TECHNICAL SPECIFICATION SHEET · DAIKIN

FXVQ500NY1

Indoor unit · FXVQ-N · Ducted floor standing

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FXVQ500NY1 specifications
Rated capacity
Cooling capacity · Btu/h191,000
Cooling capacity · kW56.0
Heating capacity · Btu/h215,000
Heating capacity · kW63.0
Electrical & efficiency
Power supply3-phase 4-wire system, 380–415 V, 50 Hz
Power consumption · Cooling · kW2.62
Power consumption · Heating · kW2.62
Airflow & sound
Sound level *1 · dB(A)62
Fan · Motor output · kW3.7
Fan · Airflow rate · m3/min165
Fan · Airflow rate · cfm5,825
Fan · External static pressure *2 · Pa142
Fan · Drive systemBelt drive system
Dimensions & weight
Casing colourIvory white (5Y7.5/1)
Dimensions (H × W × D) · mm1,900×1,470×720
Machine weight · kg281
Piping & refrigerant
Piping connections · Liquid · mm15.9 (Brazing)
Piping connections · Gas · mm28.6 (Brazing)
Piping connections · Drain · mmRp1 (PS 1B internal thread)
Filters
Air filter · TypeLong-life filter (anti-mould resin net)

Source reference

PCVVN2507Aaprv · PDF page 221 · Printed page 220
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 221
Model page: https://vrv.vn/spec/fxvq500ny1/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
*1: Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
*2: The value is the external static pressure with standard pulley.