TECHNICAL SPECIFICATION SHEET · DAIKIN
FXMQ200MFV1
Indoor unit · FXMQ-MFV1 · Outdoor air processing unit
Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.
| System configuration | |
|---|---|
| Connectable outdoor units *4 | 8 HP and above |
| Rated capacity | |
| Cooling capacity *1 · Btu/h | 76,400 |
| Cooling capacity *1 · kW | 22.4 |
| Heating capacity *1 · Btu/h | 47,400 |
| Heating capacity *1 · kW | 13.9 |
| Electrical & efficiency | |
| Power supply | 1-phase 220-240 V, 50 Hz |
| Power consumption · kW | 0.548 |
| Airflow & sound | |
| Fan · Motor output · kW | 0.380 |
| Fan · Airflow rate · m3/min | 28 |
| Fan · Airflow rate · cfm | 988 |
| Fan · External static pressure · 220 V/240 V · Pa | 225/275 |
| Sound level *3 · 220 V/240 V · dB(A) | 47/48 |
| Operation range (Fan mode operation between 15 and 19°C) · Cooling | 19 to 43°C |
| Operation range (Fan mode operation between 15 and 19°C) · Heating | -5 to 15°C |
| Dimensions & weight | |
| Casing | Galvanised steel plate |
| Dimensions (H × W × D) · mm | 470 × 1,380 × 1,100 |
| Machine weight · kg | 123 |
| Piping & refrigerant | |
| Refrigerant piping · Liquid · mm | 9.5 (Flare) |
| Refrigerant piping · Gas · mm | 19.1 (Brazing) |
| Refrigerant piping · Drain · mm | PS1B female thread |
| Operating conditions | |
| Range of the discharge temperature *5 · Cooling | 13 to 25°C |
| Range of the discharge temperature *5 · Heating | 18 to 30°C |
| Filters | |
| Air filter | *2 |
| Filters · Long-life replacement filter | KAF371N280 |
| Filters · High-efficiency filter · Colourimetric method 65% | KAF372M280 |
| Filters · High-efficiency filter · Colourimetric method 90% | KAF373M280 |
| Filters · Filter chamber * | KDJ3705L280 |
| Filters · Streamer duct chamber | BDEZ500A510VE |
| Controls & accessories | |
| lortnoc/noitarepO · Operation remote controller | BRC1H63W(K) / BRC1E63 / BRC2E61 |
| lortnoc/noitarepO · Simple touch controller | DTP401A61 |
| lortnoc/noitarepO · AC adaptor for simple touch controller | DTP401A62 |
| lortnoc/noitarepO · Central remote controller | DCS302CA61 |
| lortnoc/noitarepO · Unified ON/OFF controller | DCS301BA61 |
| lortnoc/noitarepO · Schedule timer | DST301BA61 |
| lortnoc/noitarepO · Wiring adaptor for electrical appendices (2) | KRP4AA51 |
| Drain pump kit | KDU30L250VE |
| Adaptor for wiring | KRP1B61 |
Source reference
PCVVN2507Aaprv · PDF page 233 · Printed page 232
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)
Open catalogue PDF · page 233
Model page: https://vrv.vn/spec/fxmq200mfv1/
Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.
Original source notes
Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.
Notes: *1. Specifications are based on the following conditions: • Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB. • Heating: Outdoor temp. 0°CDB, -2.9°CWB (50% RH), and discharge temp. of 25°CDB. • Equivalent reference piping length: 7.5 m (0 m horizontal) *2. An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter. *3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. These values are normally somewhat higher during actual operation as a result of ambient conditions. *4. It is possible to connect to the outdoor unit if the total capacity of the indoor units is 50% to 100% of the capacity index of the outdoor unit. *5. Local setting mode is not displayed on the remote controller. • This equipment cannot be incorporated into the remote group control of the VRV system. Options 232 sretliF MODEL FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 Operation remote controller BRC1H63W(K) / BRC1E63 / BRC2E61 DTP401A61 DTP401A62 DCS302CA61 DCS301BA61 DST301BA61 KRP4AA51 lortnoc/noitarepO This unit is intended for the treatment of outdoor air only. Not to be used for maintaining indoor air temperature. Be sure that the discharge airflow will not blow on people directly. Group control of the product and standard indoor units is not supported. A separate remote controller should be connected to individual unit. If the unit is utilised to operate 24 hours a day, maintenance (part replacement, etc.) must be performed periodically. Temperature setting and Power Proportional Distribution (PPD) are not possible even if the intelligent Touch Controller or the intelligent Touch Manager is installed. The remote controller wired to the outdoor-air processing unit must not be set as the master remote controller. Otherwise, when set to “Auto,” the operation mode will switch according to the outdoor air conditions, regardless of the indoor temperature. Central remote controller Unified ON/OFF controller Schedule timer Wiring adaptor for electrical appendices (2) Long-life replacement filter KAF371N140 KAF371N280 Colourimetric method 65% KAF372M140 KAF372M280 High-efficiency filter Colourimetric method 90% KAF373M140 KAF373M280 Filter chamber * KDJ3705L140 KDJ3705L280 Streamer duct chamber BDEZ500A140VE BDEZ500A510VE Drain pump kit KDU30L250VE Adaptor for wiring KRP1B61 Notes: * Filter chamber has a suction-type flange. (Main unit does not.) • Dimensions and weight of the equipment may vary depending on the options used. • Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering. • Some options may not be used in combination. • Operating sound may increase somewhat depending on the options used. tnempiuqE tnemtaerT riA Air Treatment Equipment Simple touch controller AC adaptor for simple touch controller
Notes: 2 1 . . T T p h h ip e e i n s o y g p s e t le e r n a m g t i t w o h n i : l l 7 r a n .5 n o g t m e o , p s H h e e o r i a w g t h e n t i i n d n i f f t a f h e n e r e m g n r o a c d e p : e h 0 w i s m h u . e n n d t e h r e t h o e u t f d o o ll o o r w a in ir g t e co m n p d e i r t a io t n u s r . e E i q s u 5 i ° v C a l o e r n t below. –5 15 19 (33.5) 43 231