TECHNICAL SPECIFICATION SHEET · DAIKIN

RWEYQ26TYM

Outdoor unit · VRV IV W · Water cooled

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

RWEYQ26TYM specifications
System configuration
Combination unitsRWEYQ8TYM / RWEYQ8TYM / RWEYQ10TYM
Rated capacity
Cooling capacity · Btu/h248,000
Cooling capacity · kW72.8
Heating capacity · Btu/h278,000
Heating capacity · kW81.5
Electrical & efficiency
Power supply3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Power consumption · Cooling · kW13.2
Power consumption · Heating · kW13.6
Compressor · TypeHermetically sealed scroll type
Compressor · Motor output · kW2.8 × 2 + 3.7
Capacity control · %21-100
Airflow & sound
Sound level · dB(A)55
Dimensions & weight
Casing colourlvory white (5Y7.5/1)
Dimensions (H × W × D) · mm(1,000 × 780 × 550) × 3
Machine weight (Operating weight) · kg146 × 2 + 147 (148 × 2 + 149)
Piping & refrigerant
Refrigerant piping connections · Liquid · mm19.1 (Flare)
Refrigerant piping connections · Suction gas *1 · mm34.9 (Brazing)
Refrigerant piping connections · High and low pressure gas · mm28.6*2, 34.9*3 (Brazing)
Water piping connections · Water inlet(PT1 1/4B) × 3 internal thread
Water piping connections · Water outlet(PT1 1/4B) × 3 internal thread
Water piping connections · Drain outlet(PS1/2B) × 3 internal thread
Refrigerant · TypeR-410A
Refrigerant · Charge · kg3.5 + 3.5 + 4.2
Operating conditions
Operation range (Inlet water temp.) · °C10 to 45

Source reference

PCVVN2507Aaprv · PDF page 162 · Printed page 161
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 162
Model page: https://vrv.vn/spec/rweyq26tym/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes:
1. Specifications are based on the following
RWEYQ10TYM RWEYQ12TYM RWEYQ12TYM
conditions:
RWEYQ12TYM RWEYQ12TYM RWEYQ12TYM • Cooling: Indoor temp.: 27ºCDB, 19ºCWB / inlet
3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz water temp.:30ºC, Equivalent piping
length: 7.5 m, Height difference: 0 m.
305,000 324,000 345,000
• Heating: Indoor temp.: 20ºCDB / inlet water
89.5 95.0 101 temp.: 20ºC, Equivalent piping length: 7.5 m,
345,000 365,000 386,000 Height difference: 0 m.
• Sound level: Anechoic chamber conversion
101 107 113 value, measured at a point 1 m in
18.2 20.1 22.0 front of the unit at a height of
1.5 m.
19.1 21.3 23.6
During actual operation, these
lvory white (5Y7.5/1) values are normally somewhat
(1,000 × 780 × 550) × 3 higher as a result of ambient
conditions and oil recovery mode.
Hermetically sealed scroll type When there is concern for noise to
3.7 × 2 + 4.7 3.7 + 4.7 × 2 4.7 × 3 the surrounding area such as
19.1 (Flare) residences, we recommend
investigating the installation
34.9 (Brazing) location and taking soundproofing
28.6*2, 34.9*3 (Brazing) measures.
2. This unit cannot be installed in the outdoors.
(PT1 1/4B) × 3 internal thread
Install indoors (Machine room, etc).
(PT1 1/4B) × 3 internal thread 3. Hold ambient temperature at 0 – 40ºC and
(PS1/2B) × 3 internal thread humidity at 80%RH or less. Heat rejection from
the casing: 0.51 kW / 6 - 8 HP / hour, 0.58 kW /
147 × 3 (149 × 3) 10 - 12 HP / hour.
57 58 4. Connectable to closed type cooling tower only.
10 to 45 *1: In the case of heat pump system, suction gas
pipe is not used.
19-100 *2: In the case of heat recovery system.
R-410A *3: In the case of heat pump system.
• Be sure to refer to the Engineering Data Book for
4.2 + 4.2 + 4.2
facility design.
162
seireS
W
VI
VRV
VRV IV W
Series