VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

RZUR250PY1

Outdoor unit · RZUR-P · Packaged · Cooling only · Inverter air cooled Packaged · R-410A

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

RZUR250PY1 specifications
System configuration
Unit combinationFVGR250PV1 + RZUR250PY1
Rated capacity
Cooling capacity (19.5°CWB) *1 · kW27.00
Cooling capacity (19.5°CWB) *1 (Max.) · kW27.00 (28.40)
Cooling capacity (19.5°CWB) *1 (Max.) · Btu/h92,000 (97,000)
Cooling capacity (19°CWB) *2 (Max.) · kW26.70 (28.10)
Cooling capacity (19°CWB) *2 (Max.) · Btu/h91,000 (96,000)
Electrical & efficiency
System power consumption (19.5°CWB) *1 · kW9.58
System power consumption (19°CWB) *2 · kW9.46
CSPF (19°CWB) *24.20
Power supply3 Phase, 380–415 V, 50 Hz
Compressor · TypeHermetically sealed scroll type
Compressor · Motor output · kW4.5×1
Airflow & sound
Air flow rate (H) · m³/min178
Sound level *4 · dB(A)57
Dimensions & weight
Casing colourIvory White
Dimensions (H×W×D) · mm1,657×930×765
Machine weight · kg185
Piping & refrigerant
Refrigerant · TypeR-410A
Refrigerant charge · kg6.7
Refrigerant piping · Liquid · mmØ 9.5 (Brazing)
Refrigerant piping · Gas · mmØ 22.2 (Brazing)
Max. piping length · m70 (equivalent length 90 m)
Max. level difference · m50
Operating conditions
Operation range · °CDB10 to 49

Source reference

PCTPMT2309 · PDF page 4 · Printed page 5
Daikin Inverter Air Cooled Packaged · PCTPMT2309

Open catalogue PDF · page 4
Model page: https://vrv.vn/spec/rzur250py1/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Note:
*1. Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*2. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
*3. Capacity is net, including a deduction for cooling for indoor fan motor heat.
*4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. Consider location and soundproofing measures near residences.
*5. The value is the external static pressure with standard pulley.
*6. Max. 40 m if the outdoor unit is lower than the indoor unit.
Packaged system: cooling capacity, system power consumption and CSPF refer to the stated indoor/outdoor pairing. Outdoor model pages use the FDR pairing as the reference, except the RZUR-P models, which use their respective FVGR-P pairings. Parenthetical capacities are the source maximum values. Optional equipment is shown separately in the PDF.