Back to resultsSpecification results
Daikin FXMA-A · VRV 7S — representative product image
Representative image · English catalogue, PDF 26 ↗

FXMA125AV2S

Daikin · Middle-high static pressure duct · R-32

FXMA125AV2S is a Daikin indoor unit in the FXMA-A · VRV 7S series, middle-high static pressure duct · r-32 type. Its rated cooling capacity is 14 kW according to catalogue VRV7S 01-04/26.

Rated cooling capacity
14 kW
Power supply
1-phase, 220–240 V/220–230 V, 50/60 Hz
Dimensions (H×W×D)
300×1,400×700 mm
Weight
45 kg
Data based on the source catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

Product overview FXMA125AV2S

FXMA125AV2S is a Daikin indoor unit in the FXMA-A · VRV 7S series (Middle-high static pressure duct · R-32).

Application and design

When planning the equipment layout, check the series connection arrangement, operating conditions and unit dimensions. The details below identify this model’s configuration in the catalogue.

Catalogue performance

Rated cooling capacity
14 kW
Airflow rate (H/HM/M/ML/L) · m³/min
39.0/36.0/33.0/30.5/28.0
External static pressure *2 · Pa
50–200 (100)
Sound level (H/HM/M/ML/L) · dB(A)
44.0/43.0/42.0/41.0/40.0

Configuration and installation

Power supply
1-phase, 220–240 V/220–230 V, 50/60 Hz
Dimensions (H×W×D) · mm
300×1,400×700
Machine weight · kg
45
Piping connections · Drain · mm
VP20 (External Dia. 32/Internal Dia. 25)

Checking a specification or quotation

Check the unit dimensions against the proposed location and allow service access. Check panels, controls and drainage accessories where the source table lists them.

Check catalogue rating conditions and connection arrangements when selecting equipment.

FXMA125AV2S specifications

FXMA125AV2S specifications · VRV7S 01-04/26
Rated capacity 2 specifications
Cooling capacity · Btu/h47,800
Cooling capacity · kW14.0
Electrical & efficiency 2 specifications
Power supply1-phase, 220–240 V/220–230 V, 50/60 Hz
Power consumption (Cooling/Heating) · kW0.350/0.387
Airflow & sound 3 specifications
Airflow rate (H/HM/M/ML/L) · m³/min39.0/36.0/33.0/30.5/28.0
Sound level (H/HM/M/ML/L) · dB(A)44.0/43.0/42.0/41.0/40.0
External static pressure *2 · Pa50–200 (100)
Dimensions & weight 3 specifications
CasingGalvanised steel plate
Dimensions (H×W×D) · mm300×1,400×700
Machine weight · kg45
Piping & refrigerant 3 specifications
Piping connections · Liquid (Flare) · mm9.5
Piping connections · Gas (Flare) · mm15.9
Piping connections · Drain · mmVP20 (External Dia. 32/Internal Dia. 25)

Catalogue source & rating conditions

Values are taken from VRV7S 01-04/26, PDF page 26 (printed page 25). English edition · Siam Daikin Sales · specifications as of November 2025.

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read catalogue notes (summary)
Notes: Cooling ratings use indoor 27°C DB / 19°C WB and outdoor 35°C DB, with 7.5 m equivalent piping and 0 m height difference. Indoor capacity depends on the system capacity index. Sound levels are measured under anechoic conditions; installed values may be higher. See PDF pages 28–30 for the R-32 safety measures. The heating test uses indoor 20°C DB and outdoor 7°C DB / 6°C WB with the same piping and height conditions. *2 The rated static pressure is 100 Pa. The catalogue states 14 remote settings for the 50–125 classes and 10 for 140. The drain designation and diameters are shown as printed.
View catalogue page · PDF 26

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original catalogue, PDF page 26

Open original English PDF ↗

Daikin VRV System Design & Installation

SAVA M&E Joint Stock Company specializes in the design and installation of Daikin VRV central air conditioning systems for factories, buildings, and luxury villas. For inquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/