VRV.vn

TECHNICAL SPECIFICATION SHEET · DAIKIN

FXFRQ50AVM

Indoor unit · FXFRQ-A · Cassette Round Flow with Streamer

Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.

FXFRQ50AVM specifications
Rated capacity
Cooling capacity · Btu/h19,100
Cooling capacity · kW5.6
Heating capacity · Btu/h21,500
Heating capacity · kW6.3
Electrical & efficiency
Power supply1-phase, 220-240 V/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.040
Power consumption · Heating · kW0.040
Airflow & sound
Airflow rate (H/HM/M/ML/L) · m3/min18/17/13.5/12.5/11
Airflow rate (H/HM/M/ML/L) · cfm635/600/477/441/388
Sound level (H/HM/M/ML/L) · dB(A)35/33.5/29.5/28.5/27
Dimensions & weight
CasingGalvanised steel plate
Dimensions (H×W×D) · mm256×840×840
Machine weight · kg19
Piping & refrigerant
Piping connections · Liquid (Flare) · mm6.4
Piping connections · Gas (Flare) · mm12.7
Piping connections · Drain · mmVP25 (External Dia. 32/Internal Dia. 25)

Source reference

PCVVN2507Aaprv · PDF page 189 · Printed page 188
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 189
Model page: https://vrv.vn/spec/fxfrq50avm/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Panel (Option) Function List
Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Wired remote controller BRC1H63W(K)
Standard
panel Dimensions(H×W×D) mm 50×950×950 Streamer function unit
Weight kg 5.5 Individual airflow direction control
Model BYCQ125EAPF (Fresh White) Switchable 5 step fan speed
Designer
panel Dimensions(H×W×D) mm 97×950×950 Auto airflow rate
Weight kg 6.5 Auto swing
Auto Model BYCQ125EBSF (Fresh White) High ceiling application
grille Dimensions(H×W×D) mm 105×950×950
panel
Weight kg 8
stinU
roodnI
188