FXZA50AV2S is a Daikin indoor unit in the FXZA-A · VRV 7S series, compact multi flow cassette · r-32 type. Its rated cooling capacity is 5.6 kW according to catalogue VRV7S 01-04/26.
- Rated cooling capacity
- 5.6 kW
- Power supply
- 1-phase, 220–240 V/220–230 V, 50/60 Hz
- Dimensions (H×W×D)
- 260×575×575 (add 63 mm to depth for the electrical box) mm
- Weight
- 19.0 kg
Product overview FXZA50AV2S
FXZA50AV2S is a Daikin indoor unit in the FXZA-A · VRV 7S series (Compact multi flow cassette · R-32).
Application and design
The cassette sits in the ceiling with its discharge panel facing the occupied area. Check body dimensions, the panel type and condensate drainage when choosing a location.
Catalogue performance
- Rated cooling capacity
- 5.6 kW
- Airflow rate (H/HM/M/ML/L) · m³/min
- 14.5/13.6/12.5/11.4/10.0
- Sound level (H/HM/M/ML/L) · dB(A)
- 43.0/42.5/40.0/36.5/33.0
Configuration and installation
- Power supply
- 1-phase, 220–240 V/220–230 V, 50/60 Hz
- Dimensions (H×W×D) · mm
- 260×575×575 (add 63 mm to depth for the electrical box)
- Machine weight · kg
- 19.0
- Piping connections · Drain · mm
- VP20 (External Dia. 26/Internal Dia. 20)
Checking a specification or quotation
Check the unit dimensions against the proposed location and allow service access. Check panels, controls and drainage accessories where the source table lists them.
Check catalogue rating conditions and connection arrangements when selecting equipment.
FXZA50AV2S specifications
| Rated capacity 2 specifications | |
|---|---|
| Cooling capacity · Btu/h | 19,100 |
| Cooling capacity · kW | 5.6 |
| Electrical & efficiency 2 specifications | |
| Power supply | 1-phase, 220–240 V/220–230 V, 50/60 Hz |
| Power consumption (Cooling) · kW | 0.092 |
| Airflow & sound 2 specifications | |
| Airflow rate (H/HM/M/ML/L) · m³/min | 14.5/13.6/12.5/11.4/10.0 |
| Sound level (H/HM/M/ML/L) · dB(A) | 43.0/42.5/40.0/36.5/33.0 |
| Dimensions & weight 3 specifications | |
| Casing | Galvanised steel plate |
| Dimensions (H×W×D) · mm | 260×575×575 (add 63 mm to depth for the electrical box) |
| Machine weight · kg | 19.0 |
| Piping & refrigerant 3 specifications | |
| Piping connections · Liquid (Flare) · mm | 6.4 |
| Piping connections · Gas (Flare) · mm | 12.7 |
| Piping connections · Drain · mm | VP20 (External Dia. 26/Internal Dia. 20) |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from VRV7S 01-04/26, PDF page 27 (printed page 26). English edition · Siam Daikin Sales · specifications as of November 2025.