Back to resultsSpecification results
Daikin FXFTQ-A / FXFSQ-C — representative product image
Representative image · Vietnamese catalogue, PDF 180 ↗

FXFTQ40AVM

Daikin · Cassette Round Flow with sensor and Streamer

FXFTQ40AVM is a Daikin indoor unit in the FXFTQ-A / FXFSQ-C series, cassette round flow with sensor and streamer type. Its rated cooling capacity is 4.5 kW according to catalogue PCVVN2507Aaprv.

Rated cooling capacity
4.5 kW
Power supply
1-phase, 220-240 V/220-230 V, 50/60 Hz
Dimensions (H×W×D)
256×840×840 mm
Weight
19 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
Open comparison tool →

FXFTQ40AVM specifications

FXFTQ40AVM specifications · PCVVN2507Aaprv
Rated capacity 4 specifications
Cooling capacity · Btu/h15,400
Cooling capacity · kW4.5
Heating capacity · Btu/h17,100
Heating capacity · kW5.0
Electrical & efficiency 3 specifications
Power supply1-phase, 220-240 V/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.035
Power consumption · Heating · kW0.034
Airflow & sound 3 specifications
Airflow rate (H/HM/M/ML/L) · m3/min17/13.5/12.5/12/11
Airflow rate (H/HM/M/ML/L) · cfm600/477/441/424/388
Sound level (H/HM/M/ML/L) · dB(A)35/29.5/29/28/27
Dimensions & weight 3 specifications
CasingGalvanised steel plate
Dimensions (H×W×D) · mm256×840×840
Machine weight · kg19
Piping & refrigerant 3 specifications
Piping connections · Liquid (Flare) · mm6.4
Piping connections · Gas (Flare) · mm12.7
Piping connections · Drain · mmVP25 (External Dia. 32/Internal Dia. 25)

Catalogue source & rating conditions

Values are taken from PCVVN2507Aaprv, PDF page 185 (printed page 184). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).

Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.

Read original source notes (English)
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Panel (Option) Function List Model BYCQ125EEF (Fresh White) Wired Wireless Dimensions(H×W×D) mm 50×950×950 Remote controller FXFTQ-A FXFSQ-C FXFSQ-C Standard panel Weight kg 5.5 BRC1H63W(K) BRC1H63W(K) BRC1E63 BRC7M635F(K) / BRC7M634F(K) with Model BYCQ125EEK (Black) Streamer function unit sensing Dimensions(H×W×D) mm 50×950×950 Dual sensors *1 Weight kg 5.5 Auto airflow function (Direct airflow) *1 Auto airflow function (Draft prevention) *1 Sensing sensor low mode *1 Sensing sensor stop mode *1 Circulation airflow *2 Individual airflow direction control Switchable 5 step fan speed Auto airflow rate Auto swing Selectable airflow pattern *1 High ceiling application *1. Applicable when sensing panel is installed. *2. Refer to Circulation airflow on page 189 for details. 184 stinU roodnI
View catalogue page · PDF 185

The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Original English catalogue, PDF page 185
Read all text from this page and its facing page
PDF page 185 VRV Indoor Units Specifications MODEL FXFTQ25AVM FXFTQ32AVM FXFTQ40AVM FXFTQ50AVM FXFTQ63AVM FXFTQ80AVM FXFTQ100AVM FXFTQ125AVM FXFTQ140AVM Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600 Cooling capacity kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0 Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 42,700 54,600 Heating capacity kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 Cooling 0.028 0.035 0.056 0.061 0.092 0.164 0.170 0.194 Power consumption kW Heating 0.026 0.034 0.056 0.060 0.092 0.144 0.159 0.183 Casing Galvanised steel plate m3/min 13/12.5/11.5/11/10 17/13.5/12.5/12/11 23/20.5/19/14.5/11 23.5/21/20/16/13.5 24.5/22/20.5/20/15 33.5/30.5/27/23.5/2134.5/31.5/28.5/25.5/2335.5/32.5/29.5/26.5/23 Airflow rate (H/HM/M/ML/L) cfm 459/441/406/388/353 600/477/441/424/388 812/724/671/512/388 830/741/706/565/477 865/777/724/706/530 1,183/1,077/953/830/7411,218/1,112/1,006/900/8121,253/1,147/1,041/935/812 Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 38/35/34.5/29.5/27 38/36/35.5/31.5/28 39/37/36/35.5/31 44/41/38/35/33 45/42.5/39.5/37/3546/43.5/40.5/38/35 Dimensions (H×W×D) mm 256×840×840 298×840×840 Machine weight kg 19 24 22 25 26 Liquid (Flare) 6.4 9.5 Piping connections Gas (Flare) mm 12.7 15.9 Drain VP25 (External Dia. 32/Internal Dia. 25) MODEL FXFSQ25CVM FXFSQ50CVM Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Btu/h 9,600 19,100 Cooling capacity kW 2.8 5.6 Btu/h 10,900 21,500 Heating capacity kW 3.2 6.3 Cooling 0.035 0.056 Power consumption kW Heating 0.035 0.056 Casing Galvanised steel plate m3/min 19/15.5/14.5/12.5/11 28.5/27/25.5/24/23 Airflow rate (H/HM/M/ML/L) cfm 671/547/512/441/388 1,006/953/900/847/812 Sound level (H/HM/M/ML/L) dB(A) 34.5/32/29.5/28.5/27 39.5/38.0/37.0/36.0/35.0 Dimensions (H×W×D) mm 256×840×840 298×840×840 Machine weight kg 24 25 Liquid 6.4 Piping connections Gas mm 12.7 Drain VP25 (External dia. 32/Internal dia. 25) Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Panel (Option) Function List Model BYCQ125EEF (Fresh White) Wired Wireless Dimensions(H×W×D) mm 50×950×950 Remote controller FXFTQ-A FXFSQ-C FXFSQ-C Standard panel Weight kg 5.5 BRC1H63W(K) BRC1H63W(K) BRC1E63 BRC7M635F(K) / BRC7M634F(K) with Model BYCQ125EEK (Black) Streamer function unit sensing Dimensions(H×W×D) mm 50×950×950 Dual sensors *1 Weight kg 5.5 Auto airflow function (Direct airflow) *1 Auto airflow function (Draft prevention) *1 Sensing sensor low mode *1 Sensing sensor stop mode *1 Circulation airflow *2 Individual airflow direction control Switchable 5 step fan speed Auto airflow rate Auto swing Selectable airflow pattern *1 High ceiling application *1. Applicable when sensing panel is installed. *2. Refer to Circulation airflow on page 189 for details. 184 stinU roodnI FACING PAGE — PDF page 184 Round Flow Cassette with Sensing and Streamer Type Other functions Quick and easy installation Installable in tight ceiling spaces 850 mm Min. of 261 mm* ceiling space when using standard panel. 175 mm * For FXFTQ25-80A models. Drain pump is equipped as standard accessory with 850 mm lift. Easy maintenance Just open the suction grille! Drain pan and drain water check Drain outlet The condition of the drain pan and drain water can be (with rubber plug) checked by removing the suction grille and drain plug. Note: For inquiries concerning auto grille panel installations, please contact your local dealer or Daikin representative. Cleanliness Silver ion anti-bacterial drain pan Prevents the growth of slime, bacteria, and mould that cause odours and clogging. * Drain pan should be changed once every two to three years. Filter has anti-mould and antibacterial treatment BAF552A160 High Performance Prefilter (MERV 8) (Option) See page 296 This filter can catch more harmful substances in the air such as PM2.5. UV Streamer air purifier unit (Option for FXFSQ-C only) See page 5 - 6 Adopts “deep ultraviolet (UVC) LED” which irradiates deep ultraviolet rays with a wavelengths of around 265 nm that have a high sterilizing effect. Antibacterial / Antiviral filter MERV 13 rating Promotion Movie BAEF125AW1 Panel (Option) Standard panel with sensing Standard panel with sensing 183 BYCQ125EEF (Fresh White) BYCQ125EEK (Black)

Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗