TECHNICAL SPECIFICATION SHEET · DAIKIN

FXMQ250PVM

Indoor unit · FXMQ-P · Concealed ceiling ducted high static pressure

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FXMQ250PVM specifications
Rated capacity
Cooling capacity · Btu/h95,500
Cooling capacity · kW28.0
Heating capacity · Btu/h107,500
Heating capacity · kW31.5
Electrical & efficiency
Power supply1-phase, 220-240 V/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.67 *1
Power consumption · Heating · kW0.65 *1
Airflow & sound
Airflow rate (HH/H/L) · m3/min84/71/58
Airflow rate (HH/H/L) · cfm2,965/2,506/2,047
External static pressure · Pa50-250 (150) *2
Sound level (HH/H/L) · dB(A)44/40/37
Dimensions & weight
CasingGalvanised steel plate
Dimensions (H × W × D) · mm470×1,490×1,100
Machine weight · kg105
Piping & refrigerant
Piping connections · Liquid (Flare) · mm9.5
Piping connections · Gas (Flange) · mm22.2
Piping connections · Drain · mmBSP1”

Source reference

PCVVN2507Aaprv · PDF page 211 · Printed page 210
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 211
Model page: https://vrv.vn/spec/fxmq250pvm/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Power consumption values are based on conditions of rated external static pressure.
*2: External static pressure can be modified using a remote controller that offers fifteen levels of control.
These values indicate the lowest and highest possible static pressures. The standard static pressure is 150 Pa.
210
stinU
roodnI
Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated
2. External static pressure is estimated from power input of DC fan because PCB
airflow. (Refer to Engineering Data Book for details)
of FXMQ-P has table of external static pressure vs. power input of DC fan.
”Airflow rate auto adjustment function” should be used at field setting only.
3. Actual duct resistance is calculated according to 1 and 2.
4. Fan speed is automatically adjusted to produce rated airflow.