FXHQ63MAVE is a Daikin indoor unit in the FXHQ-MA / B series, ceiling suspended type. Its rated cooling capacity is 7.1 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 7.1 kW
- Power supply
- 1-phase, 220-240 V/220 V, 50/60 Hz
- Dimensions (H×W×D)
- 195×1,160×680 mm
- Weight
- 28 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FXHQ63MAVE specifications
| Rated capacity 4 specifications | |
|---|---|
| Cooling capacity · Btu/h | 24,200 |
| Cooling capacity · kW | 7.1 |
| Heating capacity · Btu/h | 27,300 |
| Heating capacity · kW | 8.0 |
| Electrical & efficiency 3 specifications | |
| Power supply | 1-phase, 220-240 V/220 V, 50/60 Hz |
| Power consumption · Cooling · kW | 0.115 |
| Power consumption · Heating · kW | 0.115 |
| Airflow & sound 3 specifications | |
| Airflow rate (H/M/L) · m3/min | 17.5/-/14 |
| Airflow rate (H/M/L) · cfm | 618/-/494 |
| Sound level (H/M/L) · dB(A) | 39/-/34 |
| Dimensions & weight 3 specifications | |
| Casing | White (10Y9/0.5) |
| Dimensions (H × W × D) · mm | 195×1,160×680 |
| Machine weight · kg | 28 |
| Piping & refrigerant 3 specifications | |
| Piping connections · Liquid (Flare) · mm | 9.5 |
| Piping connections · Gas (Flange) · mm | 15.9 |
| Piping connections · Drain · mm | VP20 (External Dia. 26/Internal Dia. 20) |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 215 (printed page 214). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
214
stinU
roodnI
View catalogue page · PDF 215
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 215
VRV Indoor Units
Specifications
MODEL FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE FXHQ125BVM FXHQ140BVM
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 12,300 24,200 38,200 48,000 52,900
Cooling capacity
kW 3.6 7.1 11.2 14.1 15.5
Btu/h 13,600 27,300 42,700 54,600 58,000
Heating capacity
kW 4.0 8.0 12.5 16.0 17.0
Power Cooling 0.111 0.115 0.135 0.168 0.181
kW
consumption Heating 0.111 0.115 0.135 0.168 0.181
Casing White (10Y9/0.5) Sheet Metal / White
m3/min 12/-/10 17.5/-/14 25/-/19.5 34/26/20 36/27/20
Airflow rate (H/M/L)
cfm 424/-/353 618/-/494 883/-/688 1,200/918/706 1,271/953/706
Sound level (H/M/L) dB(A) 36/-/31 39/-/34 45/-/37 46/41/37 48/42/37
Dimensions (H × W × D) mm 195×960×680 195×1,160×680 195×1,400×680 235×1,590×690
Machine weight kg 24 28 33 41
Liquid (Flare) 6.4 9.5
Piping
Gas (Flange) mm 12.7 15.9
connections
Drain VP20 (External Dia. 26/Internal Dia. 20)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
214
stinU
roodnI
FACING PAGE — PDF page 214
Ceiling Suspended Type
FXHQ-MA / B
FXHQ32 / 63 / 100MA FXHQ125 / 140B
Slim body with quiet
and wide airflow
Comfort
• Auto swing (up and down) and louvers (left and right by hand)
bring comfort to the room.
• Louver manually adjusts for straight or wide angle airflow.
Installation flexibility
30 mm 30 mm
• Flexible installation or more or more
The unit fits more snugly into tight spaces.
*Water used in the test-run can be drained from the air discharge
opening rather than from the side as was formerly the case.
• Drain pump kit (option) can be easily incorporated.
Drain pipe connection can be done inside the unit.
Refrigerant and drain pipe outlets are at the same opening. 600 mm
• All wiring and internal servicing can be done from under the unit.
Drain pump kit
(built inside the unit)
New 125 / 140 models provide greater capacity for large spaces
• The technology of the DC fan motor, wide sirocco fan, and large heat exchanger combine
for greater airflow and quiet operation.
• Sophisticated design: Flap neatly closes when not in use.
• Suitable for high ceilings: maximum 4.3 m
• Control of the airflow rate can be selected from 3-step control.
• Drain pump kit (option) includes a silver ion antibacterial agent that assists in preventing the growth
of slime, bacteria, and mould that cause smells and clogging.
• The rear side removable frame allows ease of access for piping work.
Easier piping work
Cleanliness
Streamer filter clean unit (Option) for new 125 / 140 models See page 7 - 8
Irradiates Streamer when the fan and air conditioning operation are stopped.
Streamer fumigates the cabin and sterilizes the filter.
Remarks:
1) Only the stylish remote controller BRC1H63W(K) can be connected for ON/OFF operation of the streamer.
2) The Streamer function operates only when the fan and air conditioning operation are stopped. BAPWS55A61
The maximum operation of Streamer is 180 minutes per day.
213
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗