VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

VAM2000HVE

Other equipment · VAM-HVE · Heat recovery ventilation unit

Data based on the source catalogue; not all specifications have been manually verified. Check the original source before use.

VAM2000HVE specifications
System configuration
Heat exchange systemCounterflow total heat exchange (latent and sensible)
Heat exchange mediumNon-flammable paper
Electrical & efficiency
Power supply1 phase, 220–240 V / 220 V, 50/60 Hz
Temperature exchange efficiency · Cooling, extra high (50/60 Hz) · %58.5/58.5
Temperature exchange efficiency · Cooling, high (50/60 Hz) · %58.5/58.5
Temperature exchange efficiency · Cooling, low (50/60 Hz) · %65.5/65.5
Temperature exchange efficiency · Heating, extra high (50/60 Hz) · %73.5/73.5
Temperature exchange efficiency · Heating, high (50/60 Hz) · %73.5/73.5
Temperature exchange efficiency · Heating, low (50/60 Hz) · %76.5/77.0
Enthalpy exchange efficiency · Cooling, extra high (50/60 Hz) · %60.0/60.0
Enthalpy exchange efficiency · Cooling, high (50/60 Hz) · %60.0/60.0
Enthalpy exchange efficiency · Cooling, low (50/60 Hz) · %64.5/64.5
Enthalpy exchange efficiency · Heating, extra high (50/60 Hz) · %68.0/68.0
Enthalpy exchange efficiency · Heating, high (50/60 Hz) · %68.0/68.0
Enthalpy exchange efficiency · Heating, low (50/60 Hz) · %71.0/71.5
Power consumption · Heat exchange, extra high (50/60 Hz) · W1,365–1,471/1,763
Power consumption · Heat exchange, high (50/60 Hz) · W1,241–1,311/1,526
Power consumption · Heat exchange, low (50/60 Hz) · W1,079–1,138/1,188
Power consumption · Bypass, extra high (50/60 Hz) · W1,365–1,471/1,763
Power consumption · Bypass, high (50/60 Hz) · W1,241–1,311/1,526
Power consumption · Bypass, low (50/60 Hz) · W1,079–1,138/1,188
Fan motor output · kW0.190 × 4
Airflow & sound
Sound level · Heat exchange, extra high (50/60 Hz) · dB(A)43.5–44.0/44.5
Sound level · Heat exchange, high (50/60 Hz) · dB(A)41.5–43.0/40.0
Sound level · Heat exchange, low (50/60 Hz) · dB(A)39.0–41.0/36.5
Sound level · Bypass, extra high (50/60 Hz) · dB(A)43.5–44.0/44.5
Sound level · Bypass, high (50/60 Hz) · dB(A)41.5–43.0/40.0
Sound level · Bypass, low (50/60 Hz) · dB(A)39.0–41.0/36.5
Fan typeSirocco fan
Airflow at extra high speed (50/60 Hz) · m³/h2,000/2,000
External static pressure at extra high speed (50/60 Hz) · Pa190–210/210
Airflow at high speed (50/60 Hz) · m³/h2,000/2,000
External static pressure at high speed (50/60 Hz) · Pa140–180/85
Airflow at low speed (50/60 Hz) · m³/h1,650/1,580
External static pressure at low speed (50/60 Hz) · Pa96–123/53
Effective supply airflow ratio, extra high · %90
Dimensions & weight
CasingGalvanized steel
InsulationNon-flammable polyurethane foam
Dimensions (H×W×D) · mm785×1,012×1,110
Weight · kg133
Piping & refrigerant
Inner duct connection · mmØ250 × 4
Outer duct connection · mm□ (680 × 290) × 2
Operating conditions
Ambient operating conditions−15 to 50 °CDB, up to 80% RH
Filters
Air filterMulti-directional fibre mat

Source reference

VN-PCXDHMT2111A · PDF page 11 · Printed page 10
Vietnamese source PDF · English specifications translated from the source

Open catalogue PDF · page 11
Model page: https://vrv.vn/spec/vam2000hve/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Catalogue notes (summary)

Notes: Pairs are in 50/60 Hz order. The catalogue cites JIS B8628:2017 for heat exchange and sound testing. The reference table on PDF page 13 uses VAM-G test conditions. Use the main VAM-HVE tables on PDF pages 10–11.