TECHNICAL SPECIFICATION SHEET · DAIKIN
VAM1500HVE
Other equipment · VAM-HVE · Heat recovery ventilation unit
Data based on the source catalogue; not all specifications have been manually verified. Check the original source before use.
| System configuration | |
|---|---|
| Heat exchange system | Counterflow total heat exchange (latent and sensible) |
| Heat exchange medium | Non-flammable paper |
| Electrical & efficiency | |
| Power supply | 1 phase, 220–240 V / 220 V, 50/60 Hz |
| Temperature exchange efficiency · Cooling, extra high (50/60 Hz) · % | 61.5/61.5 |
| Temperature exchange efficiency · Cooling, high (50/60 Hz) · % | 61.5/61.5 |
| Temperature exchange efficiency · Cooling, low (50/60 Hz) · % | 65.5/66.0 |
| Temperature exchange efficiency · Heating, extra high (50/60 Hz) · % | 77.5/77.5 |
| Temperature exchange efficiency · Heating, high (50/60 Hz) · % | 77.5/77.5 |
| Temperature exchange efficiency · Heating, low (50/60 Hz) · % | 79.5/80.0 |
| Enthalpy exchange efficiency · Cooling, extra high (50/60 Hz) · % | 63.0/63.0 |
| Enthalpy exchange efficiency · Cooling, high (50/60 Hz) · % | 63.0/63.0 |
| Enthalpy exchange efficiency · Cooling, low (50/60 Hz) · % | 65.5/66.0 |
| Enthalpy exchange efficiency · Heating, extra high (50/60 Hz) · % | 72.0/72.0 |
| Enthalpy exchange efficiency · Heating, high (50/60 Hz) · % | 72.0/72.0 |
| Enthalpy exchange efficiency · Heating, low (50/60 Hz) · % | 74.0/75.0 |
| Power consumption · Heat exchange, extra high (50/60 Hz) · W | 1,274–1,353/1,645 |
| Power consumption · Heat exchange, high (50/60 Hz) · W | 1,207–1,225/1,423 |
| Power consumption · Heat exchange, low (50/60 Hz) · W | 1,008–1,089/1,125 |
| Power consumption · Bypass, extra high (50/60 Hz) · W | 1,274–1,353/1,645 |
| Power consumption · Bypass, high (50/60 Hz) · W | 1,207–1,225/1,423 |
| Power consumption · Bypass, low (50/60 Hz) · W | 1,008–1,089/1,125 |
| Fan motor output · kW | 0.190 × 4 |
| Airflow & sound | |
| Sound level · Heat exchange, extra high (50/60 Hz) · dB(A) | 43.0–44.0/44.0 |
| Sound level · Heat exchange, high (50/60 Hz) · dB(A) | 41.0–42.5/39.0 |
| Sound level · Heat exchange, low (50/60 Hz) · dB(A) | 38.0–40.5/35.0 |
| Sound level · Bypass, extra high (50/60 Hz) · dB(A) | 43.0–44.0/44.0 |
| Sound level · Bypass, high (50/60 Hz) · dB(A) | 41.0–42.5/39.0 |
| Sound level · Bypass, low (50/60 Hz) · dB(A) | 38.0–40.5/35.0 |
| Fan type | Sirocco fan |
| Airflow at extra high speed (50/60 Hz) · m³/h | 1,500/1,500 |
| External static pressure at extra high speed (50/60 Hz) · Pa | 195–215/235 |
| Airflow at high speed (50/60 Hz) · m³/h | 1,500/1,500 |
| External static pressure at high speed (50/60 Hz) · Pa | 150–180/125 |
| Airflow at low speed (50/60 Hz) · m³/h | 1,350/1,250 |
| External static pressure at low speed (50/60 Hz) · Pa | 123–146/88 |
| Effective supply airflow ratio, extra high · % | 90 |
| Dimensions & weight | |
| Casing | Galvanized steel |
| Insulation | Non-flammable polyurethane foam |
| Dimensions (H×W×D) · mm | 785×1,012×1,110 |
| Weight · kg | 133 |
| Piping & refrigerant | |
| Inner duct connection · mm | Ø250 × 4 |
| Outer duct connection · mm | □ (680 × 290) × 2 |
| Operating conditions | |
| Ambient operating conditions | −15 to 50 °CDB, up to 80% RH |
| Filters | |
| Air filter | Multi-directional fibre mat |
Source reference
VN-PCXDHMT2111A · PDF page 11 · Printed page 10
Vietnamese source PDF · English specifications translated from the source
Open catalogue PDF · page 11
Model page: https://vrv.vn/spec/vam1500hve/
Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.
Catalogue notes (summary)
Notes: Pairs are in 50/60 Hz order. The catalogue cites JIS B8628:2017 for heat exchange and sound testing. The reference table on PDF page 13 uses VAM-G test conditions. Use the main VAM-HVE tables on PDF pages 10–11.