TECHNICAL SPECIFICATION SHEET · DAIKIN
FXFQ40AVM
Indoor unit · FXFQ-A · Cassette Round Flow
Data extracted from the English catalogue; not all specifications have been manually verified. Check the original source before use.
| Rated capacity | |
|---|---|
| Cooling capacity · Btu/h | 15,400 |
| Cooling capacity · kW | 4.5 |
| Heating capacity · Btu/h | 17,100 |
| Heating capacity · kW | 5.0 |
| Electrical & efficiency | |
| Power supply | 1-phase, 220-240 V/220-230 V, 50/60 Hz |
| Power consumption · Cooling · kW | 0.036 |
| Power consumption · Heating · kW | 0.036 |
| Airflow & sound | |
| Airflow rate (H/HM/M/ML/L) · m3/min | 17/13.5/13/12/11 |
| Airflow rate (H/HM/M/ML/L) · cfm | 600/477/459/424/388 |
| Sound level (H/HM/M/ML/L) · dB(A) | 35/29.5/29/28/27 |
| Dimensions & weight | |
| Casing | Galvanised steel plate |
| Dimensions (H×W×D) · mm | 256×840×840 |
| Machine weight · kg | 19 |
| Piping & refrigerant | |
| Piping connections · Liquid (Flare) · mm | 6.4 |
| Piping connections · Gas (Flare) · mm | 12.7 |
| Piping connections · Drain · mm | VP25 (External Dia. 32/Internal Dia. 25) |
Source reference
PCVVN2507Aaprv · PDF page 193 · Printed page 192
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)
Open catalogue PDF · page 193
Model page: https://vrv.vn/spec/fxfq40avm/
Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.
Original source notes
Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.
Notes: Specifications are based on the following conditions; • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Decoration Panel (Option) Function List Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Wired Wireless Standard Remote controller panel Dimensions(H×W×D) mm 50×950×950 BRC1E63 BRC1H63W(K) BRC7M635/634F(K) Weight kg 5.5 Circulation airflow — — Model BYCQ125EAPF (Fresh White) Individual airflow direction control — Designer panel Dimensions(H×W×D) mm 97×950×950 Switchable 5 step fan speed Weight kg 6.5 Auto airflow rate Auto Model BYCQ125EBSF (Fresh White) Auto swing grille Dimensions(H×W×D) mm 105×950×950 Selectable airflow pattern panel Weight kg 8 High ceiling application — 192 stinU roodnI
Note: For inquiries concerning auto grille panel installations, please contact your local dealer or Daikin representative. Cleanliness UV Streamer air purifier unit (Option) See page 5 - 6 Adopts “deep ultraviolet (UVC) LED” which irradiates deep ultraviolet Antibacterial / rays with a wavelengths of around Antiviral filter 265 nm that have a high sterilizing MERV 13 rating Promotion effect. Movie BAEF125AW1 Silver ion anti-bacterial drain pan Prevents the growth of slime, bacteria, and mould that cause odours and clogging. * Drain pan should be changed once every two to three years. Filter has anti-mould and antibacterial treatment BAF552A160 High Performance Prefilter (MERV 8) (Option) See page 296 This filter can catch more harmful substances in the air such as PM2.5. 191