RWHQ30THYM specifications
System configuration
Combination unitsRWHQ8TYM / RWHQ10TYM / RWHQ12TYM
Rated capacity
Cooling capacity · Btu/h286,000
Cooling capacity · kW83.9
Electrical & efficiency
Power supply3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Power consumption · kW21.3
Capacity control · %5-100
Compressor · TypeHermetically Sealed Scroll Type
Compressor · Motor output · kW(3.4x1)+(4.1x1)+ (5.2x1)
Airflow & sound
Airflow rate · m3/min157+165+178
Sound level · dB(A)62
Dimensions & weight
Casing colourIvory white (5Y7.5/1)
Dimensions (HxWxD) · mm(1,657x930x765)+(1,657x930x765)+(1,657x930x765)
Machine weight · kg185+200+200
Piping & refrigerant
Refrigerant · TypeR-410A
Refrigerant · Charge · kg6.4+6.5+6.8
Piping connections (Indoor unit) · Liquid · mm19.1(Brazing)
Piping connections (Indoor unit) · Gas · mm34.9(Brazing)
Piping connections (Heat exchanger unit) · Inlet pipe · mm19.1(Brazing x 3)
Piping connections (Heat exchanger unit) · Outlet pipe · mm—
Operating conditions
Operation range · °CDB15 to 49

Source reference

PCVVN2507Aaprv · PDF page 171 · Printed page 170
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 171
Model page: https://vrv.vn/spec/rwhq30thym/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.