Back to resultsSpecification results
Daikin FXVQ-N — representative product image
Representative image · Vietnamese catalogue, PDF 220 ↗
Indoor unitFXVQ-N →

FXVQ125NY1

Daikin · Ducted floor standing

FXVQ125NY1 is a Daikin indoor unit in the FXVQ-N series, ducted floor standing type. Its rated cooling capacity is 14 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
14 kW
Power supply
3-phase 4-wire system, 380–415 V, 50 Hz
Dimensions (H×W×D)
1,670×750×510 mm
Weight
118 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FXVQ125NY1 specifications

FXVQ125NY1 specifications · PCVVN2507Aaprv
Rated capacity 4 specifications
Cooling capacity · Btu/h47,800
Cooling capacity · kW14.0
Heating capacity · Btu/h54,600
Heating capacity · kW16.0
Electrical & efficiency 3 specifications
Power supply3-phase 4-wire system, 380–415 V, 50 Hz
Power consumption · Cooling · kW0.53
Power consumption · Heating · kW0.53
Airflow & sound 6 specifications
Sound level *1 · dB(A)52
Fan · Motor output · kW0.75
Fan · Airflow rate · m3/min43
Fan · Airflow rate · cfm1,518
Fan · External static pressure *2 · Pa152
Fan · Drive systemBelt drive system
Dimensions & weight 3 specifications
Casing colourIvory white (5Y7.5/1)
Dimensions (H × W × D) · mm1,670×750×510
Machine weight · kg118
Piping & refrigerant 3 specifications
Piping connections · Liquid · mm9.5 (Brazing)
Piping connections · Gas · mm15.9 (Brazing)
Piping connections · Drain · mmRp1 (PS 1B internal thread)
Filters 1 specifications
Air filter · TypeLong-life filter (anti-mould resin net)

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 221 (printed page 220). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) *1: Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value). It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow. *2: The value is the external static pressure with standard pulley. 220 stinU roodnI
View catalogue page · PDF 221

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 221
Read all text from this page and its facing page
PDF page 221 VRV Indoor Units Specifications MODEL FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 FXVQ400NY1 FXVQ500NY1 FXVQ500NY16 Power supply 3-phase 4-wire system, 380–415 V, 50 Hz Btu/h 47,800 76,400 95,500 154,000 191,000 Cooling capacity kW 14.0 22.4 28.0 45.0 56.0 Btu/h 54,600 85,300 107,500 171,000 215,000 Heating capacity kW 16.0 25.0 31.5 50.0 63.0 Cooling 0.53 1.33 1.61 3.97 2.62 4.70 Power consumption kW Heating 0.53 1.33 1.61 3.97 2.62 4.70 Casing colour Ivory white (5Y7.5/1) Dimensions (H × W × D) mm 1,670×750×510 1,670×950×510 1,670×1,170×5101,900×1,170×720 1,900×1,470×720 Machine weight kg 118 144 169 236 281 306 Sound level *1 dB(A) 52 56 60 65 62 66 Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) Piping connections Gas mm 15.9 (Brazing) 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) Drain mm Rp1 (PS 1B internal thread) Air filter Type Long-life filter (anti-mould resin net) Motor output kW 0.75 1.5 3.7 5.5 m3/min 43 69 86 134 165 172 Airflow rate Fan cfm 1,518 2,436 3,036 4,730 5,825 6,072 External static pressure *2 Pa 152 217 281 420 142 390 Drive system Belt drive system Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) *1: Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value). It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow. *2: The value is the external static pressure with standard pulley. 220 stinU roodnI FACING PAGE — PDF page 220 All-fresh (using outdoor air only) system Return + Outdoor air mixed system Outside Air Air conditioning conditioning Outdoor air introduction 219 Circulated air Floor Standing Duct Type FXVQ-N Large airflow type for large spaces • Full-scale duct connection airflow allows for air conditioning evenly in spacious areas. Duct connection airflow type Direct airflow type • Adding the plenum chamber (option) allows for simple operation with direct airflow. *Note that the operation sound increases by approximately 5dB(A). • The belt drive system allows for use of air discharge outlets in various shapes as well as long ducts. • A long-life filter (maintenance free up to one year*) is equipped as a standard accessory. *8 hr/day, 26 day/month. For dust concentration of 0.15 mg/m3 • A wide range of optional accessories are available such as high-efficiency filters. • Outdoor air intake mode is useable as an outdoor-air processing air conditioner. *When using the unit as an outdoor-air processing unit, there are some restrictions. Strictly follow the restrictions specified in the Engineering Data Book. Outside Outdoor air introduction * Air introduced from the outside and circulated air must be mixed in the air conditioner primary side before introduction into the air conditioner.

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗