FXSA100AVMS

Daikin · Middle static pressure duct · R-32

FXSA100AVMS is a Daikin indoor unit in the FXSA-A · VRV 7S series, middle static pressure duct · r-32 type. Its rated cooling capacity is 11.2 kW according to catalogue VRV7S 01-04/26.

Rated cooling capacity
11.2 kW
Power supply
1 phase, 220 V, 50 Hz
Dimensions (H×W×D)
245×1,400×800 mm
Weight
46 kg
Data based on the source catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

Product overview FXSA100AVMS

FXSA100AVMS is a Daikin indoor unit in the FXSA-A · VRV 7S series (Middle static pressure duct · R-32).

Application and design

When planning the equipment layout, check the series connection arrangement, operating conditions and unit dimensions. The details below identify this model’s configuration in the catalogue.

Catalogue performance

Rated cooling capacity
11.2 kW
Airflow rate (H/HM/M/ML/L) · m³/min
32/29.5/27/24.7/22.5
External static pressure *2 · Pa
50–150 (50)
Sound level (H/HM/M/ML/L) · dB(A)
39/37/35/33.5/32

Configuration and installation

Power supply
1 phase, 220 V, 50 Hz
Dimensions (H×W×D) · mm
245×1,400×800
Machine weight · kg
46
Piping connections · Drain · mm
VP25 (External Dia. 34/Internal Dia. 25)

Checking a specification or quotation

Check the unit dimensions against the proposed location and allow service access. Check panels, controls and drainage accessories where the source table lists them.

Check catalogue rating conditions and connection arrangements when selecting equipment.

FXSA100AVMS specifications

FXSA100AVMS specifications · VRV7S 01-04/26
Rated capacity 2 specifications
Cooling capacity · Btu/h38,200
Cooling capacity · kW11.2
Electrical & efficiency 2 specifications
Power supply1 phase, 220 V, 50 Hz
Power consumption *1 · kW0.151
Airflow & sound 4 specifications
Airflow rate (H/HM/M/ML/L) · m³/min32/29.5/27/24.7/22.5
Airflow rate (H/HM/M/ML/L) · cfm1,130/1,041/953/872/794
Sound level (H/HM/M/ML/L) · dB(A)39/37/35/33.5/32
External static pressure *2 · Pa50–150 (50)
Dimensions & weight 3 specifications
CasingGalvanised steel plate
Dimensions (H×W×D) · mm245×1,400×800
Machine weight · kg46
Piping & refrigerant 3 specifications
Piping connections · Liquid (Flare) · mm9.5
Piping connections · Gas (Flare) · mm15.9
Piping connections · Drain · mmVP25 (External Dia. 34/Internal Dia. 25)

Catalogue source & rating conditions

Values are taken from VRV7S 01-04/26, PDF page 26 (printed page 25). English edition · Siam Daikin Sales · specifications as of November 2025.

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read catalogue notes (summary)
Notes: Cooling ratings use indoor 27°C DB / 19°C WB and outdoor 35°C DB, with 7.5 m equivalent piping and 0 m height difference. Indoor capacity depends on the system capacity index. Sound levels are measured under anechoic conditions; installed values may be higher. See PDF pages 28–30 for the R-32 safety measures. *1 Input power is based on rated external static pressure. *2 The remote controller allows 13 settings for the 20–40 classes, 11 for 50–125 and 10 for 140.