FXEQ25AV36 is a Daikin indoor unit in the FXEQ-A series, 1-way cassette type. Its rated cooling capacity is 2.8 kW according to catalogue PCVVN2507Aaprv.
- Rated cooling capacity
- 2.8 kW
- Power supply
- 1-phase, 220-240 V, 50 Hz
- Dimensions (H×W×D)
- 200×840×470 mm
- Weight
- 17 kg
Data extracted from the English catalogue; not all specifications have been manually verified. Check the source before use. Source & notes →
FXEQ25AV36 specifications
| Rated capacity 4 specifications | |
|---|---|
| Cooling capacity · Btu/h | 9,600 |
| Cooling capacity · kW | 2.8 |
| Heating capacity · Btu/h | 10,900 |
| Heating capacity · kW | 3.2 |
| Electrical & efficiency 3 specifications | |
| Power supply | 1-phase, 220-240 V, 50 Hz |
| Power consumption · Cooling · kW | 0.027 |
| Power consumption · Heating · kW | 0.023 |
| Airflow & sound 6 specifications | |
| Airflow rate (H/HM/M/ML/L) · Cooling · m3/min | 6.9/6.4/5.8/5.3/4.8 |
| Airflow rate (H/HM/M/ML/L) · Cooling · cfm | 244/226/205/187/169 |
| Airflow rate (H/HM/M/ML/L) · Heating · m3/min | 7.2/6.7/6.1/5.6/5.0 |
| Airflow rate (H/HM/M/ML/L) · Heating · cfm | 254/237/215/198/177 |
| Sound level (H/HM/M/ML/L) · Cooling · dB(A) | 32/31/30/29/28 |
| Sound level (H/HM/M/ML/L) · Heating · dB(A) | 35/33/31/30/28 |
| Dimensions & weight 3 specifications | |
| Casing | Galvanised steel plate |
| Dimensions (H×W×D) · mm | 200×840×470 |
| Machine weight · kg | 17 |
| Piping & refrigerant 3 specifications | |
| Piping connections · Liquid (Flare) · mm | 6.4 |
| Piping connections · Gas (Flare) · mm | 12.7 |
| Piping connections · Drain · mm | PVC26 (External Dia. 26/Internal Dia. 20) |
| Controls & accessories 4 specifications | |
| Panel (Option) · Model | BYEP40AW1 |
| Panel (Option) · Colour | Fresh white |
| Panel (Option) · Dimensions(H×W×D) · mm | 80×950×550 |
| Panel (Option) · Weight · kg | 8.0 |
No matching specifications. Try another search term.
Catalogue source & rating conditions
Values are taken from PCVVN2507Aaprv, PDF page 199 (printed page 198). General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN).
Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
198
stinU
roodnI
View catalogue page · PDF 199
The original page preserves symbols, merged cells and accessories; not every accessory shown is supplied with the unit.

Read all text from this page and its facing page
PDF page 199
VRV Indoor Units
Specifications
MODEL FXEQ20AV36 FXEQ25AV36 FXEQ32AV36 FXEQ40AV36 FXEQ50AV36 FXEQ63AV36
Power supply 1-phase, 220-240 V, 50 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating capacity
kW 2.5 3.2 4.0 5.0 6.3 8.0
Power Cooling 0.026 0.027 0.034 0.046 0.048 0.067
kW
consumption Heating 0.022 0.023 0.030 0.042 0.044 0.063
Casing Galvanised steel plate
m3/min 6.0/5.4/4.9/4.4/4.0 6.9/6.4/5.8/5.3/4.8 8.0/7.5/7.0/6.3/5.5 9.8/8.8/7.8/7.0/6.2 12.5/11.4/10.4/9.5/8.7 15.0/13.6/12.2/11.0/9.8
Cooling
Airflow rate cfm 212/191/173/155/141 244/226/205/187/169 282/265/247/222/194 346/311/275/247/219 441/402/367/335/307 530/480/431/388/346
(H/HM/M/ML/L) m3/min 6.0/5.6/5.1/4.7/4.2 7.2/6.7/6.1/5.6/5.0 8.6/8.0/7.4/6.7/6.0 10.2/9.3/8.4/7.6/6.8 14.0/12.8/11.6/10.7/9.8 16.9/15.3/13.6/12.3/11.0
Heating
cfm 212/198/180/166/148 254/237/215/198/177 304/282/261/237/212 360/328/297/268/240 494/452/409/378/346 597/540/480/434/388
Sound level Cooling 30/29/28/27/26 32/31/30/29/28 35/34/33/32/30 38/37/35/33/31 38/37/35/33/31 43/41/39/37/35
dB(A)
(H/HM/M/ML/L) Heating 33/31/29/28/26 35/33/31/30/28 38/36/34/33/31 41/39/37/35/33 41/39/37/36/34 46/44/42/40/38
Dimensions (H×W×D) mm 200×840×470 200×1,240×470
Machine weight kg 17 18 23
Liquid (Flare) 6.4 9.5
Piping
Gas (Flare) mm 12.7 15.9
connections
Drain PVC26 (External Dia. 26/Internal Dia. 20)
Model BYEP40AW1 BYEP63AW1
Panel Colour Fresh white
(Option) Dimensions(H×W×D) mm 80×950×550 80×1,350×550
Weight kg 8.0 10.0
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
198
stinU
roodnI
FACING PAGE — PDF page 198
Single Flow Cassette Type
FXEQ-A
Slim design for flexible installation
Slim design
Trave
447700 mmmm
• The body features a compact design with a 884400 mmmm
height of just 200 mm and depth 470 mm, Indoor unit 200 mm 255 mm
making the installation possible in tight 80 mm
ceiling spaces. 225555 mmmm
• The novel smooth panel design makes dust difficult to accumulate,
thus causing the cleaning more conveniently.
Comfort
• The swinging of horizontal and vertical swing
Front view Side view
flaps can be adjusted freely with the remote
controller, providing 3D airflow to every
corner of the room.
• Control of airflow rate can be selected from
5-step control, Automatic and quiet operation
mode, which provides comfortable airflow.
• DC motor is adopted both in the fan and
drain pump of the indoor unit, not only
enhancing the energy saving performance,
but also reducing the operating sound and
the vibration incurred to the unit.
Vertical swing flaps, Horizontal swing flaps,
swinging to swinging between
• While creating a cozy indoor environment, left or right within 45° 20° 70°
to
the unit can prevent the suspended ceiling
from being soiled by adjusting its louvre
angle.
Easy maintenance
• Drain pump is equipped as standard accessory • Maintenance
with 850 mm lift. operations can be
performed by
removing the front
panel.
197
Catalogue article on VRV.vn ↗ · Original English PDF on VRV.vn ↗