VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

RXUQ10AYMW

Outdoor unit · VRV X/A MAX · Corrosion resistant

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

RXUQ10AYMW specifications
System configuration
Combination units— / — / —
Rated capacity
Cooling capacity · Btu/h95,500
Cooling capacity · kW28.0
Electrical & efficiency
Power supply3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Power consumption · kW6.29
Capacity control · %13-100
Compressor · TypeHermetically sealed scroll type
Compressor · Motor output · kW4.2×1
Airflow & sound
Airflow rate · m3/min178
Sound level · dB(A)56
Dimensions & weight
Casing colourMetallic brown
Dimensions (H×W×D) · mm1,657×1,240×765
Machine weight · kg(235)
Piping & refrigerant
Refrigerant · TypeR-410A
Refrigerant · Charge · kg8.3
Piping connections · Liquid · mm9.5 (Brazing)
Piping connections · Gas · mm22.2 (Brazing)
Operating conditions
Operation range · °CDB10 to 49

Source reference

PCVVN2507Aaprv · PDF page 112 · Printed page 111
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 112
Model page: https://vrv.vn/spec/rxuq10aymw/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
111