FXCQ80BVM specifications
Rated capacity
Cooling capacity · Btu/h30,700
Cooling capacity · kW9.0
Heating capacity · Btu/h34,100
Heating capacity · kW10.0
Electrical & efficiency
Power supply1-phase, 220-240 V/220-230 V, 50/60 Hz
Power consumption · Cooling · kW0.090
Power consumption · Heating · kW0.086
Airflow & sound
Airflow rate (H/HM/M/ML/L) · m3/min26/24/22.5/20.5/18.5
Airflow rate (H/HM/M/ML/L) · cfm918/847/794/724/653
Sound level (H/HM/M/ML/L) · dB(A)42/40/38/36/33
Dimensions & weight
CasingGalvanised steel plate
Dimensions (H × W × D) · mm305×1,445×620
Machine weight · kg33
Piping & refrigerant
Piping connections · Liquid (Flare) · mm9.5
Piping connections · Gas (Flare) · mm15.9
Piping connections · Drain · mmVP25 (External Dia. 32/Internal Dia. 25)
Controls & accessories
Panel (Option) · ModelBYBCQ125CF
Panel (Option) · ColourFresh white (6.5Y 9.5/0.5)
Panel (Option) · Dimensions (H×W×D) · mm55×1,740×700
Panel (Option) · Weight · kg13

Source reference

PCVVN2507Aaprv · PDF page 197 · Printed page 196
General Catalogue 2025; published on VRV.vn as Catalogue 2026 (EN)

Open catalogue PDF · page 197
Model page: https://vrv.vn/spec/fxcq80bvm/

Rated performance depends on test conditions and system combinations. “—” means no value was extracted. This sheet does not replace the manufacturer’s technical documentation.

Original source notes

Extracted from the catalogue page and its facing page, where available. Notes may refer to other models or optional accessories.

Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
196
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
stinU
roodnI
Cleanliness
Streamer filter clean unit (Option) See page 7 - 8
Irradiates Streamer when the fan and air conditioning operation are stopped.
Streamer fumigates the cabin and sterilizes the filter.
Remarks:
1) Only the stylish remote controller BRC1H63W(K) can be connected for ON/OFF operation of the streamer.
2) The Streamer function operates only when the fan and air conditioning operation are stopped. BAPWS55A61
The maximum operation of Streamer is 180 minutes per day.