TECHNICAL SPECIFICATION SHEET · DAIKIN
RWHQ42THYM
Outdoor unit · VRV IV Hot water heat recovery · Hot water heat recovery
Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.
| System configuration | |
|---|---|
| Combination units | RWHQ14TYM / RWHQ14TYM / RWHQ14TYM |
| Rated capacity | |
| Cooling capacity · Btu/h | 409,000 |
| Cooling capacity · kW | 120 |
| Electrical & efficiency | |
| Power supply | 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz |
| Power consumption · kW | 32.4 |
| Capacity control · % | 4-100 |
| Compressor · Type | Hermetically Sealed Scroll Type |
| Compressor · Motor output · kW | (2.9x1)+(3.3x1)+(2.9x1)+ (3.3x1)+(2.9x1)+(3.3x1) |
| Airflow & sound | |
| Airflow rate · m3/min | 233+233+233 |
| Sound level · dB(A) | 65 |
| Dimensions & weight | |
| Casing colour | Ivory white (5Y7.5/1) |
| Dimensions (H×W×D) · mm | (1,657x1,240x765)+(1,657x1,240x765)+(1,657x1,240x765) |
| Machine weight · kg | 285+285+285 |
| Piping & refrigerant | |
| Refrigerant · Type | R-410A |
| Refrigerant · Charge · kg | 10.3+10.3+10.3 |
| Piping connections (Indoor unit) · Liquid · mm | 19.1(Brazing) |
| Piping connections (Indoor unit) · Gas · mm | 41.3( B razing) |
| Piping connections (Heat exchanger unit) · Inlet pipe · mm | 19.1(Brazing x 3) |
| Piping connections (Heat exchanger unit) · Outlet pipe · mm | 19.1(Brazing x 3) |
| Operating conditions | |
| Operation range · ºCDB | 15 to 49 |
Source reference
PCVVN2507Aaprv · PDF page 170 · Printed page 169
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)
Open catalogue PDF · page 170
Model page: https://vrv.vn/spec/rwhq42thym/
Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.
Original source notes
Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.