VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

FXSQ140PAVE

Indoor unit · FXSQ-PA · Concealed ceiling ducted medium static pressure

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FXSQ140PAVE specifications
Rated capacity
Cooling capacity · Btu/h54,600
Cooling capacity · kW16.0
Heating capacity · Btu/h61,400
Heating capacity · kW18.0
Electrical & efficiency
Power supply1-phase, 220-240 V/220 V, 50/60 Hz
Power consumption · Cooling · kW0.222*1
Power consumption · Heating · kW0.217*1
Airflow & sound
Airflow rate (H/M/L) · m3/min39/33.5/28
Airflow rate (H/M/L) · cfm1,377/1,183/988
External static pressure · Pa50-140 (50) *2
Sound level (H/M/L) · dB(A)43/40/36
Dimensions & weight
CasingGalvanised steel plate
Dimensions (H×W×D) · mm245×1,550×800
Machine weight · kg52
Piping & refrigerant
Piping connections · Liquid (Flare) · mm9.5
Piping connections · Gas (Flare) · mm15.9
Piping connections · Drain · mmVP25 (External Dia. 32/Internal Dia. 25)

Source reference

PCVVN2507Aaprv · PDF page 207 · Printed page 206
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 207
Model page: https://vrv.vn/spec/fxsq140pave/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes:
Dimensions (H×W×D) mm 245×550×800 245×700×800 245×1,000×800
Specifications are based on the following
Machine weight kg 25 27 35 conditions;
Liquid (Flare) 6.4 • Cooling: Indoor temp.: 27°CDB, 19°CWB,
P co ip n in n g e ctions Gas (Flare) mm 12.7 O pi u p t i d n o g o le r n te g m th p : . 7 : . 3 5 5 m °C , D H B e , i g Eq h u t i d v i a f l f e e n re t nce:
Drain VP25 (External Dia. 32/Internal Dia. 25) 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor
MODEL FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE temp.: 7°CDB, 6°CWB, Equivalent piping
length: 7.5 m, Height difference: 0 m.
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
• Capacity of indoor unit is only for
Btu/h 24,200 30,700 38,200 47,800 54,600 reference. Actual capacity of indoor unit
Cooling capacity kW 7.1 9.0 11.2 14.0 16.0 is based on the total capacity index. (See
Engineering Data Book for details.)
Btu/h 27,300 34,100 42,700 54,600 61,400 • Sound level: Anechoic chamber
Heating capacity
kW 8.0 10.0 12.5 16.0 18.0 conversion value, measured at a point
Power Cooling 0.106*1 0.126*1 0.151*1 0.206*1 0.222*1 1.5 m downward from the unit centre.
kW During actual operation, these values
consumption Heating 0.101*1 0.121*1 0.146*1 0.201*1 0.217*1 are normally somewhat higher as a
Casing Galvanised steel plate result of ambient conditions.
Airflow rate (H/M/L) m3/min 21/17.5/14.5 23/19.5/16 32/27/22.5 37/31.5/26 39/33.5/28 *1: Power consumption values are based
cfm 741/618/512 812/688/565 1,130/953/794 1,306/1,112/918 1,377/1,183/988 on conditions of rated external static
External static pressure Pa 50-150 (50) *2 50-140 (50) *2 pressure.
*2: External static pressure can be
Sound level (H/M/L) dB(A) 36/32/29 37.5/34/30 39/35/32 42/38.5/35 43/40/36 modified using a remote controller
Dimensions (H×W×D) mm 245×1,000×800 245×1,400×800 245×1,550×800 that offers thirteen (FXSQ20-40PA),
eleven (FXSQ50-125PA) or ten
Machine weight kg 35 37 46 47 52 (FXSQ140PA) levels of control. These
Liquid (Flare) 9.5 values indicate the lowest and highest
Piping Gas (Flare) mm 15.9 possible static pressures. The rated
connections static pressure is 50 Pa.
Drain VP25 (External Dia. 32/Internal Dia. 25)
206
stinU
roodnI
Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated airflow.
3. Actual duct resistance is calculated according to 1 and 2. (Refer to Engineering Data Book for details)
4. Fan speed is automatically adjusted to produce rated airflow. ”Airflow rate auto adjustment function” should be used at field setting only.