compressor 8.45+ (4.44+5.03)+ (4.04+6.56)+ (4.51+7.37)+ (4.04+6.56)+ (4.51+7.37)+ Motor output kW (4.51+7.37) (4.51+7.37) (4.51+7.37) (4.51+7.37) (7.80+8.11) (7.80+8.11) Airflow rate m3/min 260+306 266+306 258+306 306+306 258+430 306+430 (1,660×1,240×765) + Dimensions (H×W×D) mm (1,660×1,240×765) + (1,660×1,240×765) (1,660×1,750×765) Machine weight kg 281+357 323+357 357+357 357+409 Sound level dB(A) 67 66 68 69 70 Sound power dB 90 90 92 91 93 Operation Cooling ºCDB -5 to 49 range Heating ºCWB -25 to 15.5 Type R-410A Refrigerant Charge kg 11.7+11.7 Liquid mm 19.1 (Brazing) Piping connections Gas mm 34.9 (Brazing) 41.3 (Brazing) High and low pressure gas mm 28.6 (Brazing) 34.9 (Brazing) Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. 37 FACING PAGE — PDF page 39 VRV R Series Heat Recovery 38 seireS R VRV *EER (TCVN13256: 2021) According to TCVN13256: 2021 issued by the Ministry of Science and Technology of Vietnam, EER (Energy Efficiency Ratio) is the index to describe the energy saving levels of VRV system. EER (TCVN13256: 2021) is calculated according to the following formula: φ100% φ75% φ50% φ25% EER (TCVN13256: 2021) = 0.01 × + 0.42 × + 0.45 × + 0.12 × P P P P 100% 75% 50% 25% φn%: Cooling capacity at n% heat load (kW) Pn%: Input power at n% heat load (kW) REYQ22BYM9 REYQ24BYM9 REYQ26BYM9 REYQ28BYM9 REYQ30BYM9 REYQ32BYM9 — — REYQ12BYM9 REYQ12BYM9 REYQ12BYM9 REYQ12BYM9 — — REYQ14BYM9 REYQ16BYM9 REYQ18BYM9 REYQ20BYM9 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 210,000 229,000 251,000 268,000 285,000 305,000 61.5 67.0 73.5 78.5 83.5 89.5 235,000 256,000 282,000 299,000 319,000 345,000 69.0 75.0 82.5 87.5 93.5 101 18.6 21.3 19.9 21.6 23.1 26.2 19.6 22.2 22.6 23.4 24.3 27.3 3-100 2-100 4.37 4.27 4.57 4.59 4.65 4.54 Ivory white (5Y7.5/1) Hermetically sealed scroll type 7.06+7.37 7.80+8.11 7.67+8.45 7.67+(4.44+5.03) 7.67+(4.04+6.56) 7.67+(4.51+7.37) 430 181+260 181+266 181+258 181+306 1,660×1,750×765 (1,660×930×765) + (1,660×1,240×765) 409 232+281 232+323 232+357 232+357 67 68 64 63 66 90 86 87 90 -5 to 49 -25 to 15.5 R-410A 11.7 10.9+11.7 15.9 (Brazing) 19.1 (Brazing) 28.6 (Brazing) 34.9 (Brazing) 28.6 (Brazing) REYQ46BYM9 REYQ48BYM9 REYQ50BYM9 REYQ52BYM9 REYQ54BYM9 REYQ56BYM9 REYQ58BYM9 REYQ60BYM9 REYQ22BYM9 REYQ24BYM9 REYQ12BYM9 REYQ12BYM9 REYQ14BYM9 REYQ16BYM9 REYQ18BYM9 REYQ20BYM9 REYQ24BYM9 REYQ24BYM9 REYQ18BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 — — REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 REYQ20BYM9 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 440,000 457,000 478,000 498,000 519,000 536,000 553,000 573,000 129 134 140 146 152 157 162 168 491,000 512,000 536,000 560,000 583,000 601,000 621,000 645,000 144 150 157 164 171 176 182 189 40.2 42.6 40.9 44.0 46.2 47.9 49.4 52.5 41.8 44.4 41.8 44.5 47.2 48.0 48.9 51.6 2-100 4.32 4.27 4.61 4.55 4.59 4.60 4.62 4.57 Ivory white (5Y7.5/1) Hermetically sealed scroll type (4.44+5.03)+ (4.04+6.56)+ (4.51+7.37)+ (7.06+7.37)+ (7.80+8.11)+ 7.67+(4.04+6.56)+ 7.67+(4.51+7.37)+ 8.45+(4.51+7.37)+ (4.51+7.37)+ (4.51+7.37)+ (4.51+7.37)+ (7.80+8.11) (7.80+8.11) (4.51+7.37) (4.51+7.37) (4.51+7.37) (4.51+7.37) (4.51+7.37) (4.51+7.37) 430+430 181+258+306 181+306+306 260+306+306 266+306+306 258+306+306 306+306+306 (1,660×1,750×765) + (1,660×930×765) + (1,660×1,240×765) + (1,660×1,240×765) + (1,660×1,240×765) + (1,660×1,240×765) (1,660×1,750×765) (1,660×1,240×765) 409+409 232+357+357 281+357+357 323+357+357 357+357+357 71 67 69 70 93 91 93 94 -5 to 49 -25 to 15.5 R-410A 11.7+11.7 10.9+11.7+11.7 11.7+11.7+11.7 19.1 (Brazing) 41.3 (Brazing) 34.9 (Brazing) • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.